37A SeriesModulineAir DiffusersSelection and Installation manual
101.10 - Upstream air qualityAir filtersThe standard 50 mm air filters built into central station airhandlers may be of either the throwaway type or t
112 - AIR THROWThe air stream moves horizontally beneath the false ceilinginducing more air from the room as it does so. This creates aslowly moving u
124 - SELECTION GUIDE4.1 - INTRODUCTIONEssential data :- Room dimensions- Specified or required noise level- Room design temperature- Heat gains and l
13Room B 109/57 = 1.91 hence use 2 37AG units.4. Calculate the air flow for each unitFor rooms A and C : 44/1 = 44 l/sFor room B : 109/2 = 55 l/s5. Ve
145 - PHYSICAL AND PERFORMANCE DATA5.1 - 37AG Moduline with 900 mm active length5.1.1 - General data- Nominal air flow 200 m3/h - 56 l/s- Maximum unit
155.1.4 - Sound power level 37AG with 900 mm active length5.1.3 - 37AG air throw - 900 mm active lengthLegend :1) Based upon tests according to ASHRAE
165.2 - 37AG Moduline with 1200 mm active length5.2.1 - General data- Nominal air flow 266 m3/h - 76 l/s- Maximum units per controller : 8- Air flow a
175.2.4 - Sound power level 37AG with 1200 mm active length5.2.3 - 37AG air throw - 1200 mm active lengthLegend :(1) Based upon tests according to ASH
185.3 - 37AS Moduline5.3.1 - General data- Nominal air flow 200 m3/h - 56 l/s- Not connectible in series- Air flow at shutoff: 41 m3/h - 11 l/s ± 3 l/
195.3.4 - Sound power level 37AG with 1200 mm active length5.3.3 - 37AS air throwLegend :(1) Based upon tests according to ASHRAE 36B-63 with standard
The photo shown on the front cover is solely for informa-tion, and not contractually binding. The manufacturerreserves the right to make changes witho
205.4 - 37AH Moduline5.4.1 - General data- Nominal air flow 350 m3/h - 97 l/s- Max number of units per controller: 4- Air flow at shutoff: 68 m3/h - 1
215.4.4 - 37AH Sound power level 5.4.3 - 37AH air throwLegend :(1) Based upon tests according to ASHRAE 36B-63 with standard air and an ASHRAE sound r
225.5.2 - Physical data and dimensions5.5 - 37AHS Moduline5.5.1 - General data- Nominal air flow 325 m3/h - 90 l/s- Max number of units per controller
23Note :Value determined by this curve is for one side of the diffuser only.5.5.4 - 37AHS sound power level 5.5.3 - 37AHS air throwLegend :(1) Based u
246 - CONTROLSModuline systems are essentially self regulating.The air pressure which is the controlling force is itself derivedfrom the primary air s
256.1.1 - Control accessories6.1.1.1 - Constant volume control kitThe control assembly comprises:- filter- constant volume controller- connection tube
266.1.1.2 - Variable air volume controller with Moduline ther-mostatThe variable air volume controller assembly comprises :- filter- flow controller-
27AccessoriesPart N°37AE 900 592 C37AH 900 062 CDescriptionControl connectiontube 30,5 ml rollsTube bifurcator (Y)kit of 25 unitsApplicationUsed for c
286.1.3 - Variable air volume control with a room thermostatFor greater accessibility, Carrier offers a high precision wallmounted thermostat with the
296.2 - Electronic controlElectronic control is recommended when a Moduline system isto operate either in conjunction with an on/off heating systemor
1 - INTRODUCTION ...
30NOTE GÉNÉRALE:- With Moduline, the plug in controls are easily relocated or reconfigured. Partitions can be repositioned and spaces reallocat-ed to
317 - ACCESSORIES
32EView on EFView on FInstalling alignment piecesNOTE:Refer to the return air diffuser dimensional drawings.
337.1 - Suspension accessories7.2 - Plenum accessories
347.2.1 - Control interconnections and combinations37AG master with 37AG slaves37AH master with 37AH slaveslegende :C Controller or controller with th
35NOTES:1. Diffuser length is given by module dimension (1200 mm) and diffuser type (discontinuous = module dimension - 25 mm) Inthis example the diff
368.2 - 37AH ModulineNOTES:1. Diffuser length is given by module dimension (1200 mm) and diffuser type (discontinuous = module dimension - 25 mm) Inth
378.3 - 37AHS ModulineNOTES:The diameters of the connection spigots depend upon the size of the plenum as shown by character positions 9 and 10.
388.4 - 37AS ModulineNOTES:1. Diffuser length is given by module dimension (1200 mm) and diffuser type (discontinuous = module dimension - 25 mm) Inth
399 - INSTALLATION INSTRUCTIONS9.1 - 37AG, AH, AS constant volume and variable volumeunits9.1.1 - IntroductionControllers can be installed in the unit
41 - INTRODUCTION1.1 - Main featuresCarrier Moduline air conditioning terminals integrate air distri-bution and air volume flow control, constant volu
408 - Refer to Fig 3 or Fig 6 as appropriate. Remove the plugfrom the bellows connection, or from the Y bifurcator, accord-ing to type, and connect it
419.2 - 37AHS Constant volume and variable volume units9.2.1 - IntroductionControls can be installed in the units either before (to be pre-ferred) or
439.3 - Wall thermostats with 37AG, AH, AHS and ASunits9.3.1 - DescriptionThe thermostat is a proportional device which enables theleakage rate at shu
449.4.5 - ApplicationNOTE :Controller/amplifier to be ordered separatelyback view (wall side) front viewThermostat labelFixing slot 4.5 x 9.5 mmCover
459.4 - Installing controller/amplifiers9.4.1 - IntroductionController/amplifier assemblies may be installed before (to bepreferred) or after installa
46Controller/amplifierController/amplifiermountingScrew GasketPlugFilterTubesPlugWall thermostatTo filterTo bellowsSWarm-up switchor min air flowcontr
479.5 - Installing the minimum air flow controller9.5.1 - IntroductionThe minimum air flow controller and, more often, a controlleron 37A units may be
489.6 - Installing the warm-up switch on 37AG, AH,AHS, AS units1. Remove the rubber plug from the plastic base of the thermo-stat to enable the 3/16 i
492 - Remove the brass cap from the controller bleed orifice.3 - Set the electronic interface on the central diffuser andconnect the 4 mm internal dia
5Nominal air flow: 267 m3/h - 74 l/sAir flow range: 90-627 m3/h - 25-173 l/sThe 37AG is suitable for all types of offices, commercialpremises, hospita
5010 - SITE WORKS : SUPPLY AIR FLOW MEASUREMENT10.1 - Velocity sensor locationHot wire anemometer (0-10 m/s)NOTE:Be careful, don’t take velocity readi
51Diffuser active lengthA 1 200 mmB 900 mmC 600 mm10.2 - Average air velocity per slot as a function of total air flow - 37AGDiffuser active lengthA 1
5210.3 - Average air velocity per slot as a function of total air flow - 37AHDiffuser active lengthA 1 200 mmB 900 mmC 600 mmDiffuser active lengthA 1
5311 - SPECIAL ORDER UNITS11.1 - Diffuser lengthDiffusers may be from 449.5 to 2000 mm long.11.2 - Surface finishDiffusers may be unpainted, anodised
5412 - SPECIFICATION GUIDESupply and install Moduline air terminal units with the con-trols and accessories required for the units to function as stan
No 13716-20, October 2000 - Supersedes No: 13716-20, April 1999Manufacturer reserves the right to change any product specification without notice.Manu
61.5 - Moduline in false ceilingsa. All 37 Series Moduline terminals can be integrated intofalse ceilings with removable tiles.b. Moduline terminals,
7Fig. 4 - Moduline units installed parallel to T-bars in a single storey buildingLocation Model Discharge Plenum Adapters Diffuserlength, mmG-1 37AG 1
81.6 - Special false ceilings and ModulineConsult Carrier SA, La Boisse before planning the use of Moduline with any special false ceiling.1.7 - Insta
91.8 - Connecting Modulines in series. Sizing supplyair ductsWith the exception of the 37AS model, Moduline air terminalshave connection spigots at ea