Carrier 48HJ004---007 Specifications

Browse online or download Specifications for Heat pumps Carrier 48HJ004---007. Carrier 48HJ004---007 Specifications User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 55
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
48HJ004-007
Single-Package Rooftop Heating/Cooling
Standard and Low NOx Units
Installation, Start-Up and
Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS ...................... 1
INSTALLATION ................................ 1-36
Step 1 -- Provide Unit Support ................... 1
ROOF CURB
SLAB MOUNT
ALTERNATE UNIT SUPPORT
Step 2 -- Field Fabricate Ductwork ............... 2
Step 3 -- Install External Trap for
Condensate Drain .............................. 4
Step 4 -- Rig and Place Unit ..................... 4
POSITIONING
Step 5 -- Install Flue Hood ....................... 5
Step 6 -- Install Gas Piping ...................... 5
Step 7 -- Make Electrical Connections ........... 5
FIELD POWER SUPPLY
FIELD CONTROL WIRING
HEAT ANTICIPATOR SETTINGS
Step 8 -- Adjust Factory-Installed Options ...... 13
COBRA TM ENERGY RECOVERY UNITS
HUMIDI-MIZER TM ADAPTIVE
DEHUMIDIFICATION SYSTEM
MANUAL OUTDOOR-AIR DAMPER
CONVENIENCE OUTLET
NOVAR CONTROLS
PREMIERLINK TM CONTROL
OPTIONAL ECONOMISER IV AND ECONOMISER2
ECONOMISER IV STANDARD SENSORS
ECONOMISER IV CONTROL MODES
Step 9 -- Adjust Evaporator-Fan Speed ......... 25
PRE-START-UP .................................. 37
START-UP .................................... 37-42
SERVICE ..................................... 42-48
TROUBLESHOOTING ......................... 49-53
INDEX ........................................... 54
START-UP CHECKLIST ........................ CL-I
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electric_d compo-
nents. Only trained and qualifed service personnel should
install, repair, or service ai>conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on ai>conditioning equipment, observe precau-
tions in the literature, tags and labels attached to the unit, and
other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers avaihtble for all brazing operations.
Before performing service or maintenance operations on
unit, turn off main power switch to unit and install lockout
tag. Ensure electrical service to rooftop unit agrees with
voltage and amperage listed on the unit rating phtte. Elec-
tricgd shock could cause personal injury.
Disconnect gas piping from unit when leak
testing at pressure greater than 1/2psig. Pres-
sures greater than ]h psig will cause gas valve
damage resulting in haz_u'dous condition. If
gas valve is subjected to pressure greater titan
1h psig, it mustbe replaced before use. When
_ressure testing field-supplied gas piping at
_ressures of I/2 psig or less, a unit connected
o such piping must be isohtted by manu_dly
closing the gas valve(s).
INSTALLATION
Unit is shipped in the vertical dischtuge configuration. To
convert to horizontal discharge application, remove duct open-
ing coveLs. Using the same screws, install covers on duct open-
ings in basepan of unit with insulation-side down. Seals around
openings must be tight. See Fig. 1.
Step 1 -- Provide Unit Support
ROOF CURB -- Assemble and install accessory roof curb in
accor&mce with instructions shipped with curb. See Fig. 2. In-
stall insulation, cant strips, roofing felt, and counter flashing as
shown. Ductwork must be attached to curb, not to the unit.
If electric control power or gas service is to be routed through
the basepan, attach the accessory thin-the-bottom service con-
nections to the basepan in accordance with the accessory instal-
lation instructions. Connections must be inst_dled before unit is
set on roof curb.
IMPORTANT: The gasketing of the unit to the roof curb is ]
critical for a watertight seal. Install gasket supplied with the
I
roof curb as shown in Fig. 2. hnproperly applied gasket can
result in air leaks and poor unit performance.
Curb should be level. Unit leveling tolerances are shown in
Fig. 3. This is necessary for unit drain to lhnction properly.
Refer to Accessory Roof Curb [nstalhttion Instructions for
additional infomtation as required.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53480013-01 Printed in U,S.A. Form 48HJ-33SI Pg 1 9-05 Replaces: 48HJ-29SI
Page view 0
1 2 3 4 5 6 ... 54 55

Summary of Contents

Page 1 - Service Instructions

48HJ004-007Single-Package Rooftop Heating/CoolingStandard and Low NOx UnitsInstallation, Start-Up andService InstructionsCONTENTSPageSAFETY CONSIDERAT

Page 2 - SUPPLY DUCT OPENING COVER

BLK1YEL208/230-1-60(SIZES 48HJ004-006)EQUIPGNDF--t_Ii1PI ELD POWER SUPPLY_ .L .L L __FDISOON.EDT7PER NECL* ... JBLK _ TO COMPI,,I;%F'i'FIEL

Page 3 - SECTION "C C"

UNIT48HJOO4(3 Tons)005(4 Tons)006(5 Tons)0O7(6 Tons)Table 2A -- Electrical Data -- Standard Motor Units Without Electrical Convenience OutletVOLTAGE C

Page 4 - OlOCl C

Table 20 -- Electrical Data -- High-Static Motor Units Without Electrical Convenience OutletUNIT48HJO04005006007NOMINAL VOLTAGEVOLTAGE RANGE(V-Ph-Hz)

Page 5 - Fig. 6 -- Rigging Details

Step 8 -- Adjust Factory-Installed OptionsCOBRA TM ENERGY RECOVERY UNITS -- Please leferto the supplement provided for information on installing andop

Page 6 - 9 71"7

CB -- Circuit BreakerCR -- Cooling RelayDHR -- Dehumidify RelayDSV -- Discharge Solenoid ValveHR -- Heater RelayLPS -- Low Pressure SwitchLSV -- Liqui

Page 7 - Fig. 8-- Flue Hood Details

SCREWHOLES(TOP)HOOD_SCREENLOCATIOK(SCREENNOT SHOWN)Fig. 19 -- Outdoor-Air Damper withHood Attached0.60.5_" 0,4UIo303LUm 0.313.LU>0.2Zoo 1 2 3

Page 8 - Table 1 -- Physical Data

Table 3- PremierLink TM Sensor UsageOUTDOOR AIR RETURN AIR OUTDOOR AIR RETURN AIRAPPLICATION TEMPERATURE SENSOR TEMPERATURE SENSOR ENTHALPY SENSOR ENT

Page 9

PREMIERLINKCONTROL©©HINGEDDOORPANELPREMIERLINKCOVERFig. 21B -- PremierLink TM Controller (Installed)OUTD_R AiR i ' GRAY 'ENTHALPY SENSOR [Ec

Page 10 - I;%F'i'

Outdoor Air Enthalpy Sensor/Enthalpy Controller(HH57AC077) -- To wire the outdoor tfir enthalpy sensor.perform the following (see Fig. 23 and 24):NOTE

Page 11

FILTER ACCESS PANEL_COMPRESSORACCESS PANELOUTDOOR-AIR OPENING ANDINDOOR COIL ACCESS PANELFig. 27- Typical Access Panel LocationsHOOD BOXBRACKETi Iii I

Page 12

SLAB MOUNT (Horizontal Units Only) -- Provide a levelconcrete slab that extends a minimum of 6 in. beyond unit cab-inet. Install a gravel apron in fro

Page 13 - TM control)

FOR OCCUPANCY CONTROLREPLACE JUMPER WITHFIELD-SUPPLIED TIME CLOCK/(F]ELDACCESSORY)REMOTE MI_POSiI[O_ POTIR_M0_FOT71_ 0_-m}--8LKECONO_I ZZR MOTORWHT_RE

Page 14 - TM Device

2500Wz 2000w 1500Wm 1000o5000ZfI0.05 0] 15 0.25STATIC PRESSURE (in. wg)Fig. 34 -- Barometric Flow Capacity"530LUh-z_ 25cc 20LUD_I-- 15LULUEL 10Ca

Page 15 - Hood Attached

outdoortemperatureis comptu'edto anadjustablesetpointselectedonthecontrol.If theoutdoor-airtemperatureisabovethesetpoint,theEconoMiSerIV will adj

Page 16 - HVAC SENSOR INPUTS

usingthismodeof changeovercontrol,turntheenthalpyset-pointpotentiometerfullyclockwisetotheDsetting.Indoor Air Quality (IAQ) Sensor Input -- The IAQ in

Page 17 - 8_[)

Exhaust Set Point Adjustment -- The exhaust set point willdetermine when the exhaust fan runs based on dmnper position(if accessory power exhaust is i

Page 18 - EOO Oo E v

EconoMiSerIVcontrollerwilloutputthe6.7voltsfiomtheCO2sensortotheactuatorwhentheCO2concentrationinthespaceisfit1100ppm.TheDCVsetpointmaybeleftfit2volts

Page 19 - Fig. 28- Hood Box Removal

0.350.25 -0.10.054&5ton6 ton3 ton0 i i i i [0 1000 2000 3000 4000 5000 6000Fig. 44 -- Humidi-MiZer TM Adaptive Dehumidification System Static Pres

Page 20 - ACCESSORY

UNIT UNIT48HJ PHASESingleO04ThreeSingle005ThreeSingle006Three007 ThreeLEGENDBhp i Brake HorsepowerTable 9 -- Evaporator-Fan Motor Data -- Standard Mot

Page 21

Table 12 -- Fan Performance 48HJ004 -- Vertical Discharge Units; Standard Motor (Belt Drive)*AIRFLOWCFM900100011001200130014001500EXTERNAL STATIC PRES

Page 22 - Sensor Mounting Location

Table 14 -- Fan Performance 48HJ005 -- Vertical Discharge Units; Standard Motor (Belt Drive)*AIRFLOWCFM120013001400150016001700180019002000EXTERNAL ST

Page 23

D ALTCONNECTOR B C DRAIN GAS POWER CONTROL ACCESSORYPKG. ACCY. HOLE POWERCRBTMPWROO1A01 3/41' 3/4" [19] NPTCRBTMPWROO2A01 [19] NPT 11/4"

Page 24

AIRFLOWCFM15001600170018001900200021002200230024002500Table 16 -- Fan Performance 48HJ006, Single-Phase -- Vertical Discharge Units;Standard Motor (Be

Page 25 - Economizer

Table 18 -- Fan Performance 48HJ006 -- Vertical Discharge Units; High-Static Motor (Belt Drive)*AIRFLOWCFM15001600170018001900200021002200230024002500

Page 26 - SINGLE-GROOVE

Table 20 -- Fan Performance 48HJ007 -- Vertical Discharge Units; High-Static Motor (Belt Drive)*AIRFLOWCFM18001900200021002200230024002500260027002800

Page 27 - GENERAL FAN PERFORMANCE NOTES

Table 22 i Fan Performance 48HJ004 i Horizontal Discharge Units; High-Static Motor (Belt Drive)*AIRFLOWCFM900100011001200130014001500EXTERNAL STATIC P

Page 28

Table 24 i Fan Performance 48HJ005 i Horizontal Discharge Units; High-Static Motor (Belt Drive)*AIRFLOWCFM120013001400150016001700180019002000EXTERNAL

Page 29

AIRFLOWCFM15001600170018001900200021002200230024002500Table 26 -- Fan Performance 48HJ006, Three-Phase -- Horizontal Discharge Units;Standard Motor (B

Page 30 - Standard Motor (Belt Drive)*

Table 28 -- Fan Performance 48HJ007 -- Horizontal Discharge Units; Standard Motor (Belt Drive)*AIRFLOWCFM180019002000210022002300240025002600270028002

Page 31

PRE-START-UPFailure to observe the following warnings could result inserious pel.sonal injuu:1. Follow recognized safety practices and wear protec-tiv

Page 32

Thesuctionanddischm'gepressurelevelsshouldnowmovetotheirnorm_flstart-uplevels.NOTE:Whenthecompressorisrotatingin thewrongdirec-tion,fileunitwillm

Page 33

Theevaporator-fanoffdelaycanalsobemodified.Oncethecallforheatinghasended,thereisa10-minuteperiodduringwhichthemodificationcanoccm:If thelimitswitchtri

Page 34

UM ALLOWABLEDIFFERENCE (in.)B OlOCl C0.5 1.0 1.0Fig. 3 -- Unit Leveling TolerancesStep 3 -- Install External Trap for CondensateDrain -- The unit&apos

Page 35

• If compressor one is on then second stage of mechanicalcooling will be energized. Otherwise the first stage willbe energized.• Integrator resets.• E

Page 36

HEATING. UNIT WITH ECONOMISER2, PREMIERLINKCONTROL AND A ROOM SENSOR -- Every 40 secondsthe controller will calculate the required heat stages (maximu

Page 37 - 1/2 psig

Theneteffectoftherooftopwheninhotgasreheatmodeistoprovidenearly_dllatentcapacitylemovalfiomthespacewhensensibleloadsdiminish(whenoutdoortemperatmecon-

Page 38 - 48HJ004-006 Low NOx Units

LubricationCOMPRESSORS -- Each compressor is chmged with correctamount of oil at the factory.FAN MOTOR BEARINGS -- Fan motor bemings are of thepermane

Page 39 - Operating Sequence

HUMIDI-MIZER TM SYSTEM CHARGING -- The systemcharge for units wifll the Humidi-MiZer a&tptive dehumidifi-cation system is greater than that of the

Page 40 - Control Example

TO USE COOLING CHARGING CHART, STANDARDUNIT--Take the outdoor ambient temperature trod madthe suction pressure gage. Refer to ch_uts to detennine what

Page 41 - Mode Operation

Flue Gas Passageways -- To inspect the flue collec-tor box and upper areas of the heat exchanger:1. Remove the combustion blower wheel and motor assem

Page 42 - Reheat Mode Operation

CLEANING AND ADJUSTMENT1. Remove burner rack from unit as described above.2. Inspect burners and, if dirty, remove burners from rack.3. Using a soft b

Page 43 - Lubrication

SCHEHATIC208/2303 BOSEE NOTE *3 _EQUP GNDi i GRN/YELI_CLOPL6 RFOR STDUNIT PL6--<_l-YECONOMI*ERI_--PNK REDIONNECTIOIBOARD.YEL*.BLU.-BLK---BRN.--RED°

Page 44 - ,CTiONLIRETEMPERATURE

TROUBLESHOOTINGUnit Troubleshooting -- Refer to Tables 34-38 for unittroubleshooting details.Table 34 -- LED Error Code Service AnalysisSYMPTOM CAUSE

Page 45 - 5 tON GOHZ

36"- 54"(914-1371)POSITION ALL SEAL STRIPSIN PLACE BEFORE POSITIONINGUNIT ON ROOF CURB,DUCT ENDSEE "A_DETAILPLACE UNIT ON CURB AS CLOSE

Page 46

PROBLEMBurners Will NotIgnite.Table 35 -- Heating Service AnalysisCAUSEMisaligned spark electrodes.No gas at main burners.Water ingas line.No power to

Page 47 - DETAIL "E"

Table 38 -- Cooling Service AnalysisPROBLEMCompressor and Condenser FanWill Not Start.Compressor Will Not StartBut Condenser Fan Runs.Compressor Cycle

Page 48 - 208/2303 BO

EconoMiSer IV Troubleshooting -- See Table 39for EconoMi$er IV logic.A functional view of the EconoMi$er is shown in Fig. 68.Typical settings, sensor

Page 49 - TROUBLESHOOTING

7. Remove jumper flom TR to N.8. Remove jumper fiom TR to 1.9. Remove 5.6 kilo-ohm resistor from T and TI. Reconnectwiles tit T and TI.l 0. Remove jum

Page 50

INDEXAccess panels 19 FilterAltitude compensation 38 Cleaning 42Barometric flow capacity 21 Installation 19Burner ignition 46 Size 9Burner rack 46 Flu

Page 51

I. PRELIMINARY INFORMATIONMODEL NO.:DATE:START-UP CHECKLIST(Remove and Store in Job File)SERIAL NO.:TECHNICIAN:II. PRE-START-UP (insert checkmark in b

Page 52

UNIT48HJ_0044BHJ_OO54BHJ_OO54BHJ_O07STD. UNIT !CONOMI_ERI_ VERT. ECONIV (A) (SI (C) (D)WEIGHT WEIGHT W/P.E. WEIGHT CORNER WEIGHT CORNER WEIGHT CORNER

Page 53

k -41\INTAKE LOUVERS FLUE OPENINGFig. 8-- Flue Hood Detailsi= X9" MINIMUM CLEARANCE4 SUPPORT*FROM GAS METERLEGENDNFGC -- National Fuel Gas Code*F

Page 54 - TM controls 15-17

Table 1 -- Physical DataBASE UNIT 48 HJE/F/H/K]M/NO04 HJD/E/F/G/H/K]L/M/NO05 HJD/E/F/G/H/K]L/M/NO06 HJD/E/FO07NOMINAL CAPACITY 3 4 5 6OPERATING WEIGHT

Page 55 - III. START-UP

Table 1 -- Physical Data (cont)BASE UNIT 48 HJE/F/H/K]M/N004 HJD/E/FIGIHIK/L/M/NO05 HJD/EIF/GIH/K/LIM/NO06 HJD/E/F007FURNACE SECTIONRollout Switch Cut

Comments to this Manuals

No comments