3
SPECIFICATIONS
Heating Capacity and Efficiency 040-10 040 -12 060-12 060 -14 080-16 080 -20 100 -20 120-22
Input High Heat (BTUH) 40,000 40,000 60,000 60,000 80,000 80,000 100,000 120,000
Output High Heat (BTUH) 39,000 39,000 58,000 58,000 78,000 78,000 97,000 117,000
Certified Temperature
Rise Range ºF (ºC)
High Heat
40 - 70
(22 - 39)
40 - 70
(22 - 39)
45 - 75
(25 - 42)
40 - 70
(22 - 39)
40 - 70
(22 - 39)
40 - 70
(22 - 39)
40 - 70
(22 - 39)
40 - 70
(22 - 39)
Airflow Capacity and Blower Data 040-10 040 -12 060-12 060 -14 080-16 080 -20 100 -20 120-22
Rated External Static
Pressure (in. w.c.)
Heating 0.10 0.10 0.12 0.12 0.15 0.15 0.20 0.20
Cooling 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
Airflow Delivery
@RatedESP(CFM)
High Heat 695 705 940 1000 1360 1360 1700 2125
Cooling 925 1085 1090 1505 1610 2015 2110 2055
Cooling Capacity (tons)
@ 400, 350 CFM/ton
CFM/ton 2 2.5 2.5 3.5 4 5 5 5
CFM/ton 2.5 3 3 4 4.5 5.5 6 6
Direct-Drive Motor Type Electronically Commutated Motor (ECM)
Direct-Drive Motor HP 1/2 1/2 1/2 3/4 3/4 1 1 1
Motor Full Load Amps 6.8 6.8 6.8 8.4 8.4 10.9 10.9 10.9
RPM Range 600 - 1200
Speed Selections 5
Blower Wheel Dia x Width in. 11 x 7 11 x 8 11 x 7 11 x 8 11 x 8 11 x 10 11 x 10 11 x 11
Air Filtration System
Factory Supplied Media Cabinet
FieldSuppliedFilter
Filter Used for Certified Watt Data KGAWF1506UFR
Electrical Data 040-10 040 -12 060-12 060 -14 080-16 080 -20 100 -20 120-22
Input Voltage Volts-Hertz-Phase 115-60-1
Operating Voltage Range Min-Max 104-127
Maximum Input Amps Amps 7.4 7.4 7.5 9.1 9.1 11.6 11.7 11.7
Unit Ampacity Amps 10.3 10.3 10.4 12.4 12.4 15.5 15.6 15.6
Minimum Wire Size AWG 14 14 14 14 14 12 12 12
Maximum Wire Length
@ Minimum Wire Size
Feet 36 36 35 30 30 37 36 36
(M) (11.0) (11.0) (10.7) (9.1) (9.1) (11.3) (11.0) (11.0)
Maximum Fuse/Ckt Bkr
(Time-Delay Type Recommended)
Amps 15 15 15 15 15 20 20 20
Transfomer Cap acity (24vac output) 40 VA
External C ontrol Power
Available
Heating 27.9 VA
Cooling 34.6 VA
Controls 040-10 040 -12 060-12 060 -14 080-16 080 -20 100 -20 120-22
Gas Connection Size 1/2” - NPT
Burners (Monoport) 2 2 3 3 4 4 5 6
Gas Valve (Redundant) Manufacturer White Rodgers
Minimum Inlet Gas pressure (in. wc) 4.5
Maximum Inlet Gas pressure (in. wc) 13.6
Gas Conversion Kit - Natural to Propane KGANP50011SP
Gas Conversion Kit - Propan e to Natural KGAPN42011SP
Manufactured (Mobile) Home Kit KGAMH0601KIT
Ignition Device Silicon Nitride
Limit Control 165 180 165 180 170 200 180 160
Heating Blower Control (Heating Off-Delay) Adjustable: 90, 120, 150, 180 seconds
Cooling Blower Control (Time D el ay Relay) 90 seconds
Communication System none
Thermostat C onnections Com24V,R,W,G,Y/Y2,DHUM,Y1
Accessory Connections EAC (115vac); HUM (24vac); 1-stg AC (via Y/Y2)
* See Accessory List for part numbers available.