2.4.2 Control
NOTE
1 This procedure should be performed by an
HVAC technician who has been trained on
Carrier Model GR system design. Control
configuration is preset by the manufacturer
and resetting of the parameters should not
berequired.ItisrecommendedthatCarrier
Service or Engineering is contacted before
any control configuration is changed.
Carriercannotberesponsibleforfailuresor
damage resulting from unauthorized
changes.
2 If a replacement L ogic Module is installed,
it is necessary to match the configuration
jumpers (see Figure 1-10) to the original
board. Refer to paragraph 4.24.
a. Turn the A/C main power switch (located in the driv-
ers area) to OFF.
b. Connect the Micromate to the service port located in
the return air section.
c. Unplug the logic board connector J3.
d. Turnthe A/Cmain power switchbackto the ONposi-
tion.
e. Activate the system by pressing the 1/0 key on the
Micromate panel.
NOTE
Be sure to reconnect J3 when testing is com-
pleted or the system will fail to operate when
the Micromate is disconnected.
NOTE
When modifying the setpoint temperature for
diagnostic purposes, be sure to reset the set-
point when testing i s complete.
2.4.3 Diagnostic Mode
Diagnostic mode can be entered by pressing the up and
down arrow keys simultaneously for 5 seconds.
Diagnostic mode allows alarms and system parameters
to be viewed. If there are any alarms stored, the most
recent alarm will be shown. To view additional alarm
information, refer to section 3. Press the up and down
arrow keys to view parameters.
2.4.4 System Parameters
Pressing the up/down arrow keys will allow the user to
scroll up or down through the parameters. If no key is
pressed for 30 seconds this mode is exited and the
display will revert back to the default display. Pressing
the on/off key any time will exit this mode and the
display will again indicate the default. The parameters
are shown in Table 2-3. When scrolling through the
parameters, the current parameter will be displayed for
two seconds. After two seconds, the display will show
the data for the current parameter. When the l ast
parameter is reached, the list will wrap back to P1.
2.4.5 Test Mode
With the system in normal operation,the controllermay
be placed in the test mode, by doing the following:
a. Enter the diagnostic mode by pressing the up and
downarrow keyssimultaneously for5 seconds. Enter
the test mode by pressing the COOL key five times.
b. In the test mode, the display will read “T##” where
“##” indicated the test number that is currently run-
ning.
c. The initial indication will be “T00”. This indicates
the controller is in the test mode and all relays arede--
energized. Press the arrow keys to scroll through and
perform each test When the highest test number is
reached, the display will increment back to the lowest
test number. A listing of tests is provided in
Table 2-2.
d. To terminate testing, press the I/0 key.
Table 2 -2. Controller Test List
TEST
OUTPUT STATE
T00 All Relays Of f
T01 Evaporator High On
T02 Evaporator Low On
T03 Condenser High On
T04 Condenser Low On
T05 Compressor On
T06 Unloader Valve 1 On
T07 Unloader Valve 2 On
T08 Fresh Air Damper On
T09 Heat On
T10 Fault On
T11 Boost On
T12 Spare/Motor Input On