NOTE: Read the entire instruction manual before starting the installation.
This symbol indicates a change since the last issue.
SAFETY CONSIDERATIONS
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified personnel should
install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed
by trained service personnel. When working on heating equipment, observe precautions in the literature, on tags, and on labels attached to or
shipped with the unit, and other safety precautions that may apply.
Follow all safety codes. In the United States, follow all safety codes including the National Fuel Gas Code (NFGC) NFPA No. 54-1999/ANSI
Z223.1-1999. In Canada, refer to the National Standard of Canada, Natural Gas and Propane Installation Codes (NSCNGPIC), CAN/CGA-B149.1
and .2-M00.
Wear safety glasses and work gloves. Have a fire extinguisher available during start-up, adjustment procedures, and service calls.
Recognize safety information. This is the safety-alert symbol
. When you see this symbol on the furnace and in instructions or manuals, be
alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. The words DANGER, WARNING, and CAUTION are used with
the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies
hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury,
or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
WARNING: This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer’s
instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these
instructions is not followed exactly, a fire, explosion, or production of carbon monoxide may result causing property
damage, personal injury, or loss of life. The qualified service agency is responsible for the proper installation of this furnace
with this kit. The installation is not proper and complete until the operation of the converted appliance is checked as
specified in the manufacturer’s instructions supplied with the kit.
AVERTISSEMENT: Cette trousse de conversion ne doit être installée que par le représentant d’un organisme qualifié
et conformément aux instructions du fabricant et à tous les codes et exigences pertinents de l’autorité compétente. Les
instructions du présent guide doivent être suivies afin de réduire au minimum au risque d’incendie ou d’explosion de
dommange matériels, de blessure ou de mort. L’organisme qualifié responsable de l’installation adéquate de cette trousse.
L’installation n’est pas adéquate ni complète tant que le bon fonctionnement de l’appereil converti n’a pas été vérfié selon
les instructions du fabricant fornies avec la trousse.
INTRODUCTION
This instruction covers the installation of gas conversion kit Part No. KGANP2801F80 to convert the following furnaces from natural gas usage
to propane gas usage. See the appropriate section for your furnace type.
Section 1—Models 58DFA, 58GFA, 58PAP, 58RAP, 373LAD, 383KAD, 394HAD, 396HAD, GA1AAD, and GA2AAD Induced-
Combustion, Standing Pilot, Fixed-Speed, Non-Condensing Furnaces. This kit is designed for use in 065 through 150 size furnaces. The gas
valve will be either a Honeywell VR8200H or BR8300H.
CERTIFIED
Installation Instructions
KGANP2801F80
Gas Conversion Kit Natural-to-
Propane for Standing Pilot and
HSI Fixed-Speed Non-Condensing Furnaces
Form: AG-GANP-26 Cancels: AG-GANP-24 Printed in U.S.A. 4-01 Catalog No. 63GA-NP7
Page view 0
1 2 3 4 5 6 ... 11 12

Summary of Contents

Page 1 - Installation Instructions

NOTE: Read the entire instruction manual before starting the installation.This symbol → indicates a change since the last issue.SAFETY CONSIDERATIONSI

Page 2

4. Turn furnace gas valve control switch or control knob to ON position.5. Check all threaded pipe connections for gas leaks.WARNING: NEVER use a matc

Page 3 - DIRECTLY BELOW FRONT EDGE

PROCEDURE 5—SET GAS INPUT RATEThe gas input rate for propane is the same as for natural gas. See furnace rating plate for input rate. The input rate f

Page 4 - APPLIANCE MODELS

© 2001 CAC/BDP P.O. Box 70, Indianapolis, IN 46206 agganp26—12—Book/Tab: 1/6a, 4/8a Catalog No. 63GA-NP7

Page 5

• Section 2—Models 58DHC, 58PAV, 58RAV, 58SSC, 58WAV, 58YAV, 58ZAV, 373LAV, 376CAV, 383KAV, 393AAV, 395CAV, 480BAV,481BAV, GB1AAV, GB3AAV, PG8DAA, and

Page 6

Fig. 1—Downflow, Standing-Pilot, Fixed-Speed, Non-Condensing Furnace Component and Conversion Label LocationA95457BLOWERCOMPARTMENTDOORGAS VALVEBURNER

Page 7 - CLEARANCE

CAUTION: DO NOT redrill burner orifices. Improper drilling (burrs, out-of-round holes, etc.) can cause excessiveburner noise and misdirection of burne

Page 8

4. Turn on furnace power supply.5. Turn gas supply manual shutoff valve to ON position.6. Turn furnace gas valve control knob to PILOT position and de

Page 9

6. Light pilot in accordance with furnace lighting instructions.7. Turn furnace gas valve control knob to ON position.8. Set room thermostat to call f

Page 10 - NATURAL – SILVER, 10 TURNS)

PROCEDURE 7—APPLY LABELSNOTE: See Fig. 1 or 2 for label location.1. Fill in Conversion Responsibility Label (326755-205) and apply to inside furnace c

Page 11 - MANOMETER

5. Remove burners from manifold.6. Remove and discard orifices from manifold.7. Refer to Fig. 4 to determine main burner orifice.Furnace gas input rat

Page 12

3. Turn on furnace power supply.4. Turn gas supply manual shutoff valve to ON position.5. Turn furnace gas valve control switch or control knob to ON