Table 2B -- Electrical Data -- Units With Optional Convenience Outlet (cont)
UNIT
50PG
O6
(cont)
NOMINAL
POWER SUPPLY
Volte-Ph-Hz
460-3-60
575-3-60
VOLTAGE COMPRESSOR OFM POWER ELECTRIC HEAT POWER SUPPLY
RANGE FLA IFM EXHAUST IFM
FLA FLA FLA TYPE Nominal MCA MOCPt
Min Max RLA LRA Qty (ea) (ea) FLA kW*
-- -- 15.2 20
5,8 5,0 15,2 20
8,7 7,5 16,9 20
STD 11.5 10.0 20.4 25
17,3 15,0 27,6 30
23,1 20,0 34.9 35
28.9 25.0 42.1 45
-- -- 15.2 20
5.8 5.0 15.2 20
8.7 7.5 16.9 20
ALT 11.5 10.0 20.4 25
17.3 15.0 27.6 30
23.1 20.0 34.9 35
414 506 7.7 50 1 0.8 2.6 28.9 25.0 42.1 45
-- -- 15.8 20
5.8 5,0 15,8 20
8.7 7.5 17.6 20
STD 11.5 10.0 21.1 25
17.3 15.0 28.4 30
23.1 20.0 35.6 40
0.6 28.9 25.0 42.9 45
-- -- 15.8 20
5,8 5,0 15,8 20
8.7 7.5 17.6 20
ALT 11.5 10.0 21.1 25
17.3 15.0 28.4 30
23.1 20.0 35.6 40
28.9 25.0 42.9 45
-- -- 12.1 15
9,2 10,0 16,1 20
STD 13.9 15.0 22.0 25
18.5 20,0 27,8 30
23,1 25,0 33.5 35
-- -- 12.1 15
9,2 10,0 16,1 20
ALT 13.9 15.0 22.0 25
18,5 20,0 27,8 30
518 633 6.1 40 1 0.8 2.0 23.1 25.0 33.5 35
-- -- 13.5 15
9.2 10.0 17.9 20
STD 13.9 15.0 23.8 25
18.5 20.0 29.5 30
1.4 23.1 25.0 35.3 40
-- -- 13.5 15
9,2 10,0 17.9 20
ALT 13,9 15,0 23.8 25
18,5 20,0 29.5 30
23,1 25,0 35,3 40
DISCONNECT
SIZE
FLA LRA
15 69
15 69
16 69
19 69
25 69
32 69
39 69
15 69
15 69
16 69
19 69
25 69
32 69
39 69
16 70
16 70
16 70
19 70
26 70
33 70
39 70
16 70
16 70
16 70
19 70
26 70
33 70
39 70
12 55
15 55
20 55
26 55
31 55
12 55
15 55
20 55
26 55
31 55
14 57
16 57
22 57
27 57
32 57
14 57
16 57
22 57
27 57
32 57
LEGEND
FLA -- Full Load Amps
HACR -- Heating, Air Conditioning and Refrigeration
IFM -- Indoor (Evaporator) Fan Motor
LRA -- Locked Rotor Amps
MCA -- Minimum Circuit Amps
MOCP -- Maximum Overcurrent Protection
NEC -- National Electrical Code
OFM -- Outdoor (Condenser) Fan Motor
RLA -- Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v or
600 v. If power distribution voltage to unit varies from rated heater voltage,
heater kW will vary accordingly.
l-Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load
equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker. Canadian units may be
fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent of
voltage imbalance.
% Voltage Imbalance
= 100 x max voltage deviation from average voltage
average voltage
Example: Supply voltage is 230-3-60.
A B c AB = 224v
BC = 231 v
AC = 226 v
Average Voltage -
224 + 231 + 226
3
681
=--
3
= 227
Determine maximum deviation from average voltage.
(AB) 227 - 224 = 3 v
(BC) 231 - 227 = 4 v
(AC) 227 - 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
4
% Voltage Imbalance = 100 x 22"_-
= 1.76%
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
I IMPORTANT: If the supply voltage phase imbalance is more than 2%, 1
contact the local electric utility company immediately.
l
2O