Chassis arrangements (48 Series units)
Standard chassis — The standard chassis may be pro-
vided with a bottom or side return air opening. The return
air follows a straight-through path to the supply fan, then
into the heating section and exits through a bottom or left
side supply air outlet. The supply/return configuration may
be mixed, e.g., bottom return with side supply. If the appli-
cation utilizes an accessory roof curb, vertical ductwork is
connected to the curb. When side connections are utilized,
the ductwork is connected to flanges on the unit. These
units are available with optional modulating power exhaust
or return fan in conjunction with an optional economizer.
Standard chassis with optional blank section or
final filters
This arrangement adds a factory-installed blank section or
final filter. Return air enters through a bottom or side
opening and follows a straight-through path to the supply
fan, through the heating section and blank section or final
filters, then exits through the bottom or left side supply air
outlet. The supply/return configuration may be mixed,
e.g., bottom return with side supply. If the application uti-
lizes an accessory roof curb, vertical ductwork is connected
to the curb. When side connections are utilized, the duct-
work is connected to flanges on the unit.
Extended length chassis — The extended length chas-
sis arrangement provides an additional 25-in. of unit length
located between the evaporator coil section and the supply
fan sled. This compartment is used for the Humidi-MiZer
®
coil or may also be used for field-installation of an auxiliary
coil, e.g., a refrigeration heat reclaim coil.
Chassis arrangements - (50 Series units)
Standard chassis with discharge plenum — This con-
figuration may be provided with a bottom or side return air
opening. The return air follows a straight-through path to
the supply fan. The supply fan is arranged for horizontal
outlet into the discharge plenum area. Supply air exits
from the discharge plenum area downward through the
bottom of the unit or horizontally through the left side out-
let. The supply/return configuration may be mixed, e.g.,
bottom return with side supply. If the application utilizes an
accessory roof curb, vertical ductwork is connected to the
curb. When side connections are utilized, the ductwork is
connected to flanges on the unit. These units are available
STANDARD CHASSIS
VERTICAL SUPPLY/VERTICAL RETURN
a48-8676
STANDARD CHASSIS
VERTICAL SUPPLY/HORIZONTAL RETURN
a48-8677
SIDE SUPPLY OPENING
OPPOSITE SIDE
STANDARD CHASSIS
HORIZONTAL SUPPLY/HORIZONTAL RETURN
A48-8678
SIDE SUPPLY OPENING
OPPOSITE SIDE
STANDARD CHASSIS
HORIZONTAL SUPPLY/VERTICAL RETURN
A48-8679
SIDE SUPPLY OPENING
OPPOSITE SIDE
BLANK SECTION
STANDARD CHASSIS WITH BLANK SECTION OR
FINAL FILTERS
VERTICAL SUPPLY/VERTICAL RETURN
a48-8680
NOTE: Standard Chassis with Blank Section or Final Filters also available in
Vertical Supply/Horizontal Return, Horizontal Supply/Horizontal Return, or
Horizontal Supply/Vertical Return configurations.
SIDE SUPPLY OPENING
OPPOSITE SIDE
COIL
COMPARTMENT
EXTENDED LENGTH CHASSIS
VERTICAL SUPPLY/VERTICAL RETURN
a48-8681
NOTE: Extended Length Chassis also available in Vertical Supply/Horizontal
Return, Horizontal Supply/Horizontal Return, or Horizontal Supply/Vertical
Return configurations.