iNjumber OneAirConditbningMakerDivision of Carrier CorporationHeat Pump — Outdoor SectionINDEXPageINSTALLATION...
connect high- and low-voltage power wiring; and replace louvered casing.13. Replace top cover by running 4 screws into orifice loosely (2 on each sid
PSIG(kPa)(427) (441) (455)(469) (483) (496)(5I0) (524)(538)(552) (565)(579) PRESSURE AT SUCTION SERVICE VALVEFig. 12 — 38QB030 with 28HQ,VQ036 or 40AQ
220(1517)PSIG(kPa)68 72 76 80 84(469) (496) (524) (552) (579)PRESSURE AT SUCTION SERVICE VALVEFig. 16 — 38QB042 with 40QB042 or 28HQ,VQ048Cool
With a low-side leak there is always some pressure in the liquid line. However, compressor motor temperature increases because of insufficient suct
Remove tubing section remaining in threaded portion of fitting. Discard locknut.Clean, flux, and insert new tube end into remaining portion of
nFig. 22 — Positioning Hose to Spray Coil15
TROUBLESHOOTING CHART — COOLING CYCLEOs
TROUBLESHOOTING CHART — HEATING CYCLE
For replacement items use Carrier Specified Parts.Manufacturer reserves the right to discontinue, or change at any time, specifications or designs wit
4'-0"(l220mm) OVERHEAD SPACE REQUIRED FOR SERVICE AND AIRFLOW^ (22 mm) DIAM HOLE FOR CONTROL WIRINGl|"(35mm) DIAM HOLE FOR POWER WI
Table 2 — Installation Data (Fig. 1)required replacement piston is factory supplied with specified 38QB outdoor unit. Replace piston as describe
Table 3 — AccessoriesPART NO.38CQ90008138CQ90011138QB9000210638HQ900001128VQ90001138RQ90008138RQ90000138HQ90000238CQ90017238RQ900091DESCRIPTIONLow-Vol
rREPLACE THE ACCURATER™ REFRIGERANT CONTROL PISTON IN THE INDOOR COIL AS REQUIRED before connecting refrigerant lines. See Table 1. Correct pi
THERMOSTAT SUBBASE HH93AZI73 OR HH93AZI7540AQ OR 40QB FAN COIL COOLING CONTROL KIT TERMINAL BOARD38QBTERMINALBOARDCOOLING AND ONE-STAGE HEATING (38QB/
INSTALL A BRANCH CIRCUIT DISCONNECT PER NEC of adequate size to handle unit starting current. Provide a separate disconnect for outdoor unit, indoor u
Table 6 — Service DataRefrigerant Charging — The 38QB units contain correct operating charge for complete system when connected to28HQ,VQ,40QB or 40
6. From intersect point, project vertically downward to chart suction pressure line. Compare chart suction pressure to unit suction pressu