LEGEND C@
FLA -- Full Load Amps
LRA -- Locked Rotor Amps II_il_
MCA -- Minimum Circuit Amps
MOCP -- Maximum Overcurrent Protection
RLA -- Rated Load Amps
CKT BKR -- Circuit Breaker
NOTES:
1. In compliance with NEC (National Electrical Code) requirements
for multimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the
unit shall be Power Supply fuse. Canadian units may be
fuse or circuit breaker.
2. Minimum wire size is based on 60 C copper wire. If other than
60 C wire is used, or if length exceeds wire length in table,
determine size from NEC.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance yn supply volt-
age is greater than 2%. Use the following formula to determine
the percentage of voltage imbalance.
% Voltage imbalance
= 100 x max voltage deviation from average voltage
average voltage
EXAMPLE: Supply voltage is 460-3-60.
A B c AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage = 452 + 464 + 455
3
= 1371
3
= 457
Determine maximum deviation from average voltage.
(AB) 457 452=5v
(BC) 464 457=7v
(AC) 457 455=2v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x 7
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
supply voltage phase imbalance is]
IMPORTANT: If the
more than 2%, contact your local electric utility company/
immediately.
I
C99024
Fig. 16_Electrical Data Legend
L
@
__
THERMOSTAT
AND SUBBASE
"_BRN--
"J_ORN--
J_--_RED--
"J_GRN--
UNIT CONTROL POWER
SPLICE BOX
C99056
Fig. 17--Control Connections
SINGLE-PHASE
CONNECTIONS
TO DISCONNECT
PER NEC
3-PHASE
CONNECTIONS
LEGEND
NEC - National Electrical Code
- - - Field Wiring
_ Splice Connections
GROUND LUG
N SLPICE BOX
GROUND
LEAD
L1 - /L_BLK--
L2 - _-'_ YEL-
L3 - _L-_BLU--
m
NOTE: Use copper wire onl
C99057
Fig. 18---Line Power Connections
2. Connect the yellow primary lead to the transformer terminal
labeled 200 v.
24 V Circuit Breaker
16
C99070
Fig. 19_Control Wiring Plate
TRANSFORMER CONTAINS A MANUAL
RESET OVERCURRENT PROTECTOR
IT WILL NOT AUTOMATICALLY RESET
DISCONNECT POWER AND INSTALL
LOCKOUT TAG PRIOR TO SERVICING
THIS COMPARTMENT MUST BE CLOSED
EXCEPT WHEN SERVICING
C99058
Fig. 20_Transformer Label
Indoor blower-motor speeds may need to be changed for 208-v
operation. Refer to indoor airflow and airflow adjustments section.