
37
The WSHP Open multi-protocol controller will control me-
chanical cooling, heating, hot gas reheat and waterside
economizer outputs based on its own space temperature
input and set points. An optional CO
2
IAQ (indoor air qual-
ity) sensor mounted in the space can maximize the occu-
pant comfort. The WSHP Open has its own hardware
clock that is automatically set when the heat pump soft-
ware is downloaded to the board. Occupancy types are de-
scribed in the scheduling section below. The following sec-
tions describe the functionality of the WSHP Open multi-
protocol controller. All point objects that are referred to in
this sequence of operation will be referenced to the objects
as viewed in the BACview
6
handheld user interface.
Scheduling
Scheduling is used to start/stop the unit based upon a time
period to control the space temperature to specified occu-
pied heating and cooing set points. The controller is de-
faulted to control by occupied set points all the time, until
either a Time Schedule is configured with the Equipment
Touch™ interface, i-Vu
®
Open, or a third party control sys-
tem Enables/Disables the BAS On/Off point. Your local
time and date must be set for these functions to operate
properly. The occupancy source can be changed to one of
the following:
Occupancy schedules — The controller will be occu-
pied 24/7 until a Time schedule is configured using either,
i-Vu Open, Equipment Touch or a third party Enables/Dis-
ables the BAS On/Off point. This can be disabled by going
to Config>Unit>Occupancy Schedules and changing the
point from Enable to Disable.
NOTE: This point must be Enabled in order for i-Vu Open
or Bacview
6
to assign a Time schedule to the controller.
Schedule_Schedule — The unit will operate according
to the schedule configured and stored in the unit. The
schedule is accessible via the Equipment Touch user inter-
face, i-Vu Open, or Field Assistant. The daily schedule con-
sists of a start/stop time (standard or 24 hour mode) and
seven days of the week, starting with Monday and ending
on Sunday.
Occupancy input contact (option) — If configured for
remote occupancy control (default), the WSHP Open con-
troller has the capability to use an external dry contact clo-
sure to determine the occupancy status of the unit. You will
need to disable the Occupancy Schedules in order to utilize
the Occupancy Contact Input. The control will cause the
unit to go into an occupied mode whenever the abnormal
input is sensed. After the input returns to its normal state,
the unit will stay in the occupied mode for the configured
Occupancy Override Delay period (15 minutes default).
NOTE: Scheduling can only be controlled from one
source.
BAS (building automation system) on/off — For use
with a Building Automation System that supports network
scheduling, you will need to disable the Occupancy Sched-
ules so the BAS system can control the unit through a net-
work communication and the BAS scheduling function.
NOTE: Scheduling can only be controlled from one
source.
Global occupancy scheduling — The WSHP Open
controller has the capability to read the occupancy status
from another unit so that a group of WSHPs can be con-
trolled from a single occupancy schedule. The local Occu-
pancy Schedules must be disabled in order to utilize the
global occupancy input.
NOTE: Scheduling can only be controlled from one
source.
BACnet network occupancy input — The WSHP Open
controller has the capability to accept an external BACnet
Binary Network Input for occupancy control. This function
is only compatible with units used in BACnet systems. You
will need to configure the “System Occupancy” BACnet
network input point to locate the device and point name
where the external occupancy point information resides.
Also Occupancy Schedules must be disabled in order to
utilize this input.
NOTE: Scheduling can only be controlled from one
source.
Fire/smoke detector (FSD) input (field optional)
The WSHP Open controller has the capability to read the
status of a normally closed FSD contact input to determine
if a fire or smoke detector alarm is present. If the controller
determines an alarm condition is present, all heating, cool-
ing and the fan are disabled. The normal state of the switch
is factory set to Normally Closed and cannot be changed.
Shutdown input
The WSHP Open controller has a shutdown input (soft-
ware) which when set to its Active mode will cause the
WSHP to safely shut down in a controlled fashion. Heating
and cooling will be disabled after any minimum runtime
conditions expire and the fan will be disabled after the fan
off timer expires. All alarms are reset but any active alarm
will remain active. After the shutdown input transitions
from Active mode to Inactive mode, the WSHP Open con-
troller will restart after the configured power fail restart de-
lay expires.
Indoor fan
The indoor fan will operate in any one of three modes de-
pending upon the user configuration selected. Fan mode
can be defined/selected as Auto, Continuous, or Always
On. In Auto mode the fan is in intermittent operation dur-
ing both occupied and unoccupied periods. Continuous fan
is intermittent during unoccupied periods and continuous
during occupied periods. Always On operates the fan con-
tinuously during both occupied and unoccupied periods. In
the default mode, Continuous, the fan will be turned on
whenever any one of the following is true:
• It is in occupied mode. Determined by its occupancy
status.
• Whenever there is a demand for cooling or heating in
the unoccupied mode.
• When there is a call for dehumidification (optional).
When power is reapplied after a power outage, there
will be a configured time delay of 5 to 600 seconds before
starting the fan. There are also configured fan delays for
Fan On and Fan Off. The fan on delay defines the delay
time (0 to 30 seconds; default 10) before the fan begins to
Controls — WSHP Open sequence of operation
Comments to this Manuals