Packaged Heating/Cooling Units
Constant Volume Application
HVAC Guide Specifications
Size Range: 1-1/2 to 5 Tons, Nominal Cooling
40,000 to 130,000 Btuh,
Nominal Heating Input
Carrier Model Number: 48GS
Part 1 — General
SYSTEM DESCRIPTION
Outdoor rooftop mounted, gas heating/electric cooling unit
utilizing a hermetic compressor for cooling duty. Unit shall
discharge supply air vertically or horizontally as shown on
contract drawings. Condenser fan/coil section shall have a
draw-thru design with vertical discharge for minimum
sound levels.
QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI Standards
210-89 and 270-89.
B. Unit shall be designed in accordance with UL Standard
1995.
C. Unit shall be manufactured in a facility registered to
ISO 9001 manufacturing quality standard.
D. Unit shall be UL listed and CSA certified as a total
package for safety requirements.
E. Roof curb shall be designed to conform to NRCA
Standards.
F. Insulation and adhesives shall meet NFPA 90A
requirements for flame spread and smoke generation.
G. Cabinet insulation shall meet ASHRAE Standard 62P.
DELIVERY, STORAGE AND HANDLING
Unit shall be stored and handled per manufacturer’s
recommendations.
Part 2 — Products
EQUIPMENT
A. General:
Factory-assembled, single-piece, heating and cooling
unit. Contained within the enclosure shall be all factory
wiring, piping, controls, refrigerant chage (R-22), and
special features required prior to field start-up.
B. Unit Cabinet:
1. Unit Cabinet shall be constructed of phosphated,
zinc-coated, pre-painted steel capable of with-
standing 500 hours in salt spray.
2. Normal service shall be through a single removable
cabinet panel.
3. The unit shall be constructed on a rust proof
basepan that has an externally trapped, integrated
sloped drain pan.
4. Evaporator fan compartment top surface shall be
insulated with a minimum 1/2-in. thick, flexible
fiberglass insulation, coated on the air side and
retained by adhesive and mechanical means. The
evaporator wall sections will be insulated with a
minimum semi-rigid foil-faced board capable of
being wiped clean. Aluminum foil-faced fiberglass
insulation shall be used in the entire indoor air
cavity section.
5. Unit shall have a field-supplied condensate trap.
C. Fans:
1. The evaporator fan shall be 3-speed, direct-drive, as
shown on equipment drawings.
2. Fan wheel shall be made from steel, be double-inlet
type with forward curved blades with corrosion
resistant finish and be dynamically balanced.
3. Condenser fan shall be direct drive propeller type
with aluminum blades riveted to corrosion resistant
steel spiders, be dynamically balanced, and
discharge air vertically.
D. Compressor:
1. Fully hermetic compressors with factory-installed
vibration isolation.
2. Reciprocating and/or scroll compressors shall be
standard on all units.
E. Coils:
Evaporator and consdensor coils shall have aluminum
plate fins mechanically bonded to seamless copper
tubes with all joints brazed (copper/copper and vinyl-
coated construction available as factory-installed
option). Tube sheet openings shall be belled to prevent
tube wear.
F. Heating Section:
1. Induced-draft combustion type with energy saving
direct spark ignition system and redundant main gas
valve.
2. Induced-draft motors shall be provided with solid-
state hall-effect sensor to ensure adequate airflow
for combustion.
3. The heat exchangers shall be constructed of
aluminized steel for corrosion resistance.
4. Burners shall be of the in-shot type constructed of
aluminum coated steel.
5. All gas piping and electric power shall enter the unit
cabinet at a single location.
G. Refrigerant Components:
Refrigerant components shall be of the fixed orifice
feed type.
H. Filter section shall consist of field-installed,
throwaway, 1-in. thick fiberglass filters of com-
mercially available sizes.
I. Controls and Safeties:
1. Unit controls shall be complete with a self-
contained low voltage control circuit.
2. Safeties: compressors shall incorporate a solid-state
compressor protector that provides reset capability.
J. Operating Characteristics:
1. Unit shall be capable of starting and running at
125°F ambient outdoor temperature per maximum
load criteria of ARI Standard 210.
Guide specifications