ELECTRICAL WORK
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
C: Putting nut on
Remove flare nuts attached to indoor and
outdoor unit, then put them on pipe/tube
having completed burr removal.(not possible
to put them on after flaring work)
Flare nut
Copper tube
Fig.17
Fig.18
D: Flaring work
Firmly hold copper pipe in a die in the
dimension shown in the table below.
Caution
Align the center of the pipes.
Sufficiently tighten the flare nut with fingers,
and then tighten it with a spanner and torque
wrench as shown.
Tightening Connection
Excessive torque can break nut
depending on installation conditions.
Fig.19
Indoor unit tubing Flare nut Pipings
Electric safety regulations for the initial Installation
1. If there is serious safety problem about the
power supply, the technicians should refuse
to install the air conditioner and explain to the
client until the problem is solved.
2. Power voltage should be in the range of 90%~
110% of rated voltage.
3. The creepage protector and main power switch
with a 1.5 times capacity of Max. Current of the
unit should be installed in power circuit.
4. Ensure the air conditioner is grounded well.
7.
5. According to the attached Electrical Connection
Diagram located on the panel of the outdoor
unit to connect the wire.
6. All wiring must comply with local and national
electrical codes and be installed by qualified
and skilled electricians.
An individual branch circuit and single receptacle
used only for this air conditioner must be available.
Electrical work
Outer diam.
(mm)
A(mm)
Max. Min.
6.35 1.3 0.7
9.52
1.6 1.0
12.7
1.8
1.0
12.7
1.8
1.0
Outer
diam.
Tightening
torque(N.cm)
Additional tightening
torque(N.cm)
6.35
1570
(160kgf.cm)
1960
(200kgf.cm)
4900
(500kgf.cm)
5390
(550kgf.cm)
12.7
9.52
2940
(300kgf.cm)
3430
(350kgf.cm)
NOTE: Thesupply voltage must be consistent with the rate
voltage of the air conditioner.
Minimum norminal cross-sectional area of conductors:
Rated current of appliance
(A)
Nominal cross-sectional area
(mm )
2
>3 and <6
>6 and <10
>10 and <16
>16 and <25
0.75
1
1.5
2.5
Model
Power supply
Input Rated Amp
(Switch/Fuse)
10A/15A
16A
220-240V~ 50Hz
or
220-230V~60Hz
12000Btu/h
12000Btu/h