Fan Performance 48PMD24 Vertical Supply/Return Units
CFM
Available External Static Pressure (in. wg)
0.2 0.4 0.6 0.8 1.0 1.2
RPM BHP Drive RPM BHP Drive RPM BHP Drive RPM BHP Drive RPM BHP Drive RPM BHP Drive
6000 629 1.62 A 688 1.88 A 743 2.15 A 796 2.44 A 848 2.75 A 902 3.10 A
6400 661 1.91 A 717 2.20 A 770 2.48 A 820 2.78 A 869 3.09 A 919 3.43 A
6800 693 2.24 A 747 2.55 A 798 2.85 A 845 3.16 A 892 3.48 A 939 3.82 A
7200 726 2.61 A 777 2.94 A 826 3.26 A 872 3.58 A 917 3.91 A 960 4.25 A
7600 758 3.02 A 808 3.37 A 855 3.70 A 899 4.04 A 942 4.38 B 984 4.74 B
8000 792 3.48 A 839 3.84 A 884 4.19 A 927 4.55 B 969 4.91 B 1009 5.27 B
8400 825 3.97 A 871 4.35 B 914 4.73 B 956 5.10 B 996 5.48 B 1035 5.85 C
8800 858 4.52 B 902 4.91 B 945 5.31 B 985 5.70 B 1024 6.09 C 1061 6.48 C
9200 892 5.11 B 934 5.52 B 975 5.94 C 1014 6.35 C 1052 6.76 C 1088 7.17 C
9600 926 5.75 C 967 6.18 C 1006 6.62 C 1044 7.05 C 1081 7.48 C 1116 7.90 C
10000 960 6.45 C 999 6.90 C 1037 7.35 C 1074 7.80 C 1110 8.25 C 1144 8.69 D
CFM
Available External Static Pressure (in. wg)
1.4 1.6 1.8 2.0 2.2 2.4
RPM BHP Drive RPM BHP Drive RPM BHP Drive RPM BHP Drive RPM BHP Drive RPM BHP Drive
6000 958 3.51 A 1016 3.98 A 1074 4.50 B 1130 5.06 B 1182 5.63 B 1230 6.19 C
6400 970 3.82 A 1022 4.26 A 1076 4.76 B 1131 5.31 B 1184 5.90 C 1235 6.50 C
6800 985 4.19 A 1033 4.61 B 1083 5.08 B 1134 5.60 B 1185 6.17 C 1236 6.79 C
7200 1004 4.63 B 1049 5.03 B 1094 5.47 B 1141 5.96 C 1188 6.51 C 1237 7.10 C
7600 1026 5.11 B 1067 5.51 B 1109 5.94 C 1152 6.41 C 1196 6.92 C 1241 7.48 C
8000 1048 5.65 B 1088 6.05 C 1128 6.47 C 1168 6.93 C 1208 7.42 C 1250 7.95 C
8400 1073 6.24 C 1110 6.64 C 1148 7.07 C 1186 7.51 C 1224 7.99 C 1263 8.50 C
8800 1098 6.88 C 1134 7.29 C 1170 7.72 C 1206 8.16 C 1242 8.63 D 1278 9.13 D
9200 1124 7.58 C 1159 8.00 C 1193 8.43 C 1228 8.88 D 1262 9.35 D 1296 9.84 D
9600 1151 8.33 C 1184 8.76 D 1218 9.20 D 1251 9.66 D 1284 10.13 D 1316 10.62 D
10000 1178 9.13 D 1211 9.58 D 1243 10.04 D 1275 10.50 D 1307 10.97 D 1338 11.46 ---
LEGEND
Bhp - Brake Horsepower Input to Fan
Rpm - Fan speed
Drive - Drive option code based on 460V motor max BHP
Grey cells indicate field-supplied pulley change required.
Fan Performance 48PME24 and 48PMF24 Vertical Supply/Return Units
CFM
Available External Static Pressure (in. wg)
0.2 0.4 0.6 0.8 1.0 1.2
RPM BHP Drive RPM BHP Drive RPM BHP Drive RPM BHP Drive RPM BHP Drive RPM BHP Drive
6000 648 1.70 A 706 1.97 A 760 2.24 A 812 2.53 A 865 2.85 A 920 3.22 A
6400 681 2.01 A 736 2.30 A 788 2.58 A 837 2.88 A 887 3.21 A 937 3.56 A
6800 715 2.36 A 767 2.67 A 817 2.97 A 864 3.28 A 910 3.61 A 957 3.96 A
7200 749 2.75 A 799 3.08 A 846 3.40 A 892 3.72 A 936 4.06 A 980 4.41 B
7600 783 3.19 A 831 3.53 A 877 3.87 A 920 4.21 A 962 4.55 B 1004 4.92 B
8000 817 3.67 A 863 4.03 A 907 4.38 B 949 4.74 B 990 5.10 B 1030 5.47 B
8400 851 4.19 A 896 4.57 B 939 4.94 B 979 5.32 B 1018 5.69 B 1057 6.07 C
8800 886 4.77 B 929 5.16 B 970 5.56 B 1009 5.95 C 1047 6.34 C 1084 6.73 C
9200 921 5.39 B 962 5.81 C 1002 6.22 C 1040 6.63 C 1077 7.04 C 1113 7.45 C
9600 956 6.07 C 996 6.50 C 1034 6.94 C 1071 7.36 C 1107 7.79 C 1142 8.22 C
10000 991 6.81 C 1029 7.26 C 1067 7.71 C 1103 8.15 C 1137 8.60 C 1171 9.04 D
CFM
Available External Static Pressure (in. wg)
1.4 1.6 1.8 2.0 2.2 2.4
RPM BHP Drive RPM BHP Drive RPM BHP Drive RPM BHP Drive RPM BHP Drive RPM BHP Drive
6000 976 3.65 A 1034 4.14 A 1092 4.68 B 1147 5.24 B 1198 5.81 C 1244 6.36 C
6400 988 3.97 A 1041 4.43 B 1095 4.95 B 1150 5.51 B 1202 6.11 C 1252 6.72 C
6800 1004 4.35 B 1053 4.79 B 1103 5.28 B 1154 5.82 C 1205 6.41 C 1255 7.04 C
7200 1024 4.80 B 1069 5.22 B 1114 5.68 B 1162 6.19 C 1210 6.76 C 1258 7.37 C
7600 1046 5.30 B 1087 5.71 B 1130 6.16 C 1173 6.65 C 1218 7.18 C 1263 7.77 C
8000 1069 5.86 C 1109 6.27 C 1149 6.71 C 1189 7.18 C 1230 7.69 C 1272 8.25 C
8400 1094 6.47 C 1132 6.88 C 1170 7.32 C 1208 7.78 C 1246 8.28 C 1285 8.81 D
8800 1121 7.14 C 1157 7.56 C 1192 8.00 C 1228 8.46 C 1265 8.94 D 1301 9.46 D
9200 1148 7.86 C 1182 8.29 C 1217 8.74 D 1251 9.20 D 1285 9.68 D 1320 10.19 D
9600 1176 8.65 D 1209 9.09 D 1242 9.54 D 1275 10.00 D 1308 10.49 D 1341 10.99 D
10000 1204 9.49 D 1236 9.94 D 1268 10.40 D 1300 10.87 D 1332 11.36 --- --- --- ---
LEGEND
Bhp - Brake Horsepower Input to Fan
Rpm - Fan speed
Drive - Drive option code based on 460V motor max BHP
Grey cells indicate field-supplied pulley change required.