Copyright 2009 Carrier Corporation Form 50VQP-1PD
Single-package vertically mounted
water source heat pumps (WSHPs)
with electronic controls.
Non-ozone depleting Puron
refrigerant (R-410A)
Performance certified to ARI/ISO/
ASHRAE 13256-1
Wide application use with operating
temperature range of 20 F to 110 F
Dual refrigerant circuits for 2-stage
operation
High-efficiency scroll compressors
Thermostatic expansion valve (TXV)
provides efficient and reliable
refrigerant flow
High-static capability available
Available mute package for quiet
operation
Available low temperature insulation
to prevent condensation
Easy service access
Flexible and reliable multiple
protocol WSHP Open controller can
use BACnet*, Modbus†, N2, and
LON** (with separate card)
protocols for integrating energy
efficiency and precise unit control
Features/Benefits
Carrier’s Aquazone™ large
capacity units offer low cost,
energy efficient solutions for
all challenging water source
heat pump applications.
Operating efficiency
Carrier’s Aquazone large capacity
vertical water source heat pumps are
designed for quality and high perfor-
mance over a lifetime of operation.
Aquazone units offer cooling EERs
(Energy Efficiency Ratio) to 21.4 and
heating COPs (Coefficient of Perfor-
mance) to 5.1.
AQUAZONE
50VQP084-300
Vertical Large Capacity
Water Source Heat Pumps
with PURON
®
Refrigerant (R-410A)
7
to 25 Nominal Tons
Product
Data
TM
Page view 0
1 2 3 4 5 6 ... 59 60

Summary of Contents

Page 1 - Features/Benefits

Copyright 2009 Carrier Corporation Form 50VQP-1PDSingle-package vertically mounted water source heat pumps (WSHPs) with electronic controls.• Non-ozo

Page 2 - Features/Benefits (cont)

1050VQP084-150 UNITSUNIT 50VQPOVERALL CABINET (in.)DISCHARGE CONNECTIONS (in.)Duct FlangeWATER CONNECTIONS (in.)ELECTRICAL KNOCKOUTS (in.)RETURN AIR C

Page 3 - Maximum control flexibility

1150VQP168-300 UNITSUNIT 50VQPOVERALL CABINET (in.)DISCHARGE CONNECTIONS (in.)Duct FlangeWATER CONNECTIONS (in.)ELECTRICAL KNOCKOUTS (in.)RETURN AIR C

Page 4

12I Determine the actual cooling and heatingloads at the desired dry bulb and wet bulbconditions.Assume cooling load at desired dry bulb 80 F andwet b

Page 5 - Model number nomenclature

13VII ARI/ISO/ASHRAE 13256-1 ConversionPerformance standard ARI/ISO/ASHRAE 13256-1became effective on January 1, 2000 and replacedthe existing ARI Sta

Page 6 - Physical data

1450VQP0842800 CFM NOMINAL AIRFLOWLEGEND NOTES:1. Interpolation is permissable, extrapolation is not.2. All entering air conditions are 80 F db (dry b

Page 7 - Options and accessories

1550VQP0963200 CFM NOMINAL AIRFLOWLEGEND NOTES:1. Interpolation is permissable, extrapolation is not.2. All entering air conditions are 80 F db (dry b

Page 8 - Field-installed accessories

1650VQP1204000 CFM NOMINAL AIRFLOWLEGEND NOTES:1. Interpolation is permissable, extrapolation is not.2. All entering air conditions are 80 F db (dry b

Page 9 - WSHP OPEN SENSORS

1750VQP1505000 CFM NOMINAL AIRFLOWLEGEND NOTES:1. Interpolation is permissable, extrapolation is not.2. All entering air conditions are 80 F db (dry b

Page 10 - Dimensions

1850VQP1685600 CFM NOMINAL AIRFLOWLEGEND NOTES:1. Interpolation is permissable, extrapolation is not.2. All entering air conditions are 80 F db (dry b

Page 11 - 50VQP168-300 UNITS

1950VQP1926400 CFM NOMINAL AIRFLOWLEGEND NOTES:1. Interpolation is permissable, extrapolation is not.2. All entering air conditions are 80 F db (dry b

Page 12

2Efficiencies stated are in accordance with standard conditions under ISO (International Organization for Stan-dardization) Standard 13256-1 and pro-v

Page 13

2050VQP2408000 CFM NOMINAL AIRFLOWLEGEND NOTES:1. Interpolation is permissable, extrapolation is not.2. All entering air conditions are 80 F db (dry b

Page 14 - Performance data

2150VQP30010,000 CFM NOMINAL AIRFLOWLEGEND NOTES:1. Interpolation is permissable, extrapolation is not.2. All entering air conditions are 80 F db (dry

Page 15 - 50VQP096

22AIRFLOW CORRECTION TABLELEGENDENTERING AIR CORRECTION TABLE — HEATINGLEGENDENTERING AIR CORRECTION TABLE — COOLINGLEGEND*Sensible capacity equals to

Page 16 - Performance data (cont)

23ANTIFREEZE CORRECTION TABLELEGENDDRY COIL TO WET COIL CONVERSION TABLELEGENDNOTES:1. Sheave turns and RPM relationship is unchanged; use originalblo

Page 17 - 50VQP150

2450VQP084 BLOWER PERFORMANCE DATALEGEND NOTES:1. Unit is factory shipped with standard static sheave and drive at 2.5 turns open. Otherspeeds require

Page 18

2550VQP096 BLOWER PERFORMANCE DATALEGEND NOTES:1. Unit is factory shipped with standard static sheave and drive at 2.5 turns open. Otherspeeds require

Page 19 - 50VQP192

2650VQP120 BLOWER PERFORMANCE DATALEGEND NOTES:1. Unit is factory shipped with standard static sheave and drive at 2.5 turns open. Otherspeeds require

Page 20

2750VQP120 BLOWER PERFORMANCE DATA (cont)LEGEND NOTES:1. Unit is factory shipped with standard static sheave and drive at 2.5 turns open. Otherspeeds

Page 21 - 50VQP300

2850VQP150 BLOWER PERFORMANCE DATALEGEND NOTES:1. Unit is factory shipped with standard static sheave and drive at 2.5 turns open. Otherspeeds require

Page 22

2950VQP150 BLOWER PERFORMANCE DATA (cont)LEGEND NOTES:1. Unit is factory shipped with standard static sheave and drive at 2.5 turns open. Otherspeeds

Page 23 - ANTIFREEZE CORRECTION TABLE

3Ease of installationThe Aquazone™ unit is packaged for simple low cost handling, with minimal time required for installation. All units are pre-wired

Page 24

3050VQP168 BLOWER PERFORMANCE DATALEGEND NOTES:1. Unit is factory shipped with standard static sheave and drive at 2.5 turns open. Otherspeeds require

Page 25

3150VQP192 BLOWER PERFORMANCE DATALEGEND NOTES:1. Unit is factory shipped with standard static sheave and drive at 2.5 turns open. Otherspeeds require

Page 26

3250VQP240 BLOWER PERFORMANCE DATALEGEND NOTES:1. Unit is factory shipped with standard static sheave and drive at 2.5 turns open. Otherspeeds require

Page 27

3350VQP240 BLOWER PERFORMANCE DATA (cont)LEGEND NOTES:1. Unit is factory shipped with standard static sheave and drive at 2.5 turns open. Otherspeeds

Page 28

3450VQP300 BLOWER PERFORMANCE DATALEGEND NOTES:1. Unit is factory shipped with standard static sheave and drive at 2.5 turns open. Otherspeeds require

Page 29

3550VQP300 BLOWER PERFORMANCE DATA (cont)LEGEND NOTES:1. Unit is factory shipped with standard static sheave and drive at 2.5 turns open. Otherspeeds

Page 30

36ELECTRICAL DATA — STANDARD UNITLEGENDNOTES:1. HACR circuit breaker in U.S.A. only.2. All fuses Class RK-5.3. The 460-v units using an internal secon

Page 31

37ELECTRICAL DATA — DUAL POINT POWER UNITLEGENDNOTES:1. HACR circuit breaker in U.S.A. only.2. All fuses Class RK-5.3. The 460-v units using an intern

Page 32

38Typical piping and wiringTOptional DischargeSupply AirOptional DischargeAccessPanelAccessPanelAccessPanelAccessPanelVibrationPadControl BoxSupply Ai

Page 33

39Typical control wiring schematicsAL — Alarm RelayBC — Blower ContactorCB — Circuit BreakerCC — Compressor ContactorCO — Sensor, Condensate OverflowD

Page 34

4outdoor-air temperature, leaving-air temperature, leaving water tempera-ture, alarm status, and alarm lockout condition.The controller also provides

Page 35

40Typical control wiring schematics (cont)50VQP084-168 WITH DELUXE D CONTROL (TYPICAL)NOTES:1. Compressor and blower motor thermally protected interna

Page 36 - Electrical data

41NOTES:1. Compressor and blower motor thermally protected internally.2. All wiring to the unit must comply with NEC and local codes.3. Transformer is

Page 37

42Typical control wiring schematics (cont)NOTES:1. Compressor and blower motor thermally protected internally.2. All wiring to the unit must comply wi

Page 38 - Typical piping and wiring

43NOTES:1. Compressor and blower motor thermally protected internally.2. All wiring to the unit must comply with NEC and local codes.3. 208/230-v unit

Page 39 - A50-8438

44Typical control wiring schematics (cont)YWOGRCAL1AL2ACRCMP1FANPWRHS1/EXH/RVSPREMIERLINKCRCOMPLETECCONTROLJ4J6J5J8J1PWRSPSALWCMPSAFETTTY1GRCAL1CMP1FA

Page 40 - Deluxe D

45WSHP OPEN CONTROL012207-1BT485BTLED1DBInstall BT485 where device is located at the end of network segment only.+ 24vac(If not installed, it must be

Page 41

46Aquazone™ water source heat pump products are availablein a flexible, efficient array of models, which can be used inall types of water loop, ground

Page 42

47Vertical ground loop — This system is used in verticalborehole applications. This design is well suited for retrofitapplications when space is limit

Page 43

48WATER QUALITY GUIDELINESLEGEND*Heat exchanger materials considered are copper, cupronickel, 304 SS(stainless steel), 316 SS, titanium.†Closed recirc

Page 44

49Acoustical design Sound power levels represent the sound as it is producedby the source, the WSHP unit, with no regard to attenua-tion between the s

Page 45 - WSHP OPEN CONTROL

5ARI/ISO capacity ratings50VQP UNIT CAPACITY RATINGSLEGEND NOTES:1. Cooling capacities based upon 80.6 F db, 66.2 F wb entering airtemperature.2. Heat

Page 46 - Application data

50space. Typically a 6 dB sound reduction can beaccomplished with the use of flex duct.19. Locate the run-out duct balancing damper as far awayfrom th

Page 47 - Water conditioning

51WSHP Open sequence of operationThe WSHP Open multi-protocol controller will control me-chanical cooling, heating and waterside economizer out-puts b

Page 48 - Application data (cont)

52• Condensate overflow input is normal.• If occupied, the SPT is greater than the occupied cool-ing set point.• Space temperature reading is valid.•

Page 49 - WSHP sound control

53connected to a coil on the discharge side of the unit andsupplied by a boiler in order to maintain the desired heat-ing set point should the compres

Page 50

54the entering water loop temperature is suitable (at least5 F below space temperature). If the optional coil is pro-vided and the water loop conditi

Page 51 - Controls

55Commercial Vertical Water Source Heat Pump Units with Puron® Refrigerant (R-410A)HVAC Guide SpecificationsSize Range: 84,000 to 300,000 Bt

Page 52 - Controls (cont)

56e. High voltage protection.f. Condensate overflow shutdown.g. Unit shutdown on low refrigerant pressures.h. Unit shutdown on high or low water tempe

Page 53

576. LonWorks Interface System:Units shall have all features listed above (eitherComplete C or Deluxe D) and the control boardshall be supplied with a

Page 54

585. Fire-Rated Hose Kits:Kits include a fixed MPT on one end and aswivel with an adapter on the other end. Hosekits can be either stainless steel or

Page 56 - Guide specifications (cont)

650VQP UNIT PHYSICAL DATA LEGENDNOTES:1. All units have grommet and spring compressor mountings, and1/2 in. and 13/4 in. electrical knockout

Page 57

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Pg 6

Page 58

7Factory-installed optionsCupronickel heat exchangers are available for highercorrosion protection for applications such as open tower,geothermal, etc

Page 59

8Field-installed accessoriesCarrier’s line of Aquazone™ thermostats are bothattractive and multi-functional, accommodating stand-alone water source h

Page 60 - Section 6

9COOLHEATAUTOR5-DAY PROGRAMMABLE/NON-PROGRAMMABLEAUTOPmCOOLHEATCarrier®AQUAZONE™ THERMOSTATS7-DAY PROGRAMMABLE/LIGHT-ACTIVATED PROGRAMMABLE7-DAY PROGR