Roof Curb for Small Cabinet
Note A: When unit mounting screw is used,
retainer bracket must also be used.
VAC unrl
base "_
_ _(NOTE A) _
supplied _
Ir_ulaUon (field
Roofir_ material supplied)
field suPPlied m
eu_i work
_Cant strip field supplied
field su_l_d
Roof Curb for Large Cabinet
Note A: Whenunitmounting screwis used,
retainerbracketmustalsobe used.
R/A S/A
Insulated Gasket around
deck pan outer edge
UNIT SIZE
50JS018-042 50JX024-036
50JS048-060 50JX042-060
NOTES:
ODS CATALOG NUMBER
CPRFCURB006A00
CPRFCURS007A00
CPRFCURB008A00
CPRFCURB009A00
A
IN. (MM)
8 (203)
14 (386)
8 (203)
14 (356)
B
IN. (MM)
11 (279)
11 (279)
16 3/16 (411)
16 3/16 (411)
C
IN. (MM)
161/2 (419)
161/2 (419)
17 3/8 (441)
17 3/8 (441)
C00076
D
IN. (MM)
28-3/4 (730)
28-3/4 (730)
40-1/4 (1022)
40-1/4 (1022)
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as requiRd, to unit being installed.
3. Dimensions in ( ) are in millimeters.
4. Roof curb is made of 16-gage steel.
5. Table lists only the dimensions, per part number, that have changed.
6. Attach ductwork to curb (flanges of duct rest on curb).
7. Insulated panels: t-in. thick fiberglass 1 Ib density.
8. Dimensions are in inches.
9. When unit mounting screw is used (see Note A, a retainer bracket must be used as well• This bracket must also be used when required by code for hurricane or
seismic conditions. This bracket is available through MicrornetL
Fig. 5_Roof Curb Dimensions
4. Ensure the side duct covers are in place to block off the
horizontal air openings.
NOTE: Avoid abrupt duct size increases and reductions. Abrupt
change in duct size adversely affects air pedormance.
Step C0---Provide for Condensate Disposal
NOTE: Ensure that condensate-water disposal methods comply
with local codes, restrictions, and practices.
The units dispose of condensate through a 3/4 in. NPT female
fitting that exits on the compressor end of the unit. Condensate
water can be drained directly onto the roof in rooftop installations
(where permitted) or onto a gravel apron in ground level installa-
tions. Install a field-supplied condensate trap at end of condensate
connection to ensure proper drainage. Make sure that the outlet of
the trap is at least 1 in. lower than the drain-pan condensate