48
4 to 20 mA signal. It can be connected to terminals 8
and 9 on TB202.
• Remote Static Pressure Reset Set Point — A remote
supply air temperature set point reset can be supported
when the controls expansion module is used. This input
requires a 4 to 20 mA signal. It can be connected to ter-
minals 6 and 7 on TB202. This input is shared with the
Outdoor Air IAQ signal.
• Outdoor Air IAQ Signal — If an external outdoor air
signal is being used then it can be connected to termi-
nals 6 and 7 on TB202. This input requires a 4 to 20
mA signal. This input is shared with the Remote Static
Pressure Reset signal.
• IAQ Switch Input — If an external control will be con-
trolling IAQ then it can be connected as a contact clo-
sure through terminals 12 and 13 on TB202.
• Space Humidity — A space humidity sensor can be
used to enable the dehumidification and humidifier con-
trol logic. It can be connected to terminals 3 and 4 on
TB202. This input requires a 4 to 20 mA signal.
• Humidifier Control Output — A contact closure out can
be provided to enable the operation of a field-provided
humidifier. Carrier can also support electronic interface
to other systems using the following:
— MODBUS Carrier translator (read/write, provides
CCN to MODBUS remote terminal unit [RTU] protocol
conversion)
— LonWorks Carrier translator (read/write, provides
CCN to LON FT-10A ANSI/EIA-709.1 protocol con-
version)
Constant volume and staged air volume appli-
cations
The 48/50N Series units are designed to operate in CV
and SAV™ applications. The units are shipped as operable,
stand-alone units using either a standard (mechanical or
electronic) 2-stage heat, 2-stage cool thermostat, or with
an electronic room temperature sensor. With a standard
thermostat (programmable is optional), heating and cool-
ing operation is set by space temperature. With a space
sensor, the machine will operate at default values unless
they are changed using appropriate input devices. The
space sensor monitors space temperature and may be
equipped with a timed override feature, which allows unit
operation during unoccupied periods. The space sensors
may be used in multiples of 4 or 9 to achieve space tem-
perature averaging. The use of a space sensor also allows
the unit to be turned on and off from a remote signal or it
can be programmed to use the time of day scheduling that
is built into the control.
Features with thermostat control of unit
• Two-stage heating (if installed)
• SCR electric heating if equipped with the SCR electric
heat option
• Modulating gas heating if unit is equipped with the mod-
ulating gas heat option
• Two-stage demand with fully proportional economizers
and integrated compressor capacity
• Adaptive multiple stage cooling which can provide up to
8 stages of capacity
• Control of unit using Y1, Y2, W1, W2, and G thermo-
stat or T55, T56, or T58 space sensors
• Control of the indoor fan
• Outdoor-air temperature/supply-air temperature moni-
toring with logic to lock the compressors out at low
ambient temperatures down to 32 F (-20 F with Motor-
master
®
control)
• Control of a condenser fan based on outdoor-air and
condensing pressures
• Control of modulating economizer to provide free cool-
ing when outdoor conditions are suitable
• Control allows for use of the economizer and the com-
pressors to maximize the use of outside air cooling to
reduce part load operating costs
• Control of the power exhaust fan VFD based on config-
urable the building pressure sensor
• Compressor time guard override (power up and mini-
mum on and off timers) to assure air return in low load
conditions
• Support of IAQ sensor
Features with sensor control of unit
There are 3 sensor options available:
• T55 sensor will monitor room temperature and provide
unoccupied override capability (1 to 4 hours).
• T56 sensor will monitor room temperature, provide
unoccupied override capability (1 to 4 hours), and pro-
vide a temperature offset of 5° F maximum.
• T58 is a CCN communicating sensor that will provide
the set point and space temperature values.
Standard features are:
• Support of remote occupied/unoccupied input to start
and stop the unit
• Two-stage economizer demand with fully proportional
economizers and integrated compressor capacity
• Adaptive cooling capacity control with up to 8 stages of
mechanical refrigeration capacity
• Variable capacity control with digital scroll compressor
option
• Occupied or unoccupied set point
• Enable heating (if installed) or cooling during unoccu-
pied periods as required to maintain space temperature
within the unoccupied set points
• Adjustment of space temperature set points of ± 5° F
when using a T56 sensor
• Support of IAQ sensor
• 365-day timeclock with backup (supports minute, hour,
and day of week, date, month, and year access). The
timeclock includes the following features:
— Daylight savings time function
— Occupancy control with 8 periods for unit operation
— Holiday table containing up to 18 holiday schedules
— Ability to initiate timed override from T55 or T56
sensors (for a timed period of 1 to 4 hours)
— Temperature compensated start to calculate early
start times before occupancy
— For units connected into a CCN network the time
clock can be integrated into the overall building ener-
gy management system and be updated remotely