Copyright 2009 Carrier Corporation Form 50PEC-3PD
Single-package console water source
heat pump with self-contained line
voltage thermostats.
Non-ozone depleting Puron
refrigerant (R-410A)
Suitable for either geothermal or
boiler/tower applications with
operating temperature range from
20 F to 110 F.
Thermostatic expansion valve (TXV)
Rubber grommet mounted
compressors for quiet operation
Sloped top cabinet
Right or left hand piping connection
Multiple unit-mounted and remote
thermostat options
Adaptable cabinet and subbase
configurations
Factory-mounted flow regulators and
control valves for easy installation
Flexible and reliable multiple
protocol WSHP Open controller can
use BACnet
, Modbus
®
, N2, and
LON (with a separate card)
protocols for integrating energy
efficiency and precise unit control
Features/Benefits
Carrier’s Aquazone console
water source heat pumps are
a flexible, attractive
alternative for all finished
interior space, under-window
style installations.
Operating efficiency
Aquazone water source heat pump
(WSHP) units are designed for quality
and performance excellence over their
lifetime. Units offer standard cooling
EERs (energy efficiency ratios) up to
13.5 for boiler/tower systems and as
high as 21.3 for geothermal applica-
tions. Heating COPs (coefficients of
performance) are as high as 5.1,
among the highest in the industry.
AQUAZONE
50PEC09-18
Water Source Heat Pumps
Console Unit
with PURON
®
Refrigerant
(R-410A)
3
/
4
to 1
1
/
2
Nominal Tons
Product
Data
TM
Page view 0
1 2 3 4 5 6 ... 51 52

Summary of Contents

Page 1 - Features/Benefits

Copyright 2009 Carrier Corporation Form 50PEC-3PDSingle-package console water source heat pump with self-contained line voltage thermostats.• Non-ozon

Page 2 - Table of contents

10Options and accessories (cont)COOLHEATAUTOR5-DAY PROGRAMMABLE/NON-PROGRAMMABLEAUTOPmCOOLHEATCarrier®AQUAZONE™ THERMOSTATS7-DAY PROGRAMMABLE/LIGHT-AC

Page 3 - PremierLink™ controller adds

11DimensionsNOTES:1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.2. Access is reduced if optional disconnect box is s

Page 4

12Dimensions (cont)NOTES:1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.2. Access is reduced if optional disconnect b

Page 5 - Model number nomenclature

13a50-8341NOTES:1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.2. Access is reduced if optional disconnect box is sel

Page 6 - ARI/ISO capacity ratings

14Dimensions (cont)NOTES:1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.2. Access is reduced if optional disconnect b

Page 7 - Options and accessories

15a50-8343NOTES:1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.2. Access is reduced if optional disconnect box is sel

Page 8 - Field-installed accessories

16Dimensions (cont)a50-8344NOTES:1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.2. Access is reduced if optional disc

Page 9

17°(89)L.H.(NOTE 2).50 (13)11.50(292).75(19)4.12(105)(Note 2)a50-8345NOTES:1. Dimensions are shown in inches. Dimensions in parentheses are in millime

Page 10 - WSHP OPEN SENSORS

18Dimensions (cont)a50-8346NOTES:1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.2. Access is reduced if optional disc

Page 11 - Dimensions

19Power SupplyBlower DeckBlower Access PanelCompressorAccessPanelControl Box40.98(1041)4.46(113)0.75(19)0.75(19)*20.50(521)11.54(293)*16.66(423)30°0.8

Page 12 - Dimensions (cont)

2Quiet operationThe Carrier console WSHP provides exceptionally quiet operation for maxi-mum comfort.Design flexibilityAquazone™ console WSHP units ar

Page 13

20Dimensions (cont)NOTES:1. Dimensions shown are in inches. Dimensions in parentheses are in millimeters.2. Optional autoflow valve, motorized water v

Page 14

21Blower DeckBlower Access PanelCompressorAccessPanelControl Box46.98(1193)4.49(114)0.75(19)0.75(19)*20.50(521)Hard WirePower SupplyBlower DeckBlower

Page 15

22Dimensions (cont)Blower DeckCompressorAccessPanelControl Box46.98(1193)4.49(114)0.75(19)0.75(19)20.50(521)Hard WirePower SupplyBlower DeckFilterComp

Page 16

23I Determine the actual cooling and heatingloads at the desired dry bulb and wet bulbconditions.Given:Total Cooling (TC). . . . . . . . . . . . . . .

Page 17

24VII ARI/ISO 13256-1 ConversionPerformance standard ARI/ISO 13256-1 becameeffective on January 1, 2000 and replaced the exist-ing ARI Standards 320 W

Page 18

2550PEC09 — NOMINAL AIRFLOW 350 CFMLEGEND NOTES:1. Interpolation is permissible; extrapolation is not.2. All entering air conditions are 80 F db and 6

Page 19

2650PEC12 — NOMINAL AIRFLOW 450 CFMLEGEND NOTES:1. Interpolation is permissible; extrapolation is not.2. All entering air conditions are 80 F db and 6

Page 20 - Power Supply

2750PEC15 — NOMINAL AIRFLOW 520 CFMLEGEND NOTES:1. Interpolation is permissible; extrapolation is not.2. All entering air conditions are 80 F db and 6

Page 21 - Condensate

2850PEC18 — NOMINAL AIRFLOW 620 CFMLEGEND NOTES:1. Interpolation is permissible; extrapolation is not.2. All entering air conditions are 80 F db and 6

Page 22

29CORRECTION FACTORS — ENTERING AIR — HEATINGCORRECTION FACTORS — ENTERING AIR — COOLINGLEGEND *Sensible capacity equals total capacity.NOTES:1. ARI/I

Page 23

3High and low pressure refrigerant protection — Safeguards against unreliable unit operation and prevents refrigerant from leaking.Condensate overflow

Page 24 - Selection procedure (cont)

30Aquazone™ water source heat pump products are availablein a flexible, efficient array of models, which can be used inall types of water loop, ground

Page 25 - Performance data

31pipe inserted into a hole. The hole is back-filled andgrouted after the pipe is inserted. The completed loop isconcealed below ground. The number of

Page 26 - Performance data (cont)

32Some of the factors that affect conversion of soundpower to sound pressure and consequent NC level include:• Type of acoustical ceiling• Use of meta

Page 27

33COMPLETE C AND DELUXE D ELECTRONIC CONTROL FEATURES COMPARISONLEGENDBASIC FEATURES COMPLETE CCOMPLETE CWITH LONDELUXE DDELUXE D WITH LONCOMPLETE C O

Page 28

34ANTIFREEZE CORRECTION TABLELEGENDElectrical dataLEGENDANTIFREEZE TYPEANTIFREEZE %COOLING HEATINGWPD CORRECTION FACTOREWT 30 FEWT 90 F EWT 30 FTotal

Page 29 - CORRECTION FACTORS — AIRFLOW

35WSHP Open sequence of operationThe WSHP Open multi-protocol controller will control me-chanical cooling, heating and waterside economizer out-puts b

Page 30 - Application data

36• Condensate overflow input is normal.• If occupied, the SPT is greater than the occupied cool-ing set point.• Space temperature reading is valid.•

Page 31 - Acoustical design

37connected to a coil on the discharge side of the unit andsupplied by a boiler in order to maintain the desired heat-ing set point should the compres

Page 32 - Application data (cont)

38the entering water loop temperature is suitable (at least5 F below space temperature). If the optional coil is pro-vided and the water loop conditi

Page 33

39Typical control wiring schematicsLEGENDNOTES:1. Compressor and blower motor thermally pro-tected internally.2. All wiring to the unit must comply wi

Page 34 - Electrical data

4The PremierLink™ peer-to-peer, In-ternet ready communicating control is designed specifically for constant vol-ume (CV) and variable volume and temp

Page 35 - Controls

40Typical control wiring schematics (cont)LEGENDNOTES:1. Compressor and blower motor thermally pro-tected internally.2. All wiring to the unit must co

Page 36 - Controls (cont)

41*Optional wiring.AL — Alarm Relay ContactsBM — Blower MotorCAP — CapacitorCB — Circuit BreakerCO — Sensor, Condensate OverflowCR — Compressor RelayD

Page 37

42Typical control wiring schematics (cont)*Optional wiring.AL — Alarm Relay ContactsBM — Blower MotorBR — Blower RelayCAP — CapacitorCB — Circuit Brea

Page 38

43COMPLETECCONTROLBRCRCAPPBGROUNDTRANSFORMERBRN YELYWOGRCAL1AL2AP1ALARMRELAYSEENOTE 6JW1WVCOMPRESSORCOOLINGFAN24 VACCOMMONALARMCLASS 1 WIRINGREQUIRED

Page 39 - Complete C

44Typical control wiring schematics (cont)AL — Alarm Relay ContactsBR — Blower RelayCAP — CapacitorCB — Circuit BreakerCO — Sensor, Condensate Overflo

Page 40 - COMPLETE C

45WSHP OPEN CONTROL012207-1BT485BTLED1DBInstall BT485 where device is located at the end of network segment only.+ 24vac(If not installed, it must be

Page 41 - DELUXE D

46Typical control wiring schematics (cont)Y1GRCAL1CMP1FANPWRPREMIERLINKDELUXEDCONTROLJ4J8J1PWRCMPSAFEHS2HS1CMP2Y2W1O/W2J6J5SPTSATLWTLEGENDNOTE: Revers

Page 42 - PEC09-18

47Typical pipingLEGEND*Dimension reduced by fitting if selected.NOTE: Dimensions shown are in inches. Dimensions in parentheses are in millimeters.EPT

Page 43

48Typical piping (cont)LEGEND*Dimension reduced by fitting if selected.NOTE: Dimensions shown are in inches. Dimensions in parentheses are in millimet

Page 44

49Console Water Source Heat PumpsHVAC Guide SpecificationsSize Range: 8,600 to 16,200 BtuhCooling Capacity11,400 to 20,100 BtuhHeating CapacityCarrier

Page 45 - WSHP OPEN CONTROL

5Model number nomenclatureAquazone™ Water Source Heat PumpConsole Unit with Puron® Refrigerant (R-410A)**WWSHP Open Multiple Protocol Communicating Co

Page 46

501. Electrical:A control box shall be located within the unitand shall contain controls for compressor,reversing valve and fan motor operation.2. Pip

Page 47 - Typical piping

51will permit all units to be daisy chain connectedby a 2-wire twisted pair shielded cable. The fol-lowing points must be available at a central orrem

Page 48 - Typical piping (cont)

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Pg 5

Page 49 - Guide specifications

6LEGEND NOTES:1. Ratings are in accordance with and certified to ARI/ISO Standard13256-1.2. Cooling capacities based upon 80.6 F db, 66.2 F wb enterin

Page 50 - Guide specifications (cont)

7Factory-installed optionsCupronickel heat exchangers are available for highercorrosion protection for applications such as open tower,geothermal, etc

Page 51

8falls below 50 F. When return-air temperature is raisedabove 55 F the compressor and blower stop.Override function — An override function is availabl

Page 52

9Solenoid valves (brass body) offer 3.5 watt coil,24 volt, 50/60 Hz, 740 amps inrush, .312 amps holding.Slow operation for quiet system application.