3-2T--310
The Micromate (Figure 1-8) will allow t he user to
interface with the microprocessor based control from
the driver’s control panel. The Micromate Display
Panel (Figure 1-7) requires that the Micromate
Diagnostic Service Tool (P/N 76-62124-01) will need
to be used to access the system. The servicetool plugsin
to the Logic M odule to Driver Display Harness located
on the electrical control panel (Figure 1-1 1).
Table 3-2 Alarm Codes
ALARM
NO.
TITLE CAUSE REMEDY CONTROLLER
RESPONSE
A12 High Voltage The battery voltage is
greater than 32 volts.
Check, repair or re-
place alternator.
The s ystem is shut down
until the voltage returns
to normal levels.
A13 Low Voltage The battery voltage is
less than 17 volts.
Check, repair or re-
place wiring or alter-
nator.
The s ystem is shut down
until the voltage returns
to normal levels.
A14 Return Air Probe Failure Return air temperature
sensor failure or wir-
ing defective.
Ensure all connectors
are plugged in. Check
sensor resistance or
wiring. Refer to para-
graph 4.13. Replace
sensor or repair wir-
ing.
All outputs except the
evaporator fans will be
de-energized.
A15 Suction Pressure
Transducer Failure
Suction pressure
transducer failure or
wiring defective.
Ensure all connectors
are plugged in. Check
sensor voltage or wir-
ing. Replace sensor or
repair wiring.
Both unloaders are ener-
gized.
A16 Discharge Pressure
Transducer Failure
Discharge pressure
transducer failure or
wiring defective.
Ensure all connectors
are plugged in. Check
sensor voltage or wir-
ing. Replace sensor or
repair wiring.
One unloader is ener-
gized.
A17 Low Pressure Shutdown Low suction pressure
(below 10 psig)
Check cause of low
suction pressure. (Re-
fertosection3.4.3)
The clutch is de-ener-
gized for the minimum
off time. The evaporator
fans will remain running
during this period. After
the compressor cycles
off three times in 30
minutes all outputs will
be de-energized and the
system is locked out un-
til the power is cycled or
the alarm is reset.
A21 High Discharge Pressure High discharge pres-
sure switch open or
wiring defective.
Check discharge pres-
sure transducer read-
ing, wiring or cause of
high discharge pres-
sure. (Refer to section
3.4.3)
The clutch is de-ener-
gized for the minimum
off time. The condenser
and evaporator fans will
remain running during
this period. After the
compressor cycles off
three times in 30 min-
utes all outputs will be
de-energized and the
system is locked out un-
til the power is cycled or
the alarm is reset.