Carrier 50HEQ003-006 Specifications Page 10

  • Download
  • Add to my manuals
  • Print
  • Page
    / 66
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 9
10
Table 3
Electric Heating Capacities
UNIT SIZE
VOLTAGE
(60 Hz)
ACCESSORY
(kW)
ACCESSORY HEATER
PART NUMBER
C R H E A T E R --- --- A 0 0
( o r --- --- B 0 0 w h e r e i n d i c a t e d )
SINGLE POINT BOX
PACKAGE NO.
C R S I N G L E --- --- A 0 0
003
(2 Tons)
208/230
(single phase)
3.3/4.4
4.9/6.5
6.5/8.7
7.9/10.5
001
002
003B00
004B00
--- ---
--- ---
004
004
004
(3 Tons)
208/230/240
(single phase)
3.3/ 4.0/ 4.4
4.9/ 5.8/ 6.5
6.5/ 8.0/ 8.7
7.9/ 9.6/10.5
9.8/11.6/13.0*
001
002
003B00
004B00
002 & 002
--- ---
--- ---
004
004
005
208/230/240
(3 phase)
3.3/ 4.0/ 4.4
4.9/ 5.8/ 6.5
6.5/ 8.0/ 8.7
7.9/ 9.6/10.5
12.0/14.7/16.0
001
002
003B00
004B00
005
--- ---
--- ---
--- ---
--- ---
002
460/480
(3 phase)
5.5/ 6.0
8.1/ 8.8
10.6/11.5
12.9/14.0
006
007
008
009
--- ---
--- ---
--- ---
--- ---
005
(4 Tons)
208/230/240
(single phase)
3.3/ 4.0/ 4.4
6.5/ 8.0/ 8.7
9.8/11.6/13.0*
13.1/16.0/17.4*
15.8/19.3/21.0*
001
003B00
002 & 002
003B00 & 003B00
004B00 & 004B00**
--- ---
004
005
005
005
208/230/240
(3 phase)
4.9/ 5.8/ 6.5
6.5/ 8.0/ 8.7
12.0/14.7/16.0
15.8/19.3/21.0*
002
003
005
004B00 & 004B00**
--- ---
--- ---
002
003
460/480
(3 phase)
5.5/ 6.0
10.6/11.5
12.9/14.0
21.1/23.0*
006
008
009
008 & 008
--- ---
--- ---
--- ---
--- ---
006
(5 Tons)
208/230/240
(single phase)
4.9/ 5.8/ 6.5
6.5/ 8.0/ 8.7
9.8/11.6/13.0*
13.1/16.0/17.4*
15.8/19.3/21.0*
002
003B00
002 & 002
003B00 & 003B00
004B00 & 004B00
004
004
005
005
005
208/230/240
(3 phase)
4.9/ 5.8/ 6.5
7.9/ 9.6/10.5
12.0/14.7/16.0
15.8/19.3/21.0*
19.9/24.3/26.5*
002
004B00
005
004B00 & 004B00
004 & 005
--- ---
002
002
003
002
460/480
(3 phase)
5.5/ 6.0
10.6/11.5
12.9/14.0
21.1/23.0*
23.4/25.5*
006
008
009
008 & 008
008 & 009
--- ---
--- ---
--- ---
--- ---
--- ---
007
(6 Tons)
208/230/240
(3 phase)
4.9/ 5.8/ 6.5
7.9/ 9.6/10.5
12.0/14.7/16.0
15.8/19.3/21.0*
19.9/24.3/26.5*
002
004B00
005
004B00 & 004B00
004B00 & 006
--- ---
002
002
003
003
460/480
(3 phase)
5.5/ 6.0
10.6/11.5
12.9/14.0
21.1/23.0*
23.4/25.5*
006
008
009
008 & 008
008 & 009
--- ---
--- ---
--- ---
--- ---
--- ---
*Two heater packages required to provide kW indicated.
** Minimum a irflow is 350 cfm/ton (1400 cfm) when two CRHEATER004B00 heaters are installed on a 4 ton, 230v heat pump.
NOTES:
1. The rated heater voltage i s 240 and 480 v. If power dis tribution voltage varies from rated heater voltage, heater kW will vary accordingly.
2. To determine heater kW at voltages other than those shown in table, use the following formula:
Heater kWnew = Heater kW rated x (unit power distribution voltage/rated heater voltage)
2
As an example:
For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v
kWnew = 16 kW ( 215/240)2
kWnew = 12.8 kW ( rating at 215 v)