DEALER SERVICE BULLETIN
Number: DSB 09-0022 Date: 4/809 Supersedes: DSB 07-0049
Title: 90% Furnace Heat Exchanger
Inspection Procedure
PRODUCT CATEGORY:
90% furnaces
MODELS AFFECTED:
320A, 321A, 340A, 340M, 345M, 350A, 350M, 351D, 352A, 352M, 355A, 355B, 355C,
355M, 398A, 398B, 399A
58SX, SXA, SXB, SXC, DX, DXA, DXC, VCA, VUA, MCA, MCB, MXA, MXB, MSA,
UVB, MVP, MVB, MVC, MTA, MTB
490A, PG9MAA, PG9MAB
SITUATION
:
There are several furnace heat exchanger inspection methodologies that have been used in the field.
Improper or inadequate furnace heat exchanger inspection techniques can result in the misdiagnosis
of a heat exchanger failure when a failure has not occurred or is not imminent.
SOLUTION:
Attached is the official Carrier / Bryant / Payne 90% Furnace Heat Exchanger Inspection Procedure.
This procedure should be utilized to properly diagnose a heat exchanger failure once preliminary
service and troubleshooting techniques indicate the heat exchanger is suspected to have failed. This
bulletin may also be used as a reference to verify the furnace is installed properly. The maintenance
items section can be used to identify any existing or future service related issues.
This inspection procedure details significant installation, set-up, and maintenance items that can
impact furnace operation, combustion characteristics, and heat exchanger performance and
reliability. In general, if an initial check of combustion performance as detailed in Section 2 of this
procedure yields CO levels in the vent of 200 ppm or less, no further examination or inspection of the
heat exchanger is required. Installation, set-up, and maintenance items should still be reviewed
and corrected to resolve any remaining furnace operational concerns. An excess air measurement
can also help in diagnosis of heat exchanger failure. The combustion check procedure included in
this document details additional steps to include this diagnostic when possible.
This bulletin also includes a 90% Furnace Heat Exchanger Inspection Certificate that must be
completed, signed by the technician, and faxed or e-mailed to Warranty Administration as part of the
heat exchanger warranty claim approval process.
Warning: Do not perform any of the servicing instructions provided in this Service Bulletin unless you are a trained and
qualified technician. Observe all precautions in the instructions, equipment tags, labels, and observe all other safety
precautions that may apply. Failure to follow this warning could result in property damage, personal injury or death.
Page view 0
1 2 3 4 5 6 ... 17 18

Summary of Contents

Page 1 - DEALER SERVICE BULLETIN

DEALER SERVICE BULLETIN Number: DSB 09-0022 Date: 4/809 Supersedes: DSB 07-0049 Title: 90% Furnace Heat Exchanger Inspection Procedu

Page 2

SMB 09-0022 90% Furnace Inspection Instruction 10 Remove and clean the flame sensor with fine steel wool Blow out a

Page 3

SMB 09-0022 90% Furnace Inspection Instruction 11Restricted heat exchanger (primary or secondary) Action must be t

Page 4

SMB 09-0022 90% Furnace Inspection Instruction 12 F. Re-install the burner box Note: The burner box should be fu

Page 5

SMB 09-0022 90% Furnace Inspection Instruction 13 Repair or replace as necessary I. Check vent termination Vent t

Page 6

SMB 09-0022 90% Furnace Inspection Instruction 14If an evaporator coil is installed and the delta plate on the coil

Page 7

SMB 09-0022 90% Furnace Inspection Instruction 15 If soot is present on all parts (primary h

Page 8

SMB 09-0022 90% Furnace Inspection Instruction 16 Inspect the inlets of the secondary heat exchanger. I

Page 9

SMB 09-0022 90% Furnace Inspection Instruction 17 After the heat exchanger is inspected and ser

Page 10

SMB 09-0022 90% Furnace Inspection Instruction 1890% Furnace Secondary Heat Exchanger Inspection Certificate Fax to

Page 11

SMB 09-0022 90% Furnace Inspection Instruction 2 This procedure and the 90% Furnace Heat Exchanger Inspection Certi

Page 12

SMB 09-0022 90% Furnace Inspection Instruction 3Follow all Local Codes. In the absence of local codes, consult the

Page 13

SMB 09-0022 90% Furnace Inspection Instruction 4 These conditions indicate a possible: Split heat exchanger seam

Page 14

SMB 09-0022 90% Furnace Inspection Instruction 5 Take a flue gas reading and record the CO value Is the CO level

Page 15 - Coupling Box

SMB 09-0022 90% Furnace Inspection Instruction 6Place an “X” in the box next to each item as you inspect the system

Page 16 - Not a failure

SMB 09-0022 90% Furnace Inspection Instruction 7 Temperature rise adjusted to mid-range per installation instructio

Page 17

SMB 09-0022 90% Furnace Inspection Instruction 8b) Conversion Rating Plate Label c) Gas Control Conversion Label

Page 18

SMB 09-0022 90% Furnace Inspection Instruction 9 To clean the blower assembly: Disconnect power from furnace R