Page 1 - Air-Cooled Chillers

Installation, operation and maintenance instructions30HXC 075-37030GX 080-350Screw CompressorWater-Cooled Chillers andAir-Cooled Chillers30HXC Nominal

Page 2

10DIMENSIONS, CLEARANCES, WEIGHT DISTRIBUTION (CONT.)30GX 205-265NOTE : Refer to certified dimensional drawings 99DI 205GX when designing an installat

Page 3 - List of contents

11DIMENSIONS, CLEARANCES, WEIGHT DISTRIBUTION (CONT.)30GX 280-350NOTE : Refer to certified dimensional drawings 99DI 280GX when designing an installat

Page 4

12MAIN COMPONENTS LOCATION30HXC 075-185Legend:ACircuit ABCircuit BWater inlet (flanges supplied)Water outlet (flanges supplied)12 1211 113212021202522

Page 5

13MAIN COMPONENTS LOCATION (CONT.)30HXC 215-280Legend :ACircuit ABCircuit BITEM DESIGNATION1 Cooler water inlet and outlet2 Cooler 3/8" NPT air v

Page 6

14PHYSICAL DATA30HXC30HXC 075 085 095 105 115 125 135 145 160 170 185Nominal gross cooling capacity* kW 268 295 346 373 404 439 485 519 550 593 639Ope

Page 7 - 30HXC 300-370

15ELECTRICAL DATA30HXC30HXC 075 085 095 105 115 125 135 145 160 170 185Mains power supplyNominal voltage V-ph-Hz 400-3-50Voltage range % ± 10Control c

Page 8 - 30GX 080-160

16PHYSICAL DATA30GX30GX 080 090 105 115 125 135 150 160 175Nominal gross cooling capacity* kW 262 290 330 373 405 438 484 526 576Operating weight kg 3

Page 9 - 30GX 175

17ELECTRICAL DATA30GXCompressorPART NUMBER Tons LRA (Y) LRA (Delta) MHA06NA 1146 S7 N 39 191 605 10406NA 1174 S7 N 46 226 715 12606NA 1209 S7 N 56 270

Page 10 - 30GX 205-265

18APPLICATION DATAUnit operating rangeCooler Minimum MaximumCooler entering water temperature °C 6.8* 21Cooler leaving water temperature °C 4** 15Cond

Page 11 - 30GX 280-350

19Variable flow evaporatorVariable evaporator flow can be used in standard 30HXC and 30GXchillers. The chillers maintain a constant leaving water temp

Page 12 - 30HXC 075-185

2The cover photograph is for illustrative purposes onlyand is not part of any offer for sale or contract.

Page 13 - 30HXC 215-280

20Flow controllersCooler flow switch and chilled water pump interlockIMPORTANTIt is mandatory to install cooler flow switch and also to connectchilled

Page 14 - * Eurovent conditions :

21LIFTING INSTRUCTIONS30HXC 075-185This diagram is shown for information only. Refer to “certifieddrawings” delivered with the unit.30HXC X (mm) Y (mm

Page 15 - Compressor

22LIFTING INSTRUCTIONS (CONT.)30HXC 215-280This diagram is shown for information only. Refer to “certifieddrawings” delivered with the unit. CENTER O

Page 16

23LIFTING INSTRUCTIONS (CONT.)30HXC 300-370This diagram is shown for information only. Refer to “certifieddrawings” delivered with the unit. CENTER O

Page 17

24LIFTING INSTRUCTIONS (CONT.)30GX 080-160This diagram is shown for information only. Refer to “certifieddrawings” delivered with the unit. CENTER OF

Page 18

25LIFTING INSTRUCTIONS (CONT.)30GX 205-265This diagram is shown for information only. Refer to “certifieddrawings” delivered with the unit.30GX X (mm)

Page 19 - GOOD BAD GOOD

26153726104812 911PIPING CONNECTIONSRefer to the certified dimensional drawings for the sizes andpositions of all water inlet and outlet connections.

Page 20 - 5 x D MINI

27ELECTRICAL CHARACTERISTICS• The 30HXC 075-185 and 30GX 080-175 have only one powerterminal block.• The 30HXC 215-370 and 30GX 205-350 have two power

Page 21 - 1500 mm min

28FIELD POWER SUPPLY30HXC 075-185Electrical boxS mm2S mm230HXC A (mm) B (mm) Min. Max.075-115 125 236 70 120125 125 236 95 120135-185 136 200 120 185S

Page 22 - 50 mm min

29FIELD POWER SUPPLY (CONT.)30HXC 215-280Electrical boxSA mm2SB mm230HXC A (mm) Min. Max. Min. Max.215-280 125 120 185 70 120SA mm2SB mm230HXC A (mm)

Page 23 - 70° max

3List of contentsINTRODUCTION ... 4SAFETY CONSIDERATIONS ...

Page 24 - 150-160 2186 1391 932

30FIELD POWER SUPPLY (CONT.)30HXC 300-370Electrical boxSA mm2SB mm230HXC A (mm) B (mm) Min. Max.300 125 236 95 120315-370 125 200 120 185SA mm2SB mm23

Page 25 - CENTER OF GRAVITY

31FIELD POWER SUPPLY (CONT.)30GX 080-160Electrical boxFIELD CONTROL WIRINGRefer to the Certified Electrical Wiring Diagram supplied withthe unit for t

Page 26

32FIELD POWER SUPPLY (CONT.)30GX 175Electrical boxS mm230GX Min. Max.175 2x120 2x300Power terminal block Main disconnect switchIMPORTANTBefore the con

Page 27

33FIELD POWER SUPPLY (CONT.)30GX 205-265Electrical boxSA mm2SB mm230GX Min. Max. Min. Max.205 240 300 95 185225 240 300 120 185250 2x120 2x185 120 185

Page 28

34FIELD POWER SUPPLY (CONT.)30GX 280-350Electrical boxSA mm2SB mm230HXC Min. Max. Min. Max.280-295 2x120 2x300 240 300325 2x150 2x300 2x120 2x300350 2

Page 29

35MAJOR SYSTEM COMPONENTSAND OPERATION DATAGeared twin screw compressor• 30HXC and 30GX units use 06N geared twin screwcompressors• 06NA are used on 3

Page 30 - GROUND FIELD CONNECTION

36the EXV flashes to vapor, further subcooling the liquid that ismaintained at the bottom of the economizer. This increase insubcooling provides addit

Page 31 - CONNECTION

37Control componentsProcessor module (PSIO)It contains the operating software and controls the operation of themachine. It has 12 input channels and 6

Page 32

38The CPM communicates on the COMM3 communication bus tothe PSIO module. Proper operation of the CPM board can be verifiedby observing the three LED&a

Page 33

39CONTROL OPERATIONKeypad and display module usage (HSIO II)FUNCTION USEKEYS<STAT> STATUS - For displaying diagnostic codes and currentoperating

Page 34

4INTRODUCTIONPrior to initial start-up of the 30HXC and 30GX unit, thoseinvolved in the start-up, operation, and maintenance should bethoroughly famil

Page 35

40Accessing functions and subfunctionsOPERATION KEYPAD ENTRY DISPLAY RESPONSETo access a function, press subfunction <1> <TEST> Circuit A

Page 36

41Status functionThis function shows the rotating display, current status of alarmand alert (diagnostic) codes, capacity stages, operating modes,chill

Page 37

42STATUS (CONT.)SUBFUNCTION KEYPAD DISPLAY COMMENTENTRY4 Circuit A discrete <4><STAT> CIR. A DISCRETE OUTPUTSOutputs<↓> Compressor A

Page 38

43STATUS (CONT.)SUBFUNCTION KEYPAD DISPLAY COMMENTENTRY<↓> 2 CHLLR COMM FAILURE<↓> CIR A LOW DISCHG SUPERHT<↓> CIR B LOW DISCHG SUPE

Page 39

44TEST (CONT.)SUBFUNCTION KEYPAD DISPLAY COMMENTENTRY4 Valves and <4><TEST> VALVES AND MOTOR MASTERMotor Master <↓> Circuit A EXV Va

Page 40

45SERVICE (CONT.)SUBFUNCTION KEYPAD DISPLAY COMMENTENTRY<↓> Water Valve Type 0 = None (Default),1 = 4-20 mA,2 = 0-10 V,3 = 20-4 mA,4 = 10-0 V<

Page 41

46History function and subfunctionsHISTORYSUBFUNCTION KEYPAD DISPLAY COMMENTENTRY1 Operating Hours <1> <HIST> Machine Operating Hoursxxx.x

Page 42 - CCN: Carrier Confort Network

47Setpoint functionSetpoints are entered through the keypad. Setpoints can bechanged within the upper and lower limits, which are fixed. Theranges are

Page 43

48Head pressure controlGeneralThe microprocessor controls the condenser fans (30GX) oranalogue water valve (30HXC) to maintain the saturatedcondensing

Page 44

4930GX fan arrangement30GX 080-090-10530GX 115-125-13530GX 150-16030GX 175-205-22530GX 250-26530GX 28030GX 29530GX 325-350Fan stage Fans controlled on

Page 45

5DIMENSIONS, CLEARANCES, WEIGHT DISTRIBUTION30HXC 075-185NOTE : Refer to certified dimensional drawings 99DI 075HX when designing an installation.P1ØS

Page 46

50PRE-START-UP PROCEDUREDo not attempt to start the chiller until the following checks havebeen completed.System Check1 - Check all auxiliary componen

Page 47

51TROUBLESHOOTINGThe 30HXC/GX Screw chiller control has many features to aidthe technicians in troubleshooting. By using the keypad anddisplay module

Page 48

52Alarm/Alert Alarm Description Why was this Action taken Reset Probablecode or Alert alarm generated ? by control method cause0 – No alarms or alerts

Page 49 - 30GX fan arrangement

53Alarm/Alert Alarm Description Why was this Action taken Reset Probablecode or Alert alarm generated ? by control method cause11 Alert Condenser leav

Page 50

54Alarm/Alert Alarm Description Why was this Action taken Reset Probablecode or Alert alarm generated ? by control method cause40 Alert Compressor A1

Page 51

55Alarm/Alert Alarm Description Why was this Action taken Reset Probablecode or Alert alarm generated ? by control method cause67 Alert Circuit A high

Page 52 - Alarms and alerts codes table

56The two setpoints are used by the control for the low oil pressurealert trip criteria below:1. Oil Pressure is ignored during the first five seconds

Page 53

57MAINTENANCERefrigerant Charging - Adding ChargeIMPORTANTThese units are designed for use with R-134a only. DO NOTUSE ANY OTHER refrigerant in these

Page 54

585. Add 2.5 kg of liquid charge into the cooler using chargingvalve located in the top of the cooler.6. Allow the system to stabilize and then rechec

Page 55

59Service replacement compressorCompressor rotation controlCorrect compressor rotation is one of the most critical applicationconsiderations. Reverse

Page 56 - OIL SETPOINT 2

6DIMENSIONS, CLEARANCES, WEIGHT DISTRIBUTION (CONT.)30HXC 215-280NOTE : Refer to certified dimensional drawings 99DI 215HX when designing an installat

Page 57

60START-UP CKECKLIST FOR 30HXC/GX LIQUID CHILLERS (USE FOR JOB FILE)Preliminary informationJob name: ...

Page 58

61Check condenser system (30HXC) All condenser water valves are open All condenser piping is connected properly All air has been vented from the syste

Page 59

62Check pressure drop across the condenser (30HXC only)Entering condenser = ... (kPa)Leaving condenser =...

Page 60

63 Review and record field configuration, <2> <SRVC>External reset sensor ...

Page 61

Manufacturer reserves the right to change any product specifications without notice.Manufacturer: Carrier s.a., Montluel, France.BP 49 Route de Thil01

Page 62

7DIMENSIONS, CLEARANCES, WEIGHT DISTRIBUTION (CONT.)30HXC 300-370NOTE : Refer to certified dimensional drawings 99DI 300HX when designing an installat

Page 63

8DIMENSIONS, CLEARANCES, WEIGHT DISTRIBUTION (CONT.)30GX 080-160NOTE : Refer to certified dimensional drawings 99DI 080GX when designing an installati

Page 64 - Fax: 04 72 25 22 51

9DIMENSIONS, CLEARANCES, WEIGHT DISTRIBUTION (CONT.)30GX 175NOTE : Refer to certified dimensional drawings 99DI 175GX when designing an installation.N