wiring. A chilled water flow switch should be installed for each
chiller.
To configure the two chillers for dual chiller operation, fol-
low the example shown in Tables 19A and 19B. Both chillers
must have the Control Method variable (CTRL, Configuration
mode, sub-mode OPT2) set to 3 CCN Control. In the exam-
ple the master chiller will be configured with a CCN address of
1 and the slave chiller with a CCN address of 2 (CCNA,
Configuration mode, sub-mode OPT2). The master and slave
chillers can be addressed from 1 to 239. Each device connected
to the network must have its own unique address. Both chillers
must have the same CCN Bus Address (CCNB, Configuration
mode, sub-mode OPT2). Lead/Lag Chiller Enable must be set
to ENBL for both chillers (LLEN, Configuration mode, sub-
mode RSET). Also in this example, the master chiller will
be configured to use Lead/Lag Balance (LLBL, Configura-
tion mode, sub-mode RSET) to rotate the lead chiller after
168 hours of operation. The Lag Start Delay (LLBD, Configu-
ration mode, sub-mode RSET) will be set for 10 minutes. This
prevents the Lag chiller from starting until the lead chiller is
fully loaded and the delay has elapsed.
If Outdoor Air Temperature reset is desired, it should be
connected to the slave chiller. CCN OAT Broadcast will have
to be configured for Ye s on the slave chiller and CCN Broad-
cast Acker will have to be configured for Yes on the master
chiller. Broadcast functions can only be configured with Ser-
vice Tool, ComfortVIEW, ComfortWORKS® or the
Enhanced Display option.
Table 8 Marquee Display Menu Structure
LEGEND
Ckt Circuit
RUN
STATUS
SERVICE
TEST
TEMPERATURES PRESSURES
SET
POINTS
INPUTS OUTPUTS CONFIGURATION
TIME
CLOCK
OPERATING
MODES
ALARMS
Auto
Display
(VIEW)
Manual
Mode
On/Off
(TEST)
Unit
Temperatures
(UNIT)
Ckt A
Pressures
(PRC.A)
Cooling
(COOL)
Unit
Discrete
(GEN.I)
Unit
Discrete
(GEN.O)
Display
(DISP)
Unit Time
(TIME)
Modes
(MODE)
Current
(CRNT)
Machine
Hours/Starts
(RUN)
Ckt A/B
Outputs
(OUTS)
Ckt A
Temperatures
(CIR.A)
Ckt B
Pressures
(PRC.B)
Heating
(HEAT)
Ckt A/B
(CRCT)
Ckt A
(CIR.A)
Machine
(UNIT)
Unit Date
(DATE)
Reset
Alarms
(RCRN)
Compressor
Run Hours
(HOUR)
Compressor
Tests
(COMP)
Ckt B
Temperatures
(CIR.B)
Head
Pressure
(HEAD)
EMM
Analog
(4-20)
Ckt B
(CIR.B)
Options 1
(OPT1)
Schedule
(SCHD)
Alarm
History
(HIST)
Compressor
Starts
(STRT)
Options 2
(OPT2)
Reset
History
(RHIS)
Software
Ver sio n
(VERS)
Temperature
Reset
(RSET)
Set Point
Select
(SLCT)
MASTER
CHILLER
SLAVE
CHILLER
LEAVING
FLUID
RETURN
FLUID
THERMISTOR
WIRING*
INSTALL DUAL CHILLER LWT
LEAVING FLUID TEMPERATURE
THERMISTOR (T10) HERE
*Depending on piping sizes, use either:
HH79NZ014 sensor/10HB50106801 well (3-in. sensor/well)
HH79NZ029 sensor/10HB50106802 well (4-in. sensor/well)
Fig. 21 Dual Chiller Thermistor Location