UNIT SIZE
NOMINAL CAPACITY (ton)
OPERATING WEIGHT (lb.)
COMPRESSOR QUANTITY
TYPE
REFRIGERANT
REFRIGERANT METERING DEVICE
Refrigerant (R-22) Quantity (lb.)
ORIFICE ID (in,)
ORIFICE OD (in.)
OUTDOOR COIL
Rows... Fins/in.
Face Area (sq. ft.)
OUTDOOR FAN
Nominal Airflow (CFM)
Diameter
Motor HP (RPM)
INDOOR COIL
Rows... Fins/in.
Face Area (sq. ft.)
INDOOR BLOWER
Nominal Airflow (CFM)
Size (in.)
Motor (HP)
RETURN-AIR FILTERS (in.)
throwaway
Table 2--Physical Data
50JX024 50JX030 50JX036 50JX042
2 2-1/2 3 3-1/2
299 320 328 350
1
SCROLL COMPRESSOR
R-22
AccuRate_
5.5 6.4 7.0 10.8
0.065 0.073 0.076 0.080
0.037 (2) 0.043 (2) 0.040 (2) 0.052 (2)
1...17 2...17 2-.17 2.,,17
13.7 10.3 10.3 13.7
2350 2350 2800 2800
22 22 22 22
1/8 (825) 1/8 (825) 1/4 (1100) 1/8 (825)
3,,.15 3.,.15 4...15 4-.15
3,7 3.7 3.7 4.7
800 1000 1200 1400
10X10 10X10 10X10 11X10
1/4 1/4 1/2 1/2
20X20X1 20X20X1 20X24X1 24X30Xl
50JX048
375
NOTE: Air filter pressure drop for non-standard filters must not exceed 0.08 in. wg.
50JX060
5
428
10.1 12.3
0.088 0.093
0.057 (2) 0,063 (2)
2...17 2._17
13.7 15.7
3300 3300
22 22
1/4(1100) 1/4(1100)
4...15 4.,.15
4.7 5.7
1450 1750
11X10 11X10
1/2 1
24X30X1 24X30X1
Table 3_Minimum Airflow for Reliable Electric Heater Operation (Cfm)
SIZE 50JS018 50JS024 50JS030 50JS036 50JS042 50JS048
AIR FLOW (CFM) 650 800 1000" 1200 1400 1600
• The 030 size models must be run on medium or highspeedwhen usedin conjunctionwith15 kwelectdcheat accessory
50JS060
2000
Table 4_Minimum Airflow for Reliable Electric Heater Operation (Cfm)
SIZE 50JX024 50JXO30 50JX036 50JX042 50JX048
AIRFLOW (CFM) 800 1000" 1200 1400 1600
* The 030 size modelsmust be runon medium or high speed when usedin conjunction with15 kw electdcheat accessory
50JXO6O
2000
9