installation, operation, and maintenance instructionsPACKAGED HEAT PUMPS542ESizes 024 thru 060& 542D060NOTE TO INSTALLER: Leave these instruc
NOTE: Adjustment of the refrigerant charge is not required unless the unit is suspected of not having the proper charge.An operating pressure/temper
TABLE VI-AIR DELIVERY (FtVMin) AT INDICATED EXTERNAL STATIC PRESSURE & VOLTAGE*ModelBlowerMotorSpeedOperatingVoltageApplica-tiontExternal Static
TABLE VII-MODEL 542D060 & 542E060- 3-PHASE UNITS-MOTOR PULLEY SETTINGS FOR AIR DELIVERY AT INDICATED EXTERNAL SP & VOLTAGE WITH WET COILNOTES:
B. Cooling OperationWith the room thermostat SYSTEM switch in the COOL position and the FAN switch in the AUTO position, the cooling sequenc
deenergize indoor blower relay coil 2A and compressor contactor coil 2D. All closed contacts return to their normally open position and all
LEGENDI B-Transformer2A-lndoor Blower Relay SPST (N.O.) 2C-Outdoor Fan Relay SPOT 2D-Compressor Contactor DPST (N.O.) 2P-Defrost Relay TPDT 3D1-Outdoo
Clean and lubricate the direct-drive blower motor and wheel as follows;1. Remove and disassemble blower assembly as follows;a. Remove blower and con
TABLE Vlll-TROUBLESHOOTING CHART-HEATING CYCLEon the insulation, motor, wiring, or air filter(s). If the drain tube is restricted, clear it with a “pl
TABLE IX-TROUBLESHOOTING CHART-COOLING CYCLEally. Be sure to disconnect the electrical power to the unit. Remove the control, blower, an
542E REQUIRED CLEARANCE (Inches)Top of unit...48 Blower access door end______30Duct side of unit...
Figure 4—542D060 Dimensional DrawingTABLE ll-ELECTRICAL DATA-MODEL 542E-SIZES 024 THRU 042MODEL542ESIZEJ024 J030 J036 1 P036B042 1 P042SERIESAAAAUnit
USE SPREADER BARS TO PROTECT UNITUSE SPREADER BARS TO PROTECT UNITA79148Figure 5—542E Suggested RiggingI. MOVING AND SETTING UNIT IN PLACE CAUTION:
REVERSING VALVE ASSEMBLYHIGH-PRESSURE SERVICE FITTINGCAPACITOR(S) (COMPRESSOR a FAN MOTOR)BLOWER MOTOR RELAYLOW-PRESSURE SERVICE FITTINGACCUMULATORACC
HIGH-VOLTAGE PIGTAIL LEADS-FIELD SPLICEBLKBLK ^ RED1/r/ r-Tok F1ELD-SUPPL1E(POWERSUPPLY3-PHASE UNITS ONLYSWITCHA79244Figure 9—Field High-Voltage Conn
A79245Figure 10—Field Low-Voltage Connections Using Room Thermostat P/N 34427DP115 or P/N 34427DP118HEAT PUMP LOW-VOLTAGE TERMINAL BOARDАГ9246Figure 1
A80089Figure 12—Removing Belt-Drive Blower Shipping Bracket3. Read the following instructions on all WARNING,CAUTION, and INFORMATION labels attached
TABLE IV-HEATING PERFORMANCE PRESSURESAir Temp at Indoor Coil Inlet |°F DB)PressureDesignation(Psig)54ZED24 542E030542E036Air Temperature at Outdoo