option. Wind baffles and brackets must be field fabricated and
installed for proper operation. The fan speed will modulate
based on liquid line pressure. One control is required per refrig-
erant circuit. See Appendix C for configuration and operational
information.
Pumpout
EXV UNITS When the lead compressor in each circuit is
started or stopped, that circuit goes through a pumpout cycle to
purge the cooler and refrigerant suction lines of refrigerant. If a
circuit is starting within 15 minutes of the last shutdown, the
pumpout cycle will be skipped.
The pumpout cycle starts immediately upon starting the
lead compressor and keeps the EXV at minimum position for
10 seconds. The EXV is then opened an additional percentage
and compressor superheat control begins. At this point, the
EXV opens gradually to provide a controlled start-up to pre-
vent liquid flood-back to the compressor.
At shutdown, the pumpout cycle continuously closes the
EXV until all lag compressors are off and the EXV is at 0%.
The lead compressor continues to run for an additional 10 sec-
onds and is then shut off.
TXV UNITS Pumpout is based on timed pumpout. On a
command for start-up, the lead compressor starts. After 15 sec-
onds, the liquid line solenoid opens. At shutdown, the liquid
line solenoid closes when the lead compressor has stopped.
*Control box.
Fan numbers 11 and 12 do not apply to 30GTN,R and 30GUN,R 130-170 and associated modular units (see Tables 1A and 1B).
Fig. 18 Condenser Fan Sequence
FAN ARRANGEMENT
FAN
NO.
FAN RELAY NORMAL CONTROL
30GTN,R040-050
30GUN,R040-050
1 Compressor No. A1
2 Compressor No. B1
3 1 First Stage of Condenser Fans
4 2 Second Stage of Condenser Fans
30GTN,R060-090, 230B, 245B
30GUN,R060-090, 230B, 245B
1 Compressor No. A1
2 Compressor No. B1
3, 4 1 First Stage of Condenser Fans
5, 6 2 Second Stage of Condenser Fans
30GTN,R100,110, 255B-315B
30GUN,R100,110, 255B-315B
1 Compressor No. A1
2 Compressor No. B1
3, 4 1 First Stage of Condenser Fans
5, 6, 7, 8 2 Second Stage of Condenser Fans
30GTN,R130 (60 Hz),
30GUN,R130 (60 Hz)
POWER
5, 7 Compressor No. A1
6, 8 Compressor No. B1
1, 2 1 First Stage of Condenser Fans
3, 4, 9, 10 2 Second Stage of Condenser Fans
30GTN,R130 (50 Hz), 150-210,
230A-315A, 330A/B-420A/B
30GUN,R130 (50 Hz), 150-210,
230A-315A, 330A/B-420A/B
POWER
5, 7 Compressor No. A1
6, 8 Compressor No. B1
1, 11 1 First Stage of Condenser Fans, Circuit A
3, 9 2 Second Stage of Condenser Fans, Circuit A
2, 12 3 First Stage of Condenser Fans, Circuit B
4, 10 4 Second Stage of Condenser Fans, Circuit B
3
1
4
2
CONTROL
BOX
53
1
6
4
2
CONTROL
BOX
75 3
1
8
6
4
2
CONTROL
BOX
2
4
6
8
10
9
7
*
5
3
1
2
4
6
8
10
9
7
*
5
3
1
12
11
Page view 28
1 2 ... 24 25 26 27 28 29 30 31 32 33 34 ... 103 104

Comments to this Manuals

No comments