Motorized valve and control
If these connections are not made as described the drain
pan condensate may overflow.
Valves should only open when the fan motor is working, i.e.
when one of TB1 terminals 1 or 2 or 3 is supplied from TB1
terminal 4.
The optional electric heater (mod. 42GWE) which can only be
factory installed, must only be energized when the fan is
working.
The optional electric heater which must be factory installed on
model 42GWE, works only if TB1 terminals 5-6 are supplied
from TB1 terminal 4.
The water discharge pump should work every time the
cold water valve is opened, supplying TB1 terminal 7 and
8 from TB1 terminal 4.
When the system is filled with water, verify all couplings
for tightness.
The manufacturer does not accept responsibility for the
tightness of the field - installed valve assembly and this
is not tested in the factory. He declines any responsibility
for non functioning of these assemblies and for damage
due to dripping.
Electrical connections
Capacitor
Ground connection screw
Board
Relay board E-HTR (only on
models with electric heater)
Holes for panel fixing screws
Auxiliary board (accessory)
C
B
A
CV
CG
CP
STANDARD version unit - Control panel
CV
CG CP
C
A
B
A. Electric heater supply connection
B. Unit power supply connection
C. Polarised connector
mod. 004 - 008 - 010
mod. 012 - 016 - 020
CV
CG
CP
Fan connector
Float connector
Pump connector
We recommend to remove the main board from the electric
panelboard for better access to electric connections.