CONDENSER FLUID CONTROL VALVE — For installa-
tions where entering condensing fluid temperature could be be-
low 65 F (18.3 C), a field-supplied control valve is required.
Operation below 65 F (18.3 C) without this valve may cause
the unit to shut down on low oil pressure alarms.
NOTE: A valve that can be controlled by a 0 to 10 vdc signal
is supported by the ComfortLink control system. Figure 13
shows the installation details for the regulating valve.
INSTALL PRESSURE RELIEF REFRIGERANT VENT
PIPING The 30XW chiller is factory equipped with relief
valves on the evaporator and condenser shells. There is one re-
lief valve per circuit on the evaporator and two relief valves per
circuit on the condenser. Make the vent connection to the low
side relief valve by installing a male NPT to copper OD braze
adapter. Braze a 90-degree short-radius elbow to the adapter.
This will allow enough space to make vent connections to the
elbow. An additional relief valve is located on the liquid line
and the economizer assembly, if equipped, for each circuit.
Refer to Tables 1 and 2 for connection size information. If the
unit is equipped with an optional isolation service valve, an
additional relief valve is located on the discharge line. See
Fig. 3-5 for location and connection size information. See
Fig. 14 for location of temperature relief valves on the econo-
mizer assembly. Vent relief devices to the outdoors in accor-
dance with ANSI/ASHRAE (American National Standards
Institute/American Society of Heating, Refrigerating and Air
Conditioning Engineers) 15 Safety Code for Mechanical
Refrigeration (latest edition) and all other applicable codes.
PIPE
FLANGES
PRESSURE
GAGES
LEAVING
CONDENSER
WATER
ENTERING
CONDENSER
WATER
ENTERING
WATER
LEAVING
WATER
THERMOMETERS
(OPTIONAL)
AIR VENT
PIPE HANGERS
CHILLED
CHILLED
AIR VENT
THERMOMETERS
(OPTIONAL)
PRESSURE
GAGES
Fig. 12 — Typical NIH Piping
NOTES:
1. Chilled water flow switch is factory installed in the evaporator inlet nozzle.
2. Entering and leaving water thermistors are located in the evaporator inlet and outlet nozzles.
3. A
3
/
8
in. NPT vent plug is located in the top of the evaporator and condenser outlet nozzle.
4. A
3
/
8
in. NPT drain plug is located in the bottom of the evaporator and condenser inlet nozzle.
5. Condenser water flow switch is factory installed in the condenser inlet nozzle on units with
heat machine option only.
6. Entering and leaving water thermistors are located in the condenser inlet and outlet nozzles
on units with heat machine option only.
a30-5507
IMPORTANT: A separate, field-supplied power supply
must be used with the condenser fluid control valve. Fail-
ure to use a separate power supply may result in damage to
the electronic chiller components.
DANGER
Refrigerant discharged into confined spaces can displace
oxygen and cause asphyxiation.
INLET
OUTLET
CHILLER CONTROL PANEL
30XW CONDENSER
BYPASS VALVE
OPTIONAL BYPASS VALVE FOR NORMAL DUTY
3 WAY VALVE
(OPTIONAL)
SIGNAL
Fig. 13 — Condenser Fluid Control Valve Installation
A30-5279