Before using your air conditioner, please readthis manual carefully and keep it for future reference.ROOM AIR CONDITIONERPlease read this installation
9ELECTRICAL WORKBarCopper pipeClamp handleRed arrow markConeYokeHandleBarC: Putting nut onRemove flare nuts attached to indoor andoutdoor unit, then p
10Connect the cable to the outdoor unitELECTRICAL WORK1. Remove the electrical control board cover from the outdoor unit by loosening the screw.2. Con
After the confirmation of the above conditions, prepare the wiring as follows:1) Never fail to have an individualpower circuit specifically for the ai
When relocate the unit to another place, perform evacuation using vacuum pump.Make sure the refrigerant added into the air conditioner is liquid form
Perform the electric safe check after completing installation:1. Insulated resistanceThe insulated resistance must be more than 2M .2. Grounding workA
CS515-I120200019108120090618
Before using your air conditioner, please readthis manual carefully and keep it for future reference.ROOM AIR CONDITIONERPlease read this installation
1CONTENTSSAFETY PRECAUTIONSWarning ...
2WARNINGRead the follow SAFETYPRECAUTIONS carefully before installation.Electrical work must be installed by a licensed electrician. Be sure to use th
3Selecting installation placeRead completely, then follow step by step.Indoor unitDo not expose the indoor unit to heat or steam.Select a place where
1CONTENTSSAFETY PRECAUTIONSWarning ...
4AccessoriesINSTALLATION INSTRUCTIONSNote: Except the above parts provided, the other parts needed duringinstallation you must purchase.●●This illustr
5INSTALLATION INSTRUCTIONSIndoor unit installation2. Drill a hole in the wallFig.4Note:1. Fit the Installation Plate1. Fit the installation plate hori
6INSTALLATION INSTRUCTIONS1. For the left-hand and right-hand piping, remove the pipe cover from the side panel.Explain to clients that the pipe cover
7INSTALLATION INSTRUCTIONS5. Piping and wrappingBundle the tubing, connecting cable, anddrain hose with tape securely,evenly as shown in Fig.11.Becaus
8REFRIGERANT PIPE CONNECTIONSettlement of outdoor unitAnchor the outdoor unit witha bolt and nut 10 or 8 tightlyand horizontally on a concreteor rigid
9ELECTRICAL WORKBarCopper pipeClamp handleRed arrow markConeYokeHandleBarC: Putting nut onRemove flare nuts attached to indoor andoutdoor unit, then p
10Connect the cable to the outdoor unitELECTRICAL WORK1. Remove the electrical control board cover from the outdoor unit by loosening the screw.2. Con
After the confirmation of the above conditions, prepare the wiring as follows:1) Never fail to have an individual power circuit specifically for the a
When relocate the unit to another place, perform evacuation using vacuum pump.Make sure the refrigerant added into the air conditioner is liquid form
Perform the electric safe check after completing installation:1. Insulated resistanceThe insulated resistance must be more than 2M .2. Grounding workA
2WARNINGRead the follow SAFETYPRECAUTIONS carefully before installation.Electrical work must be installed by a licensed electrician. Be sure to use th
CS515-I2202000191083
3Selecting installation placeRead completely, then follow step by step.Indoor unitDo not expose the indoor unit to heat or steam.Select a place where
4AccessoriesINSTALLATION INSTRUCTIONSNote: Except the above parts provided, the other parts needed duringinstallation you must purchase.●●This illustr
5INSTALLATION INSTRUCTIONSIndoor unit installation2. Drill a hole in the wallFig.4Note:1. Fit the Installation Plate1. Fit the installation plate hori
6INSTALLATION INSTRUCTIONS1. For the left-hand and right-hand piping, remove the pipe cover from the side panel.Explain to clients that the pipe cover
7INSTALLATION INSTRUCTIONS5. Piping and wrappingBundle the tubing, connecting cable, anddrain hose with tape securely,evenly as shown in Fig.11.Becaus
8REFRIGERANT PIPE CONNECTIONSettlement of outdoor unitAnchor the outdoor unit witha bolt and nut 10 or 8 tightlyand horizontally on a concreteor rigid