Table 1 — Physical Data
UNIT 50ZH 030 036 042 048 060
OPERATING WEIGHT (lbs) 254 277 295 328 368
COMPRESSOR TYPE Scroll
REFRIGERANT Charge (lb)
R-22
5.8 5.9 6.6 9.1 9.7
REFRIGERANT METERING DEVICE Acutrol™ System
OUTDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
Copper Tubes, Aluminum Plate Fins
2...17
6.7
1...17
11.1
2...17
9.3
2...17
11.1
2...17
12.7
OUTDOOR-FAN MOTOR CFM
Nominal Rpm
Motor Hp
Diameter (in.)
Propeller
2000
1100
1/4
20
2600
1100
1/4
20
2600
1100
1/4
20
2600
1100
1/4
20
3200
1100
1/2
20
INDOOR COIL Copper Tubes, Aluminum Plate Fins
Rows...Fins/in.
Face Area (sq ft)
3...15
3.1
3...15
4.0
3...15
4.0
4...15
4.4
4...15
4.9
INDOOR FAN MOTOR
Blower Motor Size (in.)
Nominal Cfm
Rpm Range
Number of Speeds
Factory Speed Setting
Motor Hp
Direct Drive
10x8
1000
550-1000
3
Med
1/4
10x9
1200
800-1050
3
Low
1/2
10x9
1400
800-1050
3
Med
1/2
10x9
1600
1000-1100
2
Low
3/4
10x10
2000
950-1100
3
Low
1
CONNECTING DUCT SIZES
Supply Air (in.)
Return Air (in.)
Round
14
14
Square
13.9 x 13.9
13.9 x 27.8
FIELD-SUPPLIED RETURN-AIR FILTER†
Throwaway (in.)
24x24 24x24 24x24 24x30 24x30
* 460-v motors are 2-speed or 3-speed.
†Required filter sizes shown are based on the ARI (Air Conditioning and Refrigeration Institute) rated airflow at a velocity of 300 ft/min for throwaway type or 450 ft/min
for high capacity type. Recommended filters are 1-in. thick.