
Performance Adjustment section on page 39. See Table 18 for
accessory electric heat static pressme.
Cooling -- To start unit, turn on main power supply. Set
system selector switch tit COOL position and fan switch tit
AUTO position. Adjust therlnostat to a setting below room
temperatme. Compressor sttuts on closure of contactoc
Check unit charge. Refer to Refrigerant Charge section on
page 40.
Reset thermostat at a position above room temperature.
Compressor will shut off.
TO SHUT OFF UNIT -- Set system selector switch at OFF
position. Resetting thermostat at a position above room tem-
perature shuts unit off temporarily until space temperature ex-
ceeds thermostat setting. Units me equipped with Cycle-
LOC TM protection device. Unit shuts down on any safety trip
and remains off; an indicator light on the thermostat comes on.
Check reason for safety trip.
Complessor restart is accomplished by manual reset at the
thermostat by turning the selector switch to OFF position and
then ON position.
Heating (If Accessory Heater is Installed) -- To
st_ut unit, turn on main power supply.
Set thermostat at HEAT position and a setting above room
temperature, and set fan at AUTO position.
First stage of thermostat energizes the fi_st-stage electric
heater elements; second stage energizes second-stage electric
heater elements. Check heating effects fit air supply grille(s).
if accessory electric heaters do not energize, reset limit
switch (located on evaporator-fan scroll) by pressing button lo-
cated between termimds on the switch.
TO SHUT OFF UNIT -- Set system selector switch at OFF
position. Resetting heating selector lever below room tempera-
ture temporarily shuts unit off until space temperature ftdls be-
low thermostat setting.
Safety Relief- A soft solder joint in the suction line
fit the loss-of-charge/low-pressure switch fitting provides
pressure relief under abnormal temperature and pressure
conditions.
Ventilation (Continuous Fan) -- Set fan and system
selector switches fit ON and OFF positions, respectively.
Evaporator fan operates continuously to provide constant air
circulation.
Operating Sequence
COOLING. UNITS WITHOUT ECONOMIZER -- When
thermostat calls for cooling, terminals G and YI me energized.
The indoor-fan contactor (lFC) and compressor contactor me
energized and indoor-fan motol: compressor, and outdoor fan
stm'ts. The outdoor-fan motor runs continuously while unit is
cooling.
HEATING. UNITS WITHOUT ECONOMIZER -- Upon a
request for heating from the space thermostat, terminal Wl will
be energized with 24 v. The lFC and heater contactor no. 1
(HCI) are energized.
COOLING. UNITS WITH ECONOMISER IV -- When free
cooling is not available, the compressors will be controlled by
the zone thermostat. When free cooling is available, the
outdoor-air damper is modulated by the EconoMiSer IV con-
trol to provide 50 to 55 F mixed-air temperature into the zone.
As the mixed-air temperature fluctuates above 55 or below
50 H the dampers will be modulated (open or close) to bring
the mixed-air temperature back within control.
If the load is high and Y2 is energized, then the that stage of
mechanical cooling will be used to supplement the free cooling
provided by the economizer If mechanical cooling is utilized
with free cooling, the outdoor-air &_mper will maintain its
current position at the time the compressor is started. If the
increase in cooling capacity causes the mixed-air temperature
to drop below 45 F. then the outdoor-air dmnper position
will be decreased to the minimum position. If the mixed-air
temperature continues to fall, the outdoor-air (ktmper will
close. Control returns to normal once the mixed air temperature
rises above 48 E
If optional power exhaust is instfdled, as the outdoor-air
damper opens and closes, the power exhaust fans will be
energized and deenergized if the position goes above or below
the power exhaust set point. When the exhaust fan is required
to be on, the LED on the control will be energized.
If field-installed accessory CO2 sensors are connected to the
EconoMiSer IV control, a demand controlled ventilation strate-
gy will begin to operate. As the CO2 level in the zone increases
above the CO2 set point, the minimum position of the damper
will be increased proportionally from the minimum damper
position to the maximum demand ventilation damper position.
As the CO2 level decreases because of the increase in fresh air,
the outdoor-air damper will be proportionally closed.
If there is no G signal then the control will drive the &tmper
to the fully closed position.
The control is also equipped with an occupied/unoccupied
input. If the input is closed, then the damper will be driven to
the minimum position when G is energized. If the input is open
then the damper will remain in the lully closed position unless
there is a demand for free cooling of DCV ventihnion.
On the initial power to the EconoMiSer IV control, it will
take the damper up to 21/2 minutes before it begins to position
itself. Any change in damper position will take up to 30 sec-
onds to initiate. Damper movement from full closed to full
open (or vice vel_a) will take between 11/2to 21/2 minutes.
If free cooling can be used as determined from the appropri-
ate changeover command (switch. dq bulb, enthalpy curve,
differential dry bulb, or differential enthalpy), then the control
will modulate the dampers open to maintain the mixed air
temperature set point at 50 to 55 E
If there is a further demand for cooling (cooling second
stage -- Y2 is energized), then the control will bring on
compressor stage 1 to maintain the mixed air temperature set
point. The EconoMiSer IV &tmper will be open at maximum
position. EconoMiSer IV operation is limited to a single
complessoE
HEATING. UNITS WITH ECONOMISER IV -- When the
room temperature calls for heat, the heating controls rueenelgized
as described in the Heating, Units Without Economizer section.
The IFM is energized and the EconoMiSer IV dalnper modulates
to the minimum position. When the thermostat is satisfied, the
dalnper modulates closed.
3O
Comments to this Manuals