Step 8 — Make Connections Between Indoor
and Outdoor Units —
The thermostat is wired between
the indoor and outdoor units to make the system complete.
CHECK ACCURATER METERING DEVICE — The cor-
rect AccuRater (bypass type) refrigerant control is required for
system capacity optimization. An AccuRater device
(see Fig. 19) is supplied with the outdoor unit. Refer to
Tables 4A-4C to determine the correct AccuRater piston size
and charge combination required for the condenser/evaporator
system being installed.
Piston style as shown in Fig. 19 is shipped with the unit.
Do not interchange components between the AccuRater device
types.
COOLING ONLY SYSTEMS The following connec-
tions must be made to the outdoor unit for it to operate as a sys-
tem with the indoor unit:
Route 2 wires of field-supplied 18-gage AWG (American
Wire Gage) thermostat cable between the low-voltage terminal
block of the fan coil unit and the blue and brown low-voltage
wires in the outdoor unit low voltage terminal block. Connect
the wires Y1 to Y and C to C. See Fig. 20.
HEAT PUMP SYSTEMS — The following connections
must be made to the outdoor unit for it to operate as a system
with the indoor unit:
Route 5 wires of field-supplied 18-gage AWG thermostat
cable between the low-voltage terminal block of the fan coil
and the outdoor unit low-voltage terminal block. Connect Y1
to Y, R to R, O to O, W2 to W2, and C to C with the wires. See
Fig. 21.
The heat pump unit uses a timed defrost method. The timed
defrost can be field set for 30, 50, or 90 minutes. The timed de-
frost is factory set for 90 minutes.
38HDR018-060
38QRR018-060
Fig. 19 — AccuRater (Bypass Type)
Metering Device Components