Carrier 58MVP User Manual Page 23

  • Download
  • Add to my manuals
  • Print
  • Page
    / 48
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 22
Fault Code 32
LOW-PRESSURE SWITCH FAULT—This fault can occur under the scenarios shown below. Keep in mind that
whenever the furnace control board shuts unit down, gas shuts off immediately, inducer continues running
for 15 sec, and if blower is running it remains running at low-heat speed or reduces to low-heat speed for
selected off delay.
On propane installations when low gas pressure switch LGPS is open due to switch failure or low propane line pressure.
CALL FOR HEAT—If low-pressure switch LPS is made when a call for heat is initiated, furnace control board flashes Fault Code 32 until
switch opens, then cycle begins.
LOW HEAT
1. PREPURGE—If low-pressure switch LPS does not make within 45 sec after call for heat is initiated, furnace control board starts flashing
Fault Code 32, shuts unit down, waits 2 minutes, stops flashing Fault Code 32, and restarts heating cycle.
If low-pressure switch LPS opens before ignition, furnace control board starts flashing Fault Code 32 and ramps inducer RPM up until
low-pressure switch LPS remakes. When low-pressure switch LPS remakes, furnace control board stops flashing Fault Code 32 and
continues heating cycle. If low-pressure switch LPS does not remake within 45 sec after opening, furnace control board continues flashing
Fault Code 32, shuts unit down, waits 2 minutes, stops flashing Fault Code 32, and restarts heating cycle.
2. STEADY-STATE—If low-pressure switch LPS opens during low heat, furnace control board starts flashing Fault Code 32, shuts unit
down, waits 2 minutes, stops flashing Fault Code 32, and restarts heating cycle.
HIGH HEAT
1. PREPURGE—If low-pressure switch LPS does not make within 45 sec after call for heat is initiated, furnace control board starts flashing
Fault Code 32, shuts unit down, waits 2 minutes, stops flashing Fault Code 32, and restarts heating cycle.
If low-pressure switch LPS opens before ignition, furnace control board starts flashing Fault Code 32, shuts unit down, waits 2 minutes,
stops flashing Fault Code 32, and restarts heating cycle.
2. STEADY-STATE—If low-pressure switch LPS opens during high heat, furnace control board starts flashing Fault Code 32, shuts unit
down, waits 2 minutes, stops flashing Fault Code 32, and restarts heating cycle.
STEP ACTION YES NO GO TO
1. Turn power off, remove blower access panel, and disconnect R thermostat lead. 2
2. Turn power on and depress door switch. Use a piece of tape to hold switch closed. 3
3. Is inducer motor MTR1 running? 45
4. Are inducer motor MTR1 and blower motor MTR2 running? 13 49
5. Jumper R and W/W1 thermostat terminals on furnace control board. 6
6. Observe operation of furnace through 1 heating cycle. 7
7. Does fault occur again? 11 8
8. Does a different fault occur? 910
9. Go to page number indicated in Index for fault code flashed. INDEX
10. Go to page number indicated in Index for CLEANUP AND STARTUP INSTRUCTIONS. INDEX
11. Does fault occur within 5 sec after a call for heat? 12 17
12.
Do you have 24v between N.O. (Normally Open) contact on low-pressure switch LPS and Com on
furnace control board?
14 47
13. Replace furnace control board. —— 10
14. Is low-pressure switch LPS wired correctly? 16 15
15. Rewire low-pressure switch LPS per wiring diagram. 10
16. Replace pressure switch assembly. 10
17. At start of cycle as inducer is ramping up, does low-pressure switch LPS make then break? 34 18
18. Does fault occur after ignition but before the blower comes on? 55 54
19.
Do you have 24v between C (Common) on low-pressure switch LPS and Com on furnace control
board?
24 20
20. Do you have 24v between connector terminal PL2-1 and Com on furnace control board? 21 13
21. Turn power off. —— 22
22.
Double check continuity between C (Common) on low-pressure switch LPS and connector terminal
PL2-1.
—— 23
23. The YELLOW wire to low-pressure switch LPS is not making good connection. Repair or replace it. 10
24.
Do you have at least 0.95 in. wc pressure drop (0.75 in. wc on trophy unit) across heat exchangers
when fault occurs? Determine this by connecting 1 side of a slope manometer with a tee to collector
box pressure tap. Connect other side with a tee to gas valve air pressure fitting. Refer to pressure
check diagram in Appendix C.
35 25
25. Is inducer motor MTR1 rotating in direction indicated on inducer housing? 28 26
26. Replace inducer motor or inducer motor assembly. 10
27. Fix problem. —— 10
28. Turn power off. —— 29
23
Page view 22
1 2 ... 18 19 20 21 22 23 24 25 26 27 28 ... 47 48

Comments to this Manuals

No comments