Carrier AQUAFORCE 30XW150-400 Specifications Page 15

  • Download
  • Add to my manuals
  • Print
  • Page
    / 44
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 14
15
3/8”3/8”
3/8”3/8”
“A “A
(SEE T
ABLE BELOW) (SEE TABLE BELOW)
ISOLATION VALVE
(OPTIONAL)
ISOLATION VALVE
(OPTIONAL)
Fig. 4 — 30XW225-300 Unit Dimensions (cont)
a30-5271
SIDE VIEW
LEGEND
1P 1 Pass
2P 2 Pass
3P 3 Pass
MLV Minimum Load Valve
NIH Nozzle-In-Head
OPP ENDS Opposite Ends
SAE Society of Automotive Engineers
SSV Suction Service Valve
STD ENDS — Standard Ends
CHILLER DIMENSIONS
CONNECTION
PASSES
COOLER/
COND
WATER BOX
COOLER/
COND
PRESSURE
PSIG
NOZZLE
TYPE
“A”
ft-in. [mm]
ADDED
WGT
lb [kg]
STD ENDS 2P / 2P NIH / NIH 150 or 300 VIC 10-10
11
/
16
[3320] 0
STD ENDS 2P / 2P NIH / NIH 150 or 300 FLG 11- 4
5
/
16
[3463] 320 [145]
STD ENDS 2P / 2P NIH / MWB 150 or 300 VIC 11- 6
9
/
16
[3519] 285 [129]
STD ENDS 2P / 2P NIH / MWB 150 or 300 FLG 11- 6
9
/
16
[3519] 335 [152]
STD ENDS 2P / 2P MWB / NIH 150 or 300 VIC 11- 6
9
/
16
[3519] 278 [126]
STD ENDS 2P / 2P MWB / NIH 150 or 300 FLG 11- 6
9
/
16
[3519] 311 [141]
STD ENDS 2P / 2P MWB / MWB 150 or 300 VIC 11- 6
9
/
16
[3519] 563 [255]
STD ENDS 2P / 2P MWB / MWB 150 or 300 FLG 11- 6
9
/
16
[3519] 646 [293]
STD ENDS 2P / 3P NIH / NIH 150 or 300 FLG 12- 0
1
/
2
[3670] 470 [213]
STD ENDS 2P / 3P NIH / MWB 150 or 300 FLG 12- 5
5
/
8
[3800] 1080 [490]
OPP ENDS 1P / 1P NIH / NIH 150 or 300 FLG 12- 0
11
/
16
[3676] 492 [223]
OPP ENDS 1P / 1P NIH / MWB 150 or 300 FLG 12- 5
5
/
8
[3800] 831 [377]
OPP ENDS 1P / 1P MWB / NIH 150 or 300 FLG 12- 5
5
/
8
[3800] 768 [394]
OPP ENDS 1P / 1P MWB / MWB 150 or 300 FLG 12- 5
5
/
8
[3800] 1207 [547]
OPP ENDS 2P / 2P NIH / NIH 150 or 300 VIC 10-10
11
/
16
[3320] 0
OPP ENDS 2P / 2P NIH / NIH 150 or 300 FLG 11- 4
5
/
16
[3463] 320 [145]
OPP ENDS 2P / 2P NIH / MWB 150 or 300 VIC 11- 6
9
/
16
[3519] 285 [129]
OPP ENDS 2P / 2P NIH / MWB 150 or 300 FLG 11- 6
9
/
16
[3519] 335 [152]
OPP ENDS 2P / 2P MWB / NIH 150 or 300 VIC 11- 6
9
/
16
[3519] 278 [126]
OPP ENDS 2P / 2P MWB / NIH 150 or 300 FLG 11- 6
9
/
16
[3519] 311 [141]
OPP ENDS 2P / 2P MWB / MWB 150 or 300 VIC 11- 6
9
/
16
[3519] 563 [255]
OPP ENDS 2P / 2P MWB / MWB 150 or 300 FLG 11- 6
9
/
16
[3519] 646 [293]
OPP ENDS 3P / 1P NIH / NIH 150 or 300 FLG 12- 0
11
/
16
[3676] 505 [229]
OPP ENDS 3P / 1P NIH / MWB 150 or 300 FLG 12- 5
5
/
8
[3800] 844 [383]
OPP ENDS 3P / 1P MWB / NIH 150 or 300 FLG 12- 5
5
/
8
[3800] 903 [410]
OPP ENDS 3P / 1P MWB / MWB 150 or 300 FLG 12- 5
5
/
8
[3800] 1242 [470]
Page view 14
1 2 ... 10 11 12 13 14 15 16 17 18 19 20 ... 43 44

Comments to this Manuals