a. Disconnect CLO sensor wires connected to CL02 at
the control board. Check wires for continuity. If there
is no continuity, replace the sensor.
b. Connect the multimeter to read voltage between Pin
X on plug PI and ground.
c. Turn unit power on and check the multimeter. Within
a few seconds the meter should indicate 24 v. If it
does not, the control board is defective and must be
replaced.
d. Turn unit power off. Connect a fresh 1.5-v battery to
terminal marked CL02 as shown in Fig. 34.
8. To verify compressor lockout logic;
A CAUTION
The negative (-Ve) pole of the battery must be
connected to the inner terminal and the positive (+ Ve)
pole must be connected to the outer terminal as shown
in Fig. 34
e. Turn unit power on. Make and break the connection
between the outer CL02 terminal and the positive
( + Ve) pole of the battery.
f. If the multimeter shows 24 v when the battery is dis
connected and no voltage when the battery is con
nected, the CLO logic is good. If the multimeter shows
no change, the CLO logic is defective and the board
must be replaced. Remove all jumpers and replace all
plugs except plug PI. (Replace plug PI only if no
further troubleshooting is required.)
Symptom: First or Second Stage of Heating Will Not
Operate.
1. Turn unit power off. Disconnect plugs PI and P3.
2. Check continuity between Pin W1 at plug PI and Pin 5
at plug P3. If there is continuity, the board is good and
the problem is either the connection at P3, or external to
the control board. If there is continuity, the control board
is defective and must be replaced.
3. Check continuity between Pin W2 at plug PI and Pin 7
at plug P3. If there is continuity, the board is good and
the problem is either at the connection at plug P3 or ex
ternal to the board. If there is no continuity, the board is
defective and must be replaced. Reconnect plug P3 to
the control board. (Reconnect plug PI only if no further
troubleshooting is required.)
Symptom: Evaporator Fan Will Not Energize On a Call
For Heat.
1. Turn unit power off. Disconnect plug PI and plug P4.
2. Install jumper wire between Pin R and Pin W1 at plug
PI.
3. Turn unit power on. Check for continuity between Pin 6
and Pin 3 at plug P4 on control board.
4. If there is no continuity between these points, the board
is defective and must be replaced.
NOTE: The control board (part number HK37AA001)
has no time delay.
5. If there is continuity between these points, the problem
is at the connection at plug P4 or external to the control
board.
6. Turn unit power off. Reconnect plugs PI and P4.
ECONOMIZER BOARD CONTINUITY CHECK - The
economizer board is connection board that is used to inter
face the economizer circuit with the base unit and thermo
stat. There are no electronic components or logic built into
this board.
1. Disconnect plugs PI and P5 at the economizer control
board. Disconnect the harness going from the econo
mizer board to the unit control board.
2. Check continuity between points shown below. (See Fig.
35 for identification of points on the board.)
Pl-1 to P4-1
Pl-2 to P4-2
Pl-2 to P5-5
Pl-3 to P4-3
PI-4 to P5-2
P4-4 to P5-3
Pl-5 to P5-1
P4-5 to P5-4
PI-6 to P4-6
Pl-7 to P4-7
Pl-8 to P4-8
Pl-9 to P4-9
P4-10 to P5-6
3. If there is continuity between the above points, the econ
omizer board is good. Reconnect plugs PI and P5 to the
eeonomizer board and eonnect the economizer harness
to the unit control board.
If there is no continuity between the above points, the
economizer board is defective. Replace board.