Heat Pump — Outdoor Section
INDEX
Page
INSTALLATION................................................ 1-7
Step 1 — Check Equipment and Jobsite . 1
UNPACKAGE UNIT
INSPECT EQUIPMENT
COMPLETE OR CONSIDER SYSTEM
REQUIREMENTS
Step 2 — Mount Outdoor Heat Pump .. 3
ON THE GROUND: MOUNT UNIT
ON A SOLID, LEVEL CONCRETE
PAD
ON THE ROOF: MOUNT UNIT ON
A LEVEL PLATFORM OR FRAME
Step 3 — Make Piping Connections
_______
3-5
REPLACE THE ACCURATER™ RE
FRIGERANT CONTROL PISTON IN
THE INDOOR COIL AS REQUIRED
CONNECT REFRIGERANT LINES
Step 4 Make Electrical Connections .. 5-7
INSTALL A BRANCH CIRCUIT
DISCONNECT PER NEC
ROUTE LINE POWER LEADS
INTO UNIT
CONNECT GROUND LEAD AND
POWER WIRING
SEE INDOOR UNIT AND ELECTRIC
HEATER INSTALLATION, START-UP
AND SERVICE INSTRUCTIONS
CONNECT CONTROL POWER
WIRING (24 v)
START-UP............................................................ 7
SERVICE............................................................ 7-14
MAINTENANCE................................................ 14-17
SAFETY CONSIDERATIONS
Installation and servicing of air conditioning
equipment can be hazardous due to system pres
sure and electrical components. Only trained and
qualified service personnel should install, repair or
service air conditioning equipment.
Untrained personnel can perform basic main
tenance functions of cleaning coils and cleaning
and replacing filters. All other operations should be
performed by trained service personnel. When
working on air conditioning equipment, observe
precautions in the literature, tags and labels attached
to the unit and other safety precautions that may
apply.
Follow all safety codes. Wear safety glasses and
work gloves. Use quenching cloth for brazing oper
ations. Have fire extinguisher available for all
brazing operations.
WARNING: Before performing sersice or
maintenance operations on system, turn off
mam power switches to indoor unit and out
door unit. Turn off accessory heater power
switch if applicable. Electrical shock could cause
personal injury'.
INSTALLATION
Step 1 — Check Equipment and Jobsite
UNPACKAGE UNIT — Move to final location.
Lift carton off, taking special care not to damage
service valves or grilles.
INSPECT EQUIPMENT — File claim with ship
ping company if shipment is damaged or incomplete.
COMPLETE OR CONSIDER SYSTEM RE
QUIREMENTS before installing the 38QB:
Consult local building codes and National
Electrical Code (NEC) for special installation
requirements.
When installing, allow sufficient space for
airflow clearance, wiring, refrigerant piping and
servicing. Position so water or ice from roof cannot
drop directly on top of unit.
Make provisions for condensate drainage and
defrost water disposal whether unit is installed on
ground or roof. (Ensure unit basepan drainage
holes are not blocked.) See Step 2 for details. Roof
installation method for 38QB depends on building
construction and special requirements of local
codes. Be sure that roof can support unit weight.
It is recommended that 38 QB units be used with
Carrier approved indoor sections; see Table 1.
System Refrigerant Control on 38QB units and
matching Carrier indoor units is a factory-installed
AccuRater™ device (bypass type). Bypass-type
AccuRater components are discussed in the service
section of this booklet. The AccuRater piston has a
refrigerant metering hole thru it and is field replace
able. Table 2 indicates indoor units for which the
Carrier Corporation 1982
Form 38QB-1SIM
Page view 0
1 2 ... 18

Summary of Contents

Page 1 - Heat Pump — Outdoor Section

iNjumber OneAirConditbningMakerDivision of Carrier CorporationHeat Pump — Outdoor SectionINDEXPageINSTALLATION...

Page 2

connect high- and low-voltage power wiring; and replace louvered casing.13. Replace top cover by running 4 screws into orifice loosely (2 on each sid

Page 3

PSIG(kPa)(427) (441) (455)(469) (483) (496)(5I0) (524)(538)(552) (565)(579) PRESSURE AT SUCTION SERVICE VALVEFig. 12 — 38QB030 with 28HQ,VQ036 or 40AQ

Page 4 - Table 3 — Accessories

220(1517)PSIG(kPa)68 72 76 80 84(469) (496) (524) (552) (579)PRESSURE AT SUCTION SERVICE VALVEFig. 16 — 38QB042 with 40QB042 or 28HQ,VQ048Cool

Page 5

With a low-side leak there is always some pressure in the liquid line. However, compressor motor temperature increases because of insufficient suct

Page 6

Remove tubing section remaining in threaded portion of fitting. Discard locknut.Clean, flux, and insert new tube end into remaining portion of

Page 7

nFig. 22 — Positioning Hose to Spray Coil15

Page 8 - Table 6 — Service Data

TROUBLESHOOTING CHART — COOLING CYCLEOs

Page 9 - CAliXiOK: Excmive cmpp&t

TROUBLESHOOTING CHART — HEATING CYCLE

Page 10

For replacement items use Carrier Specified Parts.Manufacturer reserves the right to discontinue, or change at any time, specifications or designs wit

Page 11

4'-0"(l220mm) OVERHEAD SPACE REQUIRED FOR SERVICE AND AIRFLOW^ (22 mm) DIAM HOLE FOR CONTROL WIRINGl|"(35mm) DIAM HOLE FOR POWER WI

Page 12

Table 2 — Installation Data (Fig. 1)required replacement piston is factory supplied with specified 38QB outdoor unit. Replace piston as describe

Page 13 - Compatible Fitting Repair

Table 3 — AccessoriesPART NO.38CQ90008138CQ90011138QB9000210638HQ900001128VQ90001138RQ90008138RQ90000138HQ90000238CQ90017238RQ900091DESCRIPTIONLow-Vol

Page 14

rREPLACE THE ACCURATER™ REFRIGERANT CONTROL PISTON IN THE INDOOR COIL AS REQUIRED before connecting refrigerant lines. See Table 1. Correct pi

Page 15

THERMOSTAT SUBBASE HH93AZI73 OR HH93AZI7540AQ OR 40QB FAN COIL COOLING CONTROL KIT TERMINAL BOARD38QBTERMINALBOARDCOOLING AND ONE-STAGE HEATING (38QB/

Page 16

INSTALL A BRANCH CIRCUIT DISCONNECT PER NEC of adequate size to handle unit starting current. Provide a separate disconnect for outdoor unit, indoor u

Page 17

Table 6 — Service DataRefrigerant Charging — The 38QB units contain correct operating charge for complete system when connected to28HQ,VQ,40QB or 40

Page 18 - Catalog No 563-807

6. From intersect point, project vertically downward to chart suction pressure line. Compare chart suction pressure to unit suction pressu