APPENDIX C
PRESSURE CHECK DIAGRAM
PRESSURE SWITCH MAKE/BREAK POINTS
UNIT SIZE
(BTUH)
HIGH PRESSURE SWITCH MEDIUM PRESSURE SWITCH LOW PRESSURE SWITCH
Make Point Break Point Make Point Break Point Make Point Break Point
60,000
(17.5” casing)
1.21 in.wc max
1.05 in. wc +/-
0.06
0.85 in. wc max
0.70 in. wc +/-
0.05
0.62 in. wc max
0.47 in. wc +/-
0.05
60,000
(21” casing)
1.46 in.wc max
1.29 in. wc +/-
0.07
1.00 in. wc max
0.85 in. wc +/-
0.05
0.64 in. wc max
0.49 in. wc +/-
0.05
80,000
1.58 in.wc max
1.40 in. wc +/-
0.08
1.00 in. wc max
0.85 in. wc +/-
0.05
0.75 in. wc max
0.60 in. wc +/-
0.05
100,000
1.58 in.wc max
1.40 in. wc +/-
0.08
1.08 in. wc max
0.93 in. wc +/-
0.05
0.87 in. wc max
0.72 in. wc +/-
0.05
120,000
1.58 in.wc max
1.40 in. wc +/-
0.08
1.05 in. wc max
0.90 in. wc +/-
0.05
0.80 in. wc max
0.65 in. wc +/-
0.05