Carrier 58CTA/CTX User Manual Page 24

  • Download
  • Add to my manuals
  • Print
  • Page
    / 56
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 23
24
7
See notes 1, 2, 3, 4, 12, 13, 14, 15, and 17
on the page following these figures
A03182
Fig. 30 -- Dual Fuel Thermostat with Two -- Stage Furnace
and Two--Speed Heat Pump
See notes 2, 11, and 12 on the
page following these figures
A03183
Fig. 31 -- Two-- Stage Thermosta t with Two-- Stage Furnace
and Two--Speed Air Conditioner
See notes 1 and 2 on the page
following these figures
A03184
Fig. 32 -- Single-- Stage Thermostat with Two-- Stage Furnace and Two -- Speed Air Conditioner
NOTES: F o r F i gu r e s 2 6 --- 3 2
1. Heat pump MUST have a high pressure switch for dual fuel applications.
2. Refer to outdoor equipment Installation Instructions for additional information and setup procedure.
3. Outdoor Air Temperature Sensor must be attached in all dual fuel applications.
4. Dip switch No. 1 on Thermidistat should be set in OFF position for air conditioner installations. This is factory default.
5. Dip switch No. 1 on Thermidistat should be set in ON position for heat pump installations.
6. Dip switch No. 2 on Thermidistat should be set in OFF position for single---speed compressor operation. This is factory default.
7. Dip switch No. 2 on Thermidistat should be set in ON position for two---speed compressor operation.
8. Configuration Option No. 10 “Dual Fuel Selection” must be turned ON in all dual fuel applications.
9. NO connection should be made to the furnace HUM terminal when using a Thermidistat.
10. Optional connection: If wire is connected, dip switch SW1---2 on furnace control should be set in ON position to allow Thermidistat/Thermostat to control
furnace staging.
11. Optional connection: If wire is connected, ACRDJ jumper on furnace control should be removed to allow Thermidistat/Thermostat to control outdoorunit
staging.
12. When using both a two---stage furnace and a two---stage heat pump, the furnace must control its own high---stage heating operation via furnace control
algorithm.
13. The RVS Sensing terminal “L should not be connected. This is internally used to sense defrost operation.
14. DO NOT SELECT the “FURNACE INTERFACE” or “BALANCE POINT” option on the two---speed heat pump control board. This is controlled internally by
the Thermidistat/Dual Fuel Thermostat.
15. Dip switch D on Dual Fuel Thermostat should be set in OFF position for single ---speed compressor operation. This is factory default.
16. Dip switch D on Dual Fuel Thermostat should be set in ON position for two ---speed compressor operation.
58CT
Page view 23
1 2 ... 19 20 21 22 23 24 25 26 27 28 29 ... 55 56

Comments to this Manuals

No comments