TEC40ELECTRONIC CONTROLLERBARD MANUFACTURING COMPANYBryan, Ohio 43506Since 1914...Moving ahead, just as planned.Manual: 2100-393CSupersedes: 2100-393
Manual 2100-393Page 8FIGURE 4TWO UNIT MODE WITH ECONOMIZERSMIS-1657A
Manual 2100-393Page 9FIGURE 5TWO UNIT MODE WITHOUT ECONOMIZERSMIS-1658
CONTENTSShipping Damage... 1General ...
Manual 2100-393Page 1SHIPPING DAMAGEUpon receipt of equipment, the carton should bechecked for external signs of shipping damage. Ifdamage is fou
Manual 2100-393Page 2Sequence of Operation – HeatingFirst stage heating set point is determined bysubtracting the dead band setting from cooling se
Manual 2100-393Page 3Second stage cooling set point is 2.0 degrees warmerthan first stage cooling set point. On a call for secondstage cooling, t
Manual 2100-393Page 4If the jumper is set to 7 days (or other selected choice),units will rotate upwards: first to second, second tothird, third t
Manual 2100-393Page 57960-477FIGURE 1CONTROL LOCATIONS
Manual 2100-393Page 6FIGURE 2FOUR UNIT MODE WITHOUT ECONOMIZERSFOUR UNIT MODE WITH ECONOMIZERS
Manual 2100-393Page 7THREE UNIT MODE WITHOUT ECONOMIZERSTHREE UNIT MODE WITH ECONOMIZERSFIGURE 3