Installation Instructions
Gas Conversion Kit Natural ---to---Propane for
Non---Condensing 80 % and
Condensing 90 % F urnaces
Fixed Capacity , 2---Stage, V ariable Speed
TABLE OF CONTENTS
Safety Considerations 1..............................
Introduction 2......................................
Description and Usage 2..............................
Induced Combustion, Single-- Stage, Non-- Condensing
Furnaces 2.................................
Induced Combustion, Two-- Stage and Variable Speed, Non--
Condensing Furnaces 10......................
Direct--Vent, Multipoise, Single--Stage Condensing
Furnaces 15................................
Direct/Non--Direct Vent,Two--Stage and Variable--Speed Multi-
poise and Dedicated Upflow Condensing
Furnaces 22...............................
NOTE: Read the entire instruction manual before starting the
installation.
SAFETY CONSIDERATIONS
Installing and servicing heating equipment can be hazardous due
to gas and electrical components. Only trained and qualified
personnel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions,
such as cleaning and replacing air filters. Trained service
personnel must perform all other operations. When working on
heating equipment, observe precautions in the literature, on tags,
and on labels attached to or shipped with the unit, and other
safety precautions that may apply .
Follow all safety codes. In the United States, follow all safety
codes including the National Fuel Gas Code (NFGC) NFPA
54--2006/ANSI Z223.1 --2006. In Canada, refer to the National
Standard of Canada, Natural Gas and Propane Installation Codes
(NSCNGPIC), CAN/CGA--B149.1 and .2--M05.
Wear safety glasses and work gloves. Have a fire extinguisher
available during start--up, adjustment Steps, and service calls.
Recognize safety information. This is the safety-- alert symbol
. When you see this symbol on the furnace and in
instructions or manuals, be alert to the potential for personal
injury .
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety--alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies a hazard
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which ma y result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced installation,
reliability, or operation.
D
E
S
I
G
N
C
E
R
T
I
F
I
E
D
CERTIFIED
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal
injury or death.
This conversion kit shall be installed by a qualified service
agency in accordance with the manufacturers instructions
and all applicable codes and requirements of the authority
having jurisdiction. If the information in these instructions
is not followed exactly, a fire, explosion, or production of
carbon monoxide could result causing property damage,
personal injury, or loss of life. The qualified service agency
is responsible for the proper installation of this furnace with
this kit. The installation is not proper and complete until the
operation of the converted appliance is checked as specified
in the manufacturer’ s instructions supplied with the kit.
!
WARNING
LE FEU, L’EXPLOSION, CHOC ELECTRIQUE,
ET MONOXYDE DE CARBONE
EMPOISONNER
Cette trousse de conversion doit être instale par un servie
d’entretien qualifié, selon les instructions du fabricant et
selon toutes les exigences et tous les codes pertinents de
l’autori compétente. Assurezvous de bien suivre les
instructions dans cette notice pour duire au minimum le
risque d’incendie, d’explosion ou la production de
monoxyde de carbone pouvant causer des dommages
mariels, de blessure ou la mort. Le service d’entretien
qualif est responsable de l’installation de cette trousse.
L’installation n’est pas adéquate ni complète tant que le bon
fonctionnement de l’appereil converti n’a pas é vérf
selon les instructions du fabricant fornies avec la trousse.
!
AVERTISSEMENT
Page view 0
1 2 3 4 5 6 ... 29 30

Summary of Contents

Page 1 - Installation Instructions

1KGANP4601ALLInstallation InstructionsGas Conversion Kit Natural ---to---Propane forNon---Condensing 80 % andCondensing 90 % F urnacesFixed Capacity ,

Page 2 - Spoiler Screws

10FactoryClearanceLabelApply ConversionResponsibility Labelon exterior of doorFactory InformationLabelBlower DoorRating Plate onexterior of doorExisti

Page 3

11Gas input rate on furnace rating plate is for installations ataltitudes up to 2000 ft. (609 M).In the U.S.A., the input rating for altitudes above 2

Page 4

12A93347Fig. 25 -- Igniter to Burnerb. Install HSI and bracket to burner assembly.c. Insert one--piece burner in slot on sides of burner box andslide

Page 5

13ManometerconnectionA05191Fig. 29 -- LGPS Installed9. Do not install regulator seal caps at this time.10. Go to Step 3.For Fig.271. Be sure gas and e

Page 6

14FIRE AND EXPLOSION HAZARDFailure to follow this warning could result in personal injuryand/or death.NEVER test for gas leaks with an open flame. Use

Page 7

15A08099Fig. 32 -- Conversion Kit Rating Plate 334263-- 20414. Observe unit operation through two complete heatingcycles. See sequence of operation in

Page 8

16D’EQUIPMENT D’OPERATIONLors des opérations d’entretien des commandes, étiquetertous les fils avant de les déconnecter. Toute erreur decâblage peut ê

Page 9

17A93347Fig. 37 -- Position of Silicon Carbide IgniterStep 2 — Convert and Pre--Adjust Gas ValveNOTE: There are three variations of single stage gas v

Page 10 - PRUDENCE

18REGULATOR SEAL CAPREGULATORADJUSTMENTSCREWREGULATOR SPRING(PROPANE - WHITE, 8.5 TURNSNATURAL - SILVER, 8.5 TURNS)GAS PRESSURE REGULATOR ADJUSTMENTMA

Page 11 - KGANP4601ALL

19BLWNUETRALSTATUS CODE LEDSEC-2 SEC-1EAC-2 L2FUSE 3-AMP0.5 AMP@24VACHUMTEST/TWIN G Com W Y R24V120 18090 150BLOWER OF

Page 12

2INTRODUCTIONThis instruction covers the installation of gas conversion kit PartNo. KGANP4601ALL to convert the following furnaces fromnatural gas usa

Page 13

20765432101234567BURNER ENCLOSURE(REMOVE COVER WHEN CHECKING PRESSURE)GAS VALVEPRESSURESWITCH(ES)(LOCATION WILL VARYDEPENDING ON MODEL)MANOMETERA01070

Page 14 - AVERTISSEMENT

21Step 5 — Pressure Switch Wiring (Refer to furnacewiring diagram)1. Disconnect yellow wire from pressure switch (PRS) onfurnace inducer housing. Atta

Page 15 - FURNACES

22Step 9 — Check Low Gas Pressure Switch OperationThe newly installed low gas pressure switch is a safety deviceused to guard against adverse burner o

Page 16

23In Canada, the input rating must be derated by 5 percent foraltitudes of 2000 ft. (609 M) to 4500 ft. (1372 M) above sealevel.The Conversion Kit Rat

Page 17

24PROPANEGASPOSITIONAIRSHUTTERA96264Fig. 52 -- Air Shutter In Propane Gas Usage (PROP) PositionCOMBUSTION AIRINTAKE BOX SCREWSCOMBUSTIONAIR INTAKE BOX

Page 18 - All Furnaces

25DIVERTER PLATEPART NO. 323184-301A95450Fig. 55 -- Installing Diverter PlateBURNERIGNITOR1332"1132"78" (22 mm)IGNITERASSEMBLYIGNITERAS

Page 19

262-5/32˝(55 mm)A04181A05075Fig. 57 -- Position of Igniter to BurnerStep 4 — Install Manifold Assembly, All Furnaces1. Reinstall manifold, orifice, an

Page 20

27A05196Fig. 58 -- Series G and J Gas ValveONOFFON/OFFSWITCHINLETPRESSURETA PBURNER ENCLOSUREREFERENCE PRESSURE TAP(2-STAGEAND VARIABLE-SPEED, CONDENS

Page 21

2812345678 9PR2L2COMPR1L1EAC-2EAC-1HI-COOLHI-GAS-HEATLO-GAS-HEATPARK3FU1SEC-1SEC-2112345678910 11 12MASTER SLAVETWINTESTLEDGRY/Y2W/W1COM24 VW21ONOFF12

Page 22

29Model PlugSet up Switches SW1, 1 thru 8A/C & Constant Air FlowSwitchesStatus Code LightFuse, 3 Amp24 VAC OutputNeutral Leads and EAC 2 (Neutra

Page 23 - S Re--install burners

3Table 1 – Kit ContentsDESCRIPTION PART NO. QUANTITYMain Burner Orifice (Drill Size 1.30 mm) LH32DB210 7Main Burner Orifice (Drill Size 1.25 mm) LH32D

Page 24

30BURNER FLAMEBURNERMANIFOLDA89020Fig. 67 -- Burner Flamec. Remove jumper across R, W1, and W2 after high--heatadjustment to terminate call for heat.

Page 25

4A03059Fig. 2 -- Component LocationA06432Fig. 3 -- Location of Dimple for Spoiler ScrewNOTE: Models 310JAV, 311JAV, 313JAV, 58STX, 58DLX,58PHX, PG8JAA

Page 26

51-7/8(47.6 mm)A05026Fig. 6 -- Igniter to BurnerA93347Fig. 7 -- Igniter to Burner18. Secure manifold to left side of burner box, verifying thatgreen g

Page 27

6REGULATOR SEAL CAPREGULATORADJUSTMENTSCREWREGULATOR SPRING(PROPANE - WHITE, 8.5 TURNSNATURAL - SILVER, 8.5 TURNS)GAS PRESSURE REGULATOR ADJUSTMENTMAN

Page 28 - Necessary Adjustments

7BLWNUETRALSTATUS CODE LEDSEC-2 SEC-1EAC-2 L2FUSE 3-AMP0.5 AMP@24VACHUMTEST/TWIN G Com W Y R24V120 18090 150BLOWER OFF

Page 29

8BLWNUETRALSTATUS CODE LEDSEC-2 SEC-1EAC-2 L2FUSE 3-AMP0.5 AMP@24VACHUMTEST/TWINY1 DHUM G COM W/W1 Y/Y2 R24VPLT120 18090 150BLO

Page 30 - MANIFOLD

9A08098Fig. 16 -- Conversion Kit Rating Plate -- 334263-- 207NOTE: Use propane-- gas--resistant pipe dope to prevent gasleaks. DO NOT use Teflon tape.

Comments to this Manuals

No comments