Carrier 58CTA/CTX User Manual Page 32

  • Download
  • Add to my manuals
  • Print
  • Page
    / 56
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 31
32
SEE NOTES: 1,2,4,5,7,8,9
A02068
Fig. 47 -- Horizontal Right Application--Vent Elbow Left
NOTES: Venting Notes for Fig. 35---47
1. For common vent, vent con nector sizing and vent material: United States--- ---use the NFGC Can a da --- ---use the CAN/CSA---B149.1---05
2. Immediately increase to 5--- in. or 6---in. (127 or 152 mm) vent connector outside furnace casing when 5--- in. (127 mm) vent connector is required, refer to
Note 1 a bove.
3. Side outlet vent for upflow and downflow installations must u se Type B vent immediately after exiting the fu rnace, except when KGAV G0101DFG, Downflow
VentGuardKit,isusedinthedownflowposition.
4. Type ---B vent where required, refer to Note 1 above.
5. Four---in. (102 mm) single---wal l (26 ga. min.) vent must be used inside furnace casing and when the KGAVG0101DFG Down f low Vent Guard Kit is u sed
external to the furnace.
6. Accessory D o wn f low Vent Guard Kit, KGAV G0101DFG required in downflow installations with lower vent configuration.
7. Chimney Adapter Kit may be required for exterior masonry chimney applications. Refer to Chimney Adapter Kit, KGACA02014FC or KGACA02015FC, for
sizing and complete application details.
8. Secure vent connector to furnace elbow with (2) corrosion ---resistant sheet metal screws, spaced approximately 180_ apart.
9. Secure all other single wall vent connector joints with (3) corrosion resistant screws spaced approximately 120_ apart. Secure Type---B vent connectors per
vent connector manufacturer’s recommendations.
10. The total height of the vent and connector shall be at least seven feet (2 M) for the 154,000 Btuh gas input ra te model when installed in a downflow applica-
tion with furnace elbow turned to left side with the connector elbow outside furnace casing pointing upward. (See Fig. 40.)
Caution!! For the following applications, use the minimum vertical heights as specified below.
For all other applications, follow exclusively the National Fuel Gas Code
FURNACE
ORIENTATION
VENT
ORIENTATION
FURNACE
INPUT(BTUH/HR)
MINIMUM VENT
DIAMETER
IN. (mm)*
MINIMUM VERT ICAL
VENT HEIGHT
FT. (M)**
Downflow
Vent elbow left, then
up Fig. 39
154,000
132,000
110,000(036/---12 only)
5 (127) 12 (3.6)
Horizontal Left
Vent elbow right,
then up Fig. 42
154,000
132,000
5 (127) 7 (.65)
Horizontal Left
Vent Elbow up Fig.
43
154,000
132,000
5 (127) 7 (.65)
Horizontal Left
Vent elbow right Fig.
44
154,000 5 (127) 7 (.65)
Downflow
Vent elbow up then
left Fig. 37
110,000 (036/---12 only) 5 (127) 10 (3.0)
Downflow
Vent elbow up, then
right Fig. 40
110,000 (036/---12 only) 5 (127) 10 (3.0)
*4 in. (102 mm) inside casing or vent guard
**Including 4 in. (102 mm) vent section(s)
NOTE: All vent configurations must also meet National Fuel Gas Code venting requirements NFGC.
58CT
Page view 31
1 2 ... 27 28 29 30 31 32 33 34 35 36 37 ... 55 56

Comments to this Manuals

No comments