
Application data
Unit selection
Select equipment to either match or be slightly less than
anticipated peak load. This provides better humidity con-
trol, fewer unit cycles, and less part-load operation.
For units used in spaces with high sensible loads, base
equipment selection on unit sensible load, not on total an-
ticipated load. Adjust for anticipated room wet bulb tem-
perature to avoid undersizing equipment.
When selecting equipment which has outdoor air intro-
duced into the unit, determine the mix conditions of room
air and outdoor air at design conditions. The cooling ca-
pacity tables in this literature are based on 80 F edb. Adjust
for actual dry-bulb and wet-bulb conditions with the required
outdoor air to select the proper equipment.
Unit combinations and coil mixed matches
The 38AN and 38HDC units are the only units approved
for use with the Carrier 40QNB, 40QAB, and 40QKB duct-
free split systems. The 38AN and 38HDC units can also be
used with other fan coil units.
Mixed matches of indoor-fan coil capacity more than one
size larger than the outdoor condensing unit capacity may
result in inadequate indoor comfort. Do not select mixed
matches where the indoor-fan coil capacity is more than
one size larger than the outdoor condensing unit capacity
unless specifically indicated in this data. Heat pump fan coils
can be used with cooling-only condensing units to provide
electric heat capability.
Unit mounting (outdoor)
Unit leveling — For reliable operation, units should be
level in all planes.
Clearance — Adequate clearance must be provided for
airflow. See dimensional drawings for proper clearances.
The condensing units are designed for free-blow applica-
tion. Air inlets and outlets should not be restricted. Outdoor
fan external static pressure available is less than
0.1 in. wg.
Unit location — Cooling units may be stacked 2 high.
Units may be wall mounted, pad mounted at ground level,
roof mounted, or mounted on or under a deck or patio. Be
sure water from roof does not drain directly onto the unit.
See your Carrier representative for drawings to construct
stacking rails or wall mounting brackets.
If 38HDC condensing units are being mounted near a
wall, the condenser air should discharge toward the wall.
This will provide inherent coil protection and the best pos-
siblesound and airflow performance. The 38AN units should
be mounted with fan discharge pointing away from the wall.
Unit mounting (indoor)
Unit leveling — For reliable operation, units should be
level in all planes. The 40QAB ceiling-suspended fan coils
may have a slight pitch, but only toward the drain
connection.
Clearance — Provide adequate clearance for airflow. The
unit return and discharge should not be obstructed by fur-
niture, curtains, or anything which may cause unit short cy-
cling or air recirculation. See base unit dimensional draw-
ings on pages 18-24 for required clearances.
Unit location — When selecting unit location, select a lo-
cationwhich will provide the best air circulation for the room.
40QNB HIGH WALL UNITS — These units should be po-
sitioned as high as possible on the wall for best air circula-
tion. Allow adequate clearances above the unit for servicing
(removing unit covers). Place the unit in the middle of the
wall selected (if possible). Select an outside wall if available
to make piping easier, and place the unit so it faces the
normal location of room occupants.
40QABCEILING-SUSPENDEDUNITS—These unitsshould
be mounted near the ceiling and against a wall. The unit
should be centered in the room for best performance. Lo-
cating the unit on an outside wall will make piping easier,
but units can also be mounted away from a wall if desired.
(If the unit is mounted away from a wall, the rear panel of
the unit may need a field-supplied trim strip for improved
appearance.) Locate the fan coil return over an area which
isnot normally occupied for quietest operation. Do not block
air discharge for a minimum of 15 ft to prevent dumping of
cold air and drafts.
40QKB IN-CEILING CASSETTE UNITS — These units
should be mounted in the ceiling, preferably near the cen-
ter of the room. If the unit must be mounted near a wall,
close the air discharge on the blocked side(s). (Up to 2 sides
may be blocked.) Locate the control box away from the
blocked side(s).
Mounting template
The 40QAB and QNB fan coil units are furnished with
mounting templates or mounting plates to mark the loca-
tion of the mounting brackets, wiring, and refrigeration line
hole locations. In addition, the 40QAB units indicate the
location of ventilation-air connections.
Support
Adequate support must be provided to support the weight
of all fan coils. Refer to the Physical Data section on
page 11 for fan coil weights, and the base unit dimensional
drawings on pages 18-24 for the location of mounting
brackets.
System operating conditions
Operating limits:
OUTDOOR CONDENSING UNITS
CONDITION 38AN 38HDC
Maximum Cooling Ambient (F) 125 125
Minimum Cooling Ambient (F) (without
accessory low-ambient kit)
55 55
Minimum Cooling Ambient (F) (with
accessory low-ambient kit)
–20 –20
Minimum Cooling Return-Air Temperature (F) 55 55
Maximum Cooling Return-Air Temperature (F) 95 95
Saturated Suction Temperature Range
Minimum (F) –15 –15
Maximum (F) 55 55
Saturated Condensing Temperature Range
Minimum (F) 85 80
Maximum (F) 150 150
Maximum Compressor Discharge
Temperature (F)
275 275
Minimum Discharge Superheat (F) 60 60
46
Comments to this Manuals