Carrier 60 Service Manual Page 36

  • Download
  • Add to my manuals
  • Print
  • Page
    / 56
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 35
T -295
4-3
DS
1
6
10
2
3
4
5
7
8
9
1. Filter-Drier I nlet
Service Valve
2. Thermostatic
Expansion Valve
3. Manifold Gauge
Set
4. Thermistor Vacuum
Gauge
5. Vacuum Pump
6. Refrigerant Cylinder
7. Reclaimer
8. Filter-Drier
9. Liquid Solenoid
Valve
10. Filter-Drier Outlet
Service Valve
Figure 4-4. Low Side Pump Down Connections
i. Re--connect suction pressure transducer and remove
low pressure switch jumper. If required, clear any
alarms that have been generated during this proce-
dure.
j. Open service valves and check refrigerant level. Re-
fer to paragraph 4.8.1.
4.5.2 Refrigerant Removal From An Inoperative
Compressor .
To remove the refrigerant from a compressor that is not
operational, do the following:
a. Attach a manifold gauge set as shown in Figure 4-5
andisolatethecompressorbyfrontseating thesuction
and discharge valves.
b. Recoverrefrigerantwith a refrigerantreclaimer. Ifthe
discharge service valve port is not accessible, it will
be necessary to recover refrigerant through the suc-
tion service valve port only.
c. Service or replace components as required and leak
check the compressor.
d. Using refrigerant hoses designed for vacuum service,
connect a vacuum pump to center connection of man-
ifold gauge set. Evacuate system to 500 microns.
Close offpump valve, isolatevacuum gauge andstop
pump. Wait 5 minutes to verify that vacuum holds.
e. Once vacuum is maintained, recharge low side to 20
to 30 psig (1.36 to 2.04 bar) by admitting vapor from
the refrigerant cylinder. Disconnect manifold gauge
set and backseat compressor service valves.
f. Check refrigerant level. Refer to paragraph 4.8.1. It
may be necessary to clear any alarms that have been
generated.
DS
7
1
2
3
4
5
6
1. Discharge Service
Valve and Port
2. Suction Service
Valve and Port
3. Manifold Gauge
Set
4. Vacuum Pump
5. Reclaimer
6. Refrigerant Cylinder
7. Thermistor Vacuum
Gauge
Figure 4-5. Compressor Service Connections
4.5.3 Pump Down An Operable Compressor For
Repair
To servicean operablecompressor, pump therefrigerant
into the condenser coil and receiver as follows:
a. Install manifold gauge set. Refer to Figure 4-5.
b. Frontseat the compressor suction service valve by
turning clockwise.
c. Place a jumper on the low pressure switch. Start the
unit and run in cooling until 10 ”/hg (25.4 cm/hg) of
vacuum is reached. Shut the system down.
d. Frontseat the compressor discharge service valve and
wait 5 minutes to verify vacuum is maintained. If the
pressure rises above vacuum, open the compressor
dischargeservicevalveandrepeatsteps candd until a
vacuum is maintained.
e. Service or replace components as required and leak
check the compressor.
f. Using refrigerant hoses designed for vacuum service,
connect a vacuum pump to center connection of man-
ifold gauge set. Evacuate system to 500 microns.
Close offpump valve, isolatevacuum gauge andstop
pump. Wait 5 minutes to verify that vacuum holds.
g. Oncevacuum is maintained, re--connect low pressure
switch, disconnect manifoldgauge setand open com-
pressor service valves.
h. Check refrigerant level. Refer to paragraph 4.8.1. It
may be necessary to clear any alarms that have been
generated.
Page view 35
1 2 ... 31 32 33 34 35 36 37 38 39 40 41 ... 55 56

Comments to this Manuals

No comments