Table 2 - *Altitude Compensation for Low NOx Models 48TC04-06 (L, M, N), 48HC04-06 (L, M, N), and 48LC04-06 (L,M,N)
Feet
ELEVATION
Meters
Low NOx Models 580J04-06 and 581J04-06
Low NOx Models RGS036, 048, 060 and RGH036, 048, 060
0 - 2000
2000
3000
4000
5000
6000
7000
8000
9000
10000
11000
12000
13000
14000
0 - 610
610
914
1219
1524
1829
2134
2438
2743
3048
3353
3658
3962
4267
NATURAL GAS ONLY
NOMINAL HEAT INPUT
60k BTUH 90k BTUH 120k BTUH
Orifice Input Orifice Input Orifice Input
Size (btu/hr) Size (btu/hr) Size (btu/hr)
382 60,000 382 90,000 321 120,000
392 55,200 392 82,800 331 110,400
740 52,800 740 79,200 331 105,600
_41 50,400 _41 75,600 351 100,800
_41 48,000 _41 72,000 351 96,000
_42 45,600 _42 68,400 361 91,200
742 43,200 742 64,800 361 86,400
_43 40,800 _43 61,200 372 81,600
_43 38,400 _43 57,600 382 76,800
442 36,000 442 54,000 _40 72,000
442 33,600 442 50,400 _41 67,200
452 31,200 452 46,800 _42 62,400
473 28,800 473 43,200 _43 57,600
483 26,400 483 39,600 _43 52,800
* As the height above sea level increases, there is less oxygen per cubic ft. of air. Therefore, heat input rate
should be reduced at higher altitudes.
1- Not included in kit. May be purchased separately through dealer.
ORIFICE ACC. KIT PN
XX 1 CRLPELEV001A00
XX 2 CRLPELEV002A00
XX 3 CRLPELEV003A00
XX 4 CRLPELEV004A00