264975-BIM-B-1208
Johnson Controls Unitary Products 13
NOTE: A one-inch clearance must be provided between
any combustible material and the supply ductwork
for a distance of 3 feet from the unit.
NOTE: If the unit includes gas heating, locate the unit so
the flue exhaust is at least:
• Three (3) feet above any forced air inlet located within 10
horizontal feet (excluding those integral to the unit).
• Four (4) feet below, four (4) horizontal feet from, or one
(1) foot above any door or gravity air inlet into the build-
ing.
• Four (4) feet from electric meters, gas meters, regula-
tors, and relief equipment.
FIGURE 8 - UNIT DIMENSIONS
See Detail
A
For Baserail
Dimensions
See Detail B
89
27
59
4-1/4
6-3/16
17-3/16
24-3/16
30-3/16
Convenience
Power
Outlet
Entry
Ø 7/8
Power
Entry
Ø 2-1/2
30-11/32
Control
Entry
Ø 7/8
Power
Entry
Ø 2-1/2
LEFT
FRONT
For Drain
Dimensions
See Detail C
11-1/2
X
TABLE 6: UNIT HEIGHT
Unit Model Number X
DL-06
50 3/4
DL-07
42
DL-08
42
DL-10
50 3/4
DL-12
50 3/4
DU-06
42
DU-07
42
DU-08
42
DU-10
50 3/4
DU-12
50 3/4
TABLE 7: UNIT CLEARANCES
Top
1
1.
Units must be installed outdoors. Overhanging structure or
shrubs should not obstruct condenser air discharge outlet.
72”
Right
12”
Front
2
2.
The products of combustion must not be allowed to
accumulate within a confined space and re-circulate.
36”
Left
36”
Rear
3
3.
To remove the slide-out drain pan, a rear clearance of
sixty inches is required. If space is unavailable, the
drain pan can be removed through the front by separat-
ing the corner wall.
36”
Bottom
4
4.
Units may be installed on combustible floors made from
wood or class A, B or C roof covering materials.
0”
5 - 1 / 4
B a s e
P a n
1 7 - 1 3 / 1 6
V i e w o f W a l l A c r o s s f r o m C o i l
G a s P i p e I n l e t
DETAIL A
3 - 3 / 4
3 - 9 / 1 6
2 - 3 / 8
5 - 3 / 8
DETAIL C