Copyright 2009 Carrier Corporation Form 50PS-5PD
Single-package horizontally and verti-
cally mounted water source heat
pumps with electronic controls offer:
Non-ozone depleting Puron
refrigerant (R-410A)
State-of-the-art electronically
commutated motor (ECM) variable
speed blower motor option
Stainless steel drain pan
E-coated air coil available
Mute package for quieter operation
available
Versatility: apply to commercial
boiler/cooling tower or geothermal
applications (select extended range
option for use in geothermal
applications)
Performance certified to ARI/ISO
13256-1:1998
Flexible and reliable multiple
protocol WSHP Open controller can
use BACnet
, Modbus
®
, N2, and
LON (with a separate card)
protocols for integrating energy
efficiency and precise unit control
Modulating hot water reheat (HWR)
available for dehumidification
capability
Features/Benefits
The Aquazone single-stage
water source heat pump with
Puron refrigerant (R-410A) is
a high quality, efficient
solution for all boiler/tower
and geothermal applications.
Operating efficiency
Carrier water source heat pumps
(WSHPs) are designed for quality and
high performance over a lifetime of
operation. Single-stage WSHP models
with Puron refrigerant (R-410A) offer
cooling EERs (Energy Efficiency Ra-
tios) to 27.4 and heating COPs (Coeffi-
ciency of Performance) to 5.9.
AQUAZONE
50PSH, PSV, PSD006-070
Single-Stage Water Source
Heat Pumps
with PURON
®
Refrigerant (R-410A)
1
/
2
to 6 Nominal To n s
Product
Data
Well exceeds
ASHRAE 90.1 and
Energy Star Standards.
Page view 0
1 2 3 4 5 6 ... 67 68

Summary of Contents

Page 1 - Features/Benefits

Copyright 2009 Carrier Corporation Form 50PS-5PDSingle-package horizontally and verti-cally mounted water source heat pumps with electronic controls o

Page 2 - Table of contents

10SPT Plus offers space temperature sensor with set pointadjust, local override with indicating light and communica-tion port.SPT Pro offers space tem

Page 3

11COOLHEATAUTOR5-DAY PROGRAMMABLE/NON-PROGRAMMABLEAUTOPmCOOLHEATCarrier®AQUAZONE™ THERMOSTATS7-DAY PROGRAMMABLE/LIGHT-ACTIVATED PROGRAMMABLE7-DAY PROG

Page 4

12Dimensions50PSH006-070 UNITSNOTES:1. Condensate is 3/4-in. FPT copper.2. Horizontal unit shipped with filter bracket only. This bracket should berem

Page 5 - Model number nomenclature

1350PSV006-070 UNITSNOTES:1. Condensate is 3/4-in. FPT copper and is switchable from side to front.2. Vertical unit shipped with filter bracket only,

Page 6 - ARI/ISO capacity ratings

14Dimensions (cont)2' ServiceAccess Air Coil SideGFDKJL43215CAPTURSAir CoilCSPFrontBackFront-ViewBSPLeft Return Left View -Air Coil OpeningConde

Page 7 - Physical data

15I Determine the actual cooling and heatingloads at the desired dry bulb and wet bulbconditions.Given:Total Cooling (TC) . . . . . . . . . . . . . .

Page 8 - Options and accessories

1650PSH,PSV006240 CFM NOMINAL AIRFLOW COOLING/240 CFM NOMINAL AIRFLOW HEATING — PSC BLOWERLEGEND NOTES:1. Interpolation is permissible; extrapolation

Page 9 - Field-installed accessories

1750PSH,PSV009300 CFM NOMINAL AIRFLOW COOLING/300 CFM NOMINAL AIRFLOW HEATING — PSC BLOWERLEGEND NOTES:1. Interpolation is permissible; extrapolation

Page 10

1850PSH,PSV012350 CFM NOMINAL AIRFLOW COOLING/350 CFM NOMINAL AIRFLOW HEATING — PSC BLOWERLEGEND NOTES:1. Interpolation is permissible; extrapolation

Page 11 - WSHP OPEN SENSORS

1950PSH,PSV,PSD018600 CFM NOMINAL AIRFLOW COOLING/600 CFM NOMINAL AIRFLOW HEATING — PSC BLOWERLEGEND NOTES:1. Interpolation is permissible; extrapolat

Page 12 - Dimensions

2All efficiencies stated are in accordance with standard conditions under ISO (In-ternational Organization for Standard-ization) Standard 13256-1:1998

Page 13 - 50PSV006-070 UNITS

2050PSH,PSV,PSD024850 CFM NOMINAL AIRFLOW COOLING/850 CFM NOMINAL AIRFLOW HEATING — PSC BLOWERLEGEND NOTES:1. Interpolation is permissible; extrapolat

Page 14 - Dimensions (cont)

2150PSH,PSV,PSD030950 CFM NOMINAL AIRFLOW COOLING/950 CFM NOMINAL AIRFLOW HEATING — PSC BLOWERLEGEND NOTES:1. Interpolation is permissible; extrapolat

Page 15

2250PSH,PSV,PSD0361,250 CFM NOMINAL AIRFLOW COOLING/1,250 CFM NOMINAL AIRFLOW HEATING — PSC BLOWERLEGEND NOTES:1. Interpolation is permissible; extrap

Page 16 - Performance data

2350PSH,PSV,PSD0421,400 CFM NOMINAL AIRFLOW COOLING/1,400 CFM NOMINAL AIRFLOW HEATING — PSC BLOWERLEGEND NOTES:1. Interpolation is permissible; extrap

Page 17 - 50PSH,PSV009

2450PSH,PSV,PSD0481,600 CFM NOMINAL AIRFLOW COOLING/1,600 CFM NOMINAL AIRFLOW HEATING — PSC BLOWERLEGEND NOTES:1. Interpolation is permissible; extrap

Page 18 - Performance data (cont)

2550PSH,PSV,PSD0601,950 CFM NOMINAL AIRFLOW COOLING/1,950 CFM NOMINAL AIRFLOW HEATING — PSC BLOWERLEGEND NOTES:1. Interpolation is permissible; extrap

Page 19 - 50PSH,PSV,PSD018

2650PSH,PSV,PSD0702,100 CFM NOMINAL AIRFLOW COOLING/2,100 CFM NOMINAL AIRFLOW HEATING — PSC BLOWERLEGEND NOTES:1. Interpolation is permissible; extrap

Page 20

2750PSH,PSV,PSD018700 CFM NOMINAL AIRFLOW COOLING/700 CFM NOMINAL AIRFLOW HEATING — ECM BLOWERLEGEND NOTES:1. Interpolation is permissible; extrapolat

Page 21 - 50PSH,PSV,PSD030

2850PSH,PSV,PSD024850 CFM NOMINAL AIRFLOW COOLING/950 CFM NOMINAL AIRFLOW HEATING — ECM BLOWERLEGEND NOTES:1. Interpolation is permissible; extrapolat

Page 22

2950PSH,PSV,PSD0301,000 CFM NOMINAL AIRFLOW COOLING/1,100 CFM NOMINAL AIRFLOW HEATING — ECM BLOWERLEGEND NOTES:1. Interpolation is permissible; extrap

Page 23 - 50PSH,PSV,PSD042

3E-coated (electro-coated) air coilsThe 50PSH, PSV, PSD units are avail-able with an optional e-coated air coil. This electro-coating process will pro

Page 24

3050PSH,PSV,PSD0361,250 CFM NOMINAL AIRFLOW COOLING/1,250 CFM NOMINAL AIRFLOW HEATING — ECM BLOWERLEGEND NOTES:1. Interpolation is permissible; extrap

Page 25 - 50PSH,PSV,PSD060

3150PSH,PSV,PSD0421,400 CFM NOMINAL AIRFLOW COOLING/1,400 CFM NOMINAL AIRFLOW HEATING — ECM BLOWERLEGEND NOTES:1. Interpolation is permissible; extrap

Page 26

3250PSH,PSV,PSD0481,550 CFM NOMINAL AIRFLOW COOLING/1,650 CFM NOMINAL AIRFLOW HEATING — ECM BLOWERLEGEND NOTES:1. Interpolation is permissible; extrap

Page 27

3350PSH,PSV,PSD0601,825 CFM NOMINAL AIRFLOW COOLING/2,050 CFM NOMINAL AIRFLOW HEATING — ECM BLOWERLEGEND NOTES:1. Interpolation is permissible; extrap

Page 28

3450PSH,PSV,PSD0701,950 CFM NOMINAL AIRFLOW COOLING/2,100 CFM NOMINAL AIRFLOW HEATING — ECM BLOWERLEGEND NOTES:1. Interpolation is permissible; extrap

Page 29

35ENTERING AIR CORRECTION TABLELEGEND *Sensible capacity equals total capacity.AIRFLOW CORRECTION TABLEECM AIRFLOW LEGEND*Sensible

Page 30

36PSC BLOWER MOTOR PERFORMANCE DATA LEGENDNOTES:1. Shaded areas denote ESP where operation is not recommended.2. Units factory sh

Page 31

37PSC BLOWER MOTOR PERFORMANCE DATA FOR 50PS UNITS WITH HWR*LEGEND *HWR not available on 50PS006-012 units.NOTE: For units with HWR coil applications,

Page 32

38SOUND DATA — DUCTED DISCHARGE WITH STANDARD CONSTRUCTIONNOTE: All performance is Sound Power Level in dB referenced to 1 picoWatt.50PS UNIT MODEDUCT

Page 33

39SOUND DATA — CASE RADIATED WITH STANDARD CONSTRUCTIONNOTE: All performance is Sound Power Level in dB referenced to 1 picoWatt.50PS UNIT MODEFREE AI

Page 34

4Accessory output — A 24-v output is provided to cycle a motorized water valve or damper actuator with com-pressor in applications such as variable sp

Page 35 - AIRFLOW CORRECTION TABLE

40SOUND DATA — CASE RADIATED WITH MUTE CONSTRUCTIONNOTE: All performance is Sound Power Level in dB referenced to 1 picoWatt.50PS UNIT MODEFREE AIR IN

Page 36

4150PSH, PSV, PSD STANDARD PSC MOTOR ELECTRICAL DATALEGEND50PSUNITSIZERATEDVOLTAGEV-Ph-HzVOLTAGEMIN/MAXCOMPRESSORFANMOTORFLATOTALUNITFLAMINCIRCUITAMPM

Page 37

4250PSH, PSV, PSD HIGH-STATIC PSC MOTOR ELECTRICAL DATALEGEND50PSUNITSIZERATEDVOLTAGEV-Ph-HzVOLTAGEMIN/MAXCOMPRESSORFANMOTORFLATOTALUNITFLAMINCIRCUITA

Page 38

4350PSH, PSV, PSD ECM MOTOR ELECTRICAL DATA LEGENDNOTE: 460V with ECM motor requires a neutral wire.50PSUNI

Page 39 - 50PS UNIT MODE

44Typical piping and wiringTYPICAL PIPING AND WIRING INSTALLATIONA50-7728ef

Page 40

45Typical control wiring schematicsUNITS WITH COMPLETE C CONTROLLER, SINGLE-PHASE*Optional.AL — Alarm Relay ContactsASTAT — AquastatBR — Blower RelayC

Page 41 - Electrical data

46Typical control wiring schematics (cont)UNITS WITH DELUXE D CONTROLLER, THREE-PHASE (460/575 V)*Optional.AL — Alarm Relay ContactsASTAT — AquastatBM

Page 42 - Electrical data (cont)

47UNITS WITH COMPLETE C ECM BLOWER, THREE-PHASE (208/230 V)*Optional.AL — Alarm Relay ContactsASTAT — AquastatBM — Blower MotorBR — Blower RelayCB — C

Page 43

48Typical control wiring schematics (cont)Wire NutRelay Contacts - N.C.Relay Contacts - N.O.Low Pressure SwitchHigh Pressure SwitchSplice CapCircuit B

Page 44 - Typical piping and wiring

49NOTES:1. Compressor and blower motor thermally protected internally.2. All wiring to the unit must comply with NEC and local codes.3. Transformer is

Page 45

5Sensor Link (S-Link) communication protocol completes a system of net-worked control.Humidity control — Aquazone 50PSH, PSV, PSD units provide very g

Page 46

50Typical control wiring schematics (cont)Wire NutRelay Contacts - N.C.Relay Contacts - N.O.Low Pressure SwitchHigh Pressure SwitchSplice CapCircuit B

Page 47

51Wire NutRelay Contacts - N.C.Relay Contacts - N.O.Low Pressure SwitchHigh Pressure SwitchSplice CapCircuit BreakerCapacitorLEDUNITS WITH COMPLETE C

Page 48 - Complete C

52Typical control wiring schematics (cont)WSHP OPEN CONTROL012207-1BT485BTLED1DBInstall BT485 where device is located at the end of network segment on

Page 49

53Aquazone™ water source heat pump products are availablein a flexible, efficient array of models, which can be used inall types of water loop, ground

Page 50

54conditions, heating, and cooling requirements of the appli-cation and system design.Vertical ground loop — This system is used in verticalborehole a

Page 51

55WATER QUALITY GUIDELINESLEGEND*Heat exchanger materials considered are copper, cupronickel, 304 SS(stainless steel), 316 SS, titanium.†Closed recirc

Page 52 - WSHP OPEN CONTROL

56COMPLETE C AND DELUXE D ELECTRONIC CONTROL FEATURES COMPARISONLEGENDBASIC FEATURES COMPLETE CCOMPLETE CWITH LONDELUXE DDELUXE D WITH LONCOMPLETE C O

Page 53 - Application data

57Acoustical designSound power levels represent the sound as it is producedby the source, the WSHP unit, with no regard to attenua-tion between the so

Page 54 - Application data (cont)

58Vertical unitsAll guidelines established for horizontal units also apply forvertical units. In addition, since vertical units tend to be in-stalled

Page 55 - WATER QUALITY GUIDELINES

59WSHP Open sequence of operationThe WSHP Open multi-protocol controller will control me-chanical cooling, heating and waterside economizer out-puts b

Page 56

6LEGENDNOTES:1. Cooling capacities based upon 80.6 F db, 66.2 F wb entering airtemperature.2. Heating capacities based upon 68 F db, 59 F wb entering

Page 57 - Horizontal units

60Cooling — The WSHP Open controller will operate oneor two stages of compression to maintain the desired cool-ing set point. The compressor outputs a

Page 58

61connected to a coil on the discharge side of the unit andsupplied by a boiler or a single-stage ducted electric heaterin order to maintain the desir

Page 59 - Controls

62• If unoccupied, the SPT is greater than the unoccupiedcooling set point or less than the unoccupied heating setpoint and the condenser water is sui

Page 60 - Controls (cont)

63Single-Stage Water Source Heat Pumps withPuron® Refrigerant (R-410A)HVAC Guide SpecificationsSize Range: 6,300 to 77,100 BtuhCooling Capacity4,800 t

Page 61

643. The compressor shall have a dual level vibrationisolation system.4. The compressor will be mounted on computer-selected vibration isolation sprin

Page 62

65thermostat must be provided to preventover-cooling an already cold room.I. Controls and Safeties:1. Electrical:a. A control box shall be located wit

Page 63 - Guide specifications

66i. Single grounded wire to initiate night setback,or emergency shutdown.j. Boilerless system control can switch automati-cally to electric heat at l

Page 64 - Guide specifications (cont)

67allowing for connection to a flexible hose with-out the use of a back-up wrench.2. All water connections and electrical knockoutsmust be in the comp

Page 65

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Pg 6

Page 66

7LEGEND*Unit sizes 006-012 not available on 50PSD unit.NOTE: All units have spring compressor mountings, TXV expansiondevices, and 1/2-in. and 3/4-in.

Page 67

8Factory-installed optionsCupronickel heat exchangers are available for highercorrosion protection for applications such as open tower,geothermal, etc

Page 68

9LONMark® compliant controller contains the factory-loaded Aquazone™ water source heat pump application foran interoperable control solution.Permanent