50RHC,RVC018 — 600 CFM NOMINAL AIRFLOW
LEGEND
*ARI 320 points (bold printing) are shown for comparison purposes
only. These are not certified data points.
NOTES:
1. Interpolation is permissible, extrapolation is not.
2. All entering air conditions are 80 F db (dry bulb) and 67 F wb (wet
bulb) in cooling and 70 F db in heating.
3. All performance data is based upon the lower voltage of dual voltage
rated units.
4. See Performance Correction tables for operating conditions other
than those listed above.
5. Data table does not reflect ISO pump or fan corrections.
6. Performance capacities shown in thousands of Btuh.
EWT (F) GPM
PRESSURE DROP COOLING HEATING
PSI Ft Wg TC TSC kW THR TC kW THA
60
2.3 2.1 4.8 20.2 14.8 1.37 24.8 19.9 1.54 14.6
3.4 3.0 7.0 20.9 15.1 1.28 25.3 20.7 1.57 15.4
4.5 4.3 9.8 21.3 15.2 1.24 25.6 21.1 1.58 15.7
70*
2.3 2.0 4.6 19.3 14.4 1.48 24.4 21.6 1.60 16.1
3.4 2.9 6.7 20.0 14.7 1.39 24.7 22.4 1.63 16.8
4.5 4.1 9.5 20.3 14.9 1.36 24.9 22.7 1.64 17.1
80
2.3 1.9 4.5 18.3 13.8 1.58 23.7 23.1 1.65 17.4
3.4 2.8 6.5 19.1 14.3 1.50 24.2 23.8 1.68 18.1
4.5 4.0 9.2 19.4 14.4 1.47 24.4 24.1 1.69 18.3
85*
2.3 1.9 4.4 17.6 13.4 1.63 23.1 23.7 1.68 18.0
3.4 2.8 6.4 18.6 14.0 1.56 23.9 24.4 1.71 18.6
4.5 3.9 9.1 18.9 14.2 1.52 24.1 24.7 1.72 18.8
90
2.3 1.9 4.4 16.7 12.9 1.67 22.4 24.3 1.70 18.5
3.4 2.7 6.3 17.9 13.6 1.61 23.4 24.9 1.73 19.0
4.5 3.9 9.0 18.3 13.8 1.58 23.7 25.3 1.74 19.4
95
2.3 1.9 4.3 15.7 12.3 1.72 21.5
Operation Not Recommended3.4 2.7 6.3 17.1 13.1 1.65 22.7
4.5 3.8 8.9 17.6 13.4 1.63 23.2
EWT Entering Water Temperature (F)
GPM Gallons Per Minute
TC Total Capacity (MBtuh)
THA Total Heat of Absorption (MBtuh)
THR Total Heat of Rejection (MBtuh)
TSC Total Sensible Capacity (MBtuh)