30GT Units
— All control box internal wiring is supplied
from the factory in a harness assembly. Connect the coil of
HGBPR-A in series between TB5-3 and TB5-7. (Connect
the wires marked HGBPR-A-C1, HGBPR-A-C2 to the appro-
priate terminals.) See Fig. 7 (top section). Wire the coil of
HGBPR-B in series between TB5-4 and HGBPR-A-C2. (Con-
nect the wires marked HGBPR-B-C1 and HGBPR-B-C2 to the
appropriate terminals.) See Fig. 7 (top section).
For hot gas bypass on circuit A, locate a black wire in the
control harness with the label HGBPR-A-1, which originates at
TRAN 1. Connect the wires to the HGBPR-A-B, HGBPR-B-1,
HGBPR-B-2, TDR-HGA-1, TDR-HGA-4, and TB5-5 to the
correct terminals. See Fig. 7 (bottom section). For hot gas
bypass on circuit B, connect the wires labeled HGBPR-A-1,
HGBPR-A-4, HGBPR-A-5, HGBPR-B-4, HGBPR-B-6,
TDR-HGB-1, TDR-HGB-4, and TB5-6 to their correct termi-
nals. See Fig. 7 (bottom section). Connect the 620,000-ohm,
1
/
2
-w, field-supplied resistor across terminals 2 and 3 of the
time-delay relay. Repeat this procedure for the other time-delay
relay.
Wire in the solenoid valves. Terminal blocks are provided
for easy field wiring. Wiring external to the control box must
be run in field-supplied conduit. Use one of the
7
/
8
-in. (22-mm)
holes in the control box with a strain relief to run the wires to
the solenoid A (HGBPS-A) between TB5-5 and TB5-8. Con-
nect hot gas bypass solenoid B between TB5-6 and TB5-8. See
Fig. 7. Check all electrical connections for proper location and
tightness. Close and secure control box door.
LEGEND
HGA
Hot Gas Circuit A
HGB
Hot Gas Circuit B
HGBPR
Hot Gas Bypass Relay
HGBPS
Hot Gas Bypass Solenoid
LLSV
Liquid Line Solenoid Valve
TB
Terminal Block
TDR
Time-Delay Relay (Field Supplied)
TRAN
Transformer
TXV
Thermostatic Expansion Valve
Fig. 7 30GT040-420 HGBP (Hot Gas Bypass) Wiring