Guide Specification for AHUCU-6
Project: Mount Vernon 11/24/2014
Prepared By: Joe Bailey
Residential Carrier Products Bldr 1.19q Page 11 of 14
Operating Characteristics
The capacity of the unit will meet or exceed _____ Btuh at a suction temperature of _____ _F/_C. The power consumption at full load will not
exceed _____ kW.
Combination of the unit and the evaporator or fan coil unit will have a total net cooling capacity of _____ Btuh or greater at conditions of _____
CFM entering air temperature at the evaporator at _____ _F wet bulb and _____ _F/_C dry bulb, and air entering the unit at _____ _F/_C.
The system will have a SEER of _____ Btuh/watt or greater at DOE conditions.
Electrical Requirements
Nominal unit electrical characteristics will be _____ v, single phase, 60 hz. The unit will be capable of satisfactory operation within voltage
limits of _____ v to _____ v.
Nominal unit electrical characteristics will be _____ v, three phase, 60 hz. The unit will be capable of satisfactory operation within voltage
limits of _____ v to _____ v.
Unit electrical power will be single point connection.
Control circuit will be 24v.
Special Features
Refer to section of this literature identifying accessories and descriptions for specific features and available enhancements.
SYSTEM DESIGN SUMMARY
1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than .01--in. wc.
2. Minimum outdoor operating air temperature without low--ambient operation accessory is 55_F (12.8_C).
3. Maximum outdoor operating air temperature for cooling mode is 125_F (51.7_C).
4. Minimum outdoor operating air temperature for heating mode is 30_F (–34.4_C).
5. Maximum outdoor operating air temperature for heating mode is 66_F (18.9_C).
6. For reliable operation, unit should be level in all horizontal planes.
7. For interconnecting refrigerant tube lengths greater than 80 ft (23.4 m) and/or elevation differences between indoor and outdoor units greater than
20 ft (6.1 m), consult Residential Piping and Longline Guideline and Service Manual available from equipment distributor.
8. If any refrigerant tubing is buried, provide a 6 in. (152.4 mm) vertical rise to the valve connections at the unit. Refrigerant tubing lengths up to 36
in. (914.4 mm) may be buried without further consideration. Do not bury refrigerant lines longer than 36 in. (914.4 mm).
9. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.
10. Do not apply capillary tube indoor coils to these units.
11. Factory--supplied filter drier must be installed.
Guide Specifications Fan Coils Fixed Speed
Guide Specifications for ________________________________.
(See the most recent edition of publication ___________________for data for the specific model to be specified).
Furnish and Install _________________ direct expansion fan coil(s) equipped with cooling control kit and _____(with)
_____(without) electric heater in the location and manner shown on the plan. Unit shall operate properly in _____(vertical
upflow) _____(horizontal right) _____(horizontal left) _____(vertical downflow) position and is to be installed with ductwork.
Total cooling capacity shall be ______ Btuh or greater, and sensible heat capacity shall be _____Btuh or greater, at conditions of
_____ cfm, _____degree F wb _____degree F db air entering unit, and a coil refrigerant temperature of _____ degree F.
Efficiency shall be __________ when matched with outdoor unit _____________ (per ARI ratings certification).
Unit enclosure shall be insulated with a 1 inch foil faced, high density, R4.2 insulation, and be constructed of prepainted galvanized
steel. Large front service access panels shall provide easy access to all components. Unit shall be _____ (factory), _____ (field)
equipped with reusable type filters. Filter shall be _____inches (X) _____ inches.
Fan shall be forward curved with double inlet, mounted on motor shaft, dynamically and statically balanced. The fan shall deliver
_____ cfm with _____ in. wg external static pressure operating at _____ hp. Fan-motor assembly shall be removable for service.
Blower motor shall be induction type, of _____ hp.
Cooling coil shall have a face area of not less than _____sq. ft. and be constructed with brazed copper tubing with aluminum lanced
fins. Coil shall have TXV ( thermal expansion valve); refrigerant line fittings which permit braze connections. Condensate pans