40QAQ060 with 38QRR 060
13 SEER Underceiling Syst e m
Performancet Series Heat Pump
with Puron Refrigerant
Submittal Data
Job Data:_________________________________________________ Location:________________________________________
Buyer:________________________________________ Buyer P.O.#_______________________Carrier # _________________
Unit Number:__________________________________ Model Number: _____________________________________________
Performance Data Certified By: _________________________________________ Date: _______________________________
40QAQ
38QRR
the environmentally sound refrigerant
FEATURES
S
Mounting bracket
S Electro mechanical controls
S Built--in electric heat
S Auto restart after power failure
S User selectable fan speeds plus auto
S Cleanable filters
S Motorized louvers
S Accessory wired user interfaces
S Capable of connecting to an Energy Management system
S Up to 200 ft (61 m) total piping (accessories required)
S Accessory fresh air intake kit
S Low ambient operation down to -- 20_F (28.9_C)
w/accessory
S Accessory condensate pump
S Power ventilation accessory
S Limited Warranty: 1--year parts / 5--year compressor
S Optional extended parts and labor warranty
Indoor Unit -- 40QAQ / Outdoor Unit -- 38QRR
(Unless otherwise indicated, data applies to both indoor and outdoor models)
SYSTEM SIZE 060...........................................
REFRIGERANT R--410A......................................
PERFORMANCE
Cooling Nominal Capacity (Btuh) 60,000........................
Heating Nominal Capacity (Btuh) 60,000........................
SEER 13..................................................
HSPF 7.7.................................................
Moisture Removal Rate(Pints/hr) 14.5...........................
Airflow (Low/Med/High) 1040 / 1220 / 1600.....................
SOUND PRESSURE (dBA)
Indoor (Low/Med/High) 54.8 / 57.8 / 59.1.....................
Outdoor 61..............................................
SOUND POWER (dBA)
Indoor (Low/Med/High) 65.8 / 68.8 / 70.1.....................
Outdoor 72..............................................
PERFORMANCE AT ACTUAL CONDITIONS:
Attached j Not Attached j
ELECTRICAL
System Voltage 208/230 --1; 208/230-- 3; 460-- 3 V...................
MCA
Indoor 34.5; 21.5; 10.6....................................
Outdoor (208/230 --1; 208/230-- 3; 460--3) 28.7..................
MOCP 30.................................................
Indoor 15...............................................
Outdoor (208/230 --1; 208/230-- 3; 460--3) 60; 35; 15.............
Fan Motor (Indoor) (FLA) 2.6.................................
Electric Heat (kW) 5.00......................................
CONTROLS
Control Remote Wired.......................................
Control Voltage 24v.........................................
Control Wiring (0--75 ft.) 18 AWG..............................
Control Wiring (75--200 ft.) 16 AWG............................
REFRIGERANT LINES (Insulate v apor line)
Liquid Line (in.) OD 3/8.....................................
Vapor Line (in.) OD 7/8.....................................
Metering/Control Device Accurater at outdoor unit................
* Refer to NEC and local codes for compliance requirements.
Thermostat Slim Line 7 --day Programmable: Required j Not Required j
Flat Stat 7 --day Programmable: Required j Not Required j
Thermostat Super T2 5--1--1 Commercial: Required j Not Required j
Remote Room Sensor Kit: Required j Not Required j
Condensate Pump: Required j Not Required j
Fresh Air Intake Kit: Required j Not Required j
Low Ambient Kit: Required j Not Required j
Isolation Relay: Required j Not Required j
Crankcase Heater: Required j Not Required j
Wind Baffle: Required j Not Required j