Electric heat units (50N units)
The 50N units may be equipped with
factory-installed electric heat, with 3
heat sizes available for every unit. The
heaters are resistance type, open wire
nichrome elements, insulated with ce-
ramic bushings, and include operating
and safety controls. The standard
heater control is a 2-stage type. An
optional SCR control is available for
applications requiring precise leaving
air temperature control.
Optional SCR controlled electric
heat — The SCR electric heat option
monitors unit supply-air temperature
and controls the electric heaters to pro-
vide first-stage demand heating con-
trol, with modulation to maintain user-
configured heating supply air tempera-
ture set point. The option also pro-
vides full output demand heating on
heating control command and temper-
ing heat control, based on user-config-
ured ventilation supply air tempera-
ture set point, to eliminate cold draft
conditions with low mixed-air tempera-
tures. The SCR control option consists
of an SCR controller capable of vary-
ing the heater output, supply air tem-
perature thermistors with duct-mount-
ing base, and required limit switch con-
figurations.
Power Exhaust or Return Fan
• Building pressure control
• VFD controlled
• High-static fan option
Airflow measurement options
Cabinet Features
• Double wall foam panel design
• Pre-painted panels
• High strength steel roll formed base rails
• Hinged access panels, both sides
• Optional 4' and 8' blank sections
• Agion
®
anti-microbial interior option
Mixed Air and Final Filter Options
• Bag, cartridge, or pleated styles
• MERV 8 to 17
High-Efficiency Airfoil Supply Fan
• Premium-efficiency ODP or TEFC motor
• VFD control with soft start
• High-static fan option
Ultra low leak economizer
• Blade and edge seals
ComfortLink DDC controller
• CV, SAV™ or VAV systems
• Multi-protocol communication
• Navigator™ user interface
• Prognostics and diagnostics
Evaporator section
• High-capacity evaporator option
• Electronic expansion valves
• Stainless steel double-sloped condensate pan
• Humidi-MiZer
®
dehumidification option