2-6
T--295
Table 2-3. Parameter Codes
CODE
CODE NAME DESCRIPTION
P1 Return Air
Temperature
This value is the temperature measured by the return air sensor. If the sensor is
shorted it will display CL. If it is open circuited it will display OP.
P2 Coil Temperature This value i s the coil temperature measured by the evaporator temperature sen-
sor. If the sensor is shorted it will display CL. If it is open circuited it will dis-
play OP.
P3 Ambient Temperature This value is the outside temperature measured by the ambient temperat ure
sensor. If the sensor is shorted it will display CL. If it is open circuited it will
display OP.
P4 Suction Line Temper-
ature
Not used.
P5 Suction Pressure This value is the suction pressure measured by the suction pressure transducer.
If the sensor is shorted it will display CL If it is open circuited it will display
OP.
P6 Discharge Pressure This value is the discharge pressure measured by the discharge pressure trans-
ducer. If the sensor is shorted it will display “CL” and if it is open circuited i t
will display “OP”.
P7 Superheat Not used.
P8 Analog Set Point
Temperature
Not used.
P9 A/C Control Window
#1
This is the number of degrees F above setpoint at which the unloaders will be
both energized. This value can be modified between 0 and 10 degrees F. The
default value is 1 degree F.
P10 A/C Control Window
#2
This is the number of degrees F above AC control window one at which the
first unloader will be energized. This value can be modified between 0 and 10
degrees F. The default value is 1 degree F.
P11 A/C Control Window
#3
This is the number of degrees F above AC control window two at which the
evaporator fan speed will be set to low. This value can be modified between 0
and 10 degrees F. The default value is 1 degree F.
P12 Heat Control Window This is the number of degrees F below setpoint before the heat valve is energi-
zed. This value can be modified between 0 and 10 degrees F. The default value
is 2 degree F for heat and 4 degrees F for reheat.
P13 Compressor Safety
Off Delay
This number is the minimum time in minutes that the compressor must be off
after a high or low pressure alarm before it can be restarted. This value can be
modified between one and five minutes. The default value is 1.
P14 Fan Delay This is the minimum time (in seconds) that the fans must run at a particular
speed before changing to another speed. This value can be modified between
one and 60 seconds. The default value is two seconds.
P15 Unloader/Heat Valve
Delay
This is the minimum time (in seconds) that the unloaders and heat valve must
be in a particular state (open /closed) before changing to another state. This
value can be modified between 1 and 60 seconds. The default value is 2 sec-
onds.
P16 Compressor High
Pressure Switch
This is the current state of the compressor high pressure switch input. “CL”
will be displayed i f it is closed and “OP” will be displayed if it is open.
P17 Condenser Fan Speed
Switch
Not used.